Home |
Search |
Today's Posts |
![]() |
|
UK diy (uk.d-i-y) For the discussion of all topics related to diy (do-it-yourself) in the UK. All levels of experience and proficency are welcome to join in to ask questions or offer solutions. |
Reply |
|
LinkBack | Thread Tools | Display Modes |
#1
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
We are having a problem with some sort of airlock - a buzzing noise. I
live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. |
#2
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On 09/04/2021 15:38, Scott wrote:
We are having a problem with some sort of airlock - a buzzing noise. I live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. The idea of the air column is to provide an air cushion to stop the water hammer. It should be filled with air, and you also hope that trapped air in the cold water supply will keep the air pocket topped up. Changing the valve to another type can also change the precise characteristics and stop the resonance. It's all very hit and miss. Even moving the float can change the resonance of the float arm and make a difference. |
#3
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On 09/04/2021 15:38, Scott wrote:
We are having a problem with some sort of airlock - a buzzing noise. I live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. Its a worn out ball cock valve. The valve is not shutting off cleanly when the tank reaches its final water level. the buzzing sounds is caused by the ball bobbing up and down in the water which is causing a pressure ripple through the rising main and hence the sound you hear. although you could replace the washer, its better to replace the whole thing. |
#4
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
In article ,
Fredxx wrote: On 09/04/2021 15:38, Scott wrote: We are having a problem with some sort of airlock - a buzzing noise. I live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. The idea of the air column is to provide an air cushion to stop the water hammer. It should be filled with air, and you also hope that trapped air in the cold water supply will keep the air pocket topped up. Changing the valve to another type can also change the precise characteristics and stop the resonance. It's all very hit and miss. Even moving the float can change the resonance of the float arm and make a difference. with our last tank, I fitted a "damper plate" to stop the valve shutting off too quickly. Worked perfectly. -- from KT24 in Surrey, England "I'd rather die of exhaustion than die of boredom" Thomas Carlyle |
#5
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On Fri, 9 Apr 2021 15:52:07 +0100, SH wrote:
On 09/04/2021 15:38, Scott wrote: We are having a problem with some sort of airlock - a buzzing noise. I live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. Its a worn out ball cock valve. The valve is not shutting off cleanly when the tank reaches its final water level. the buzzing sounds is caused by the ball bobbing up and down in the water which is causing a pressure ripple through the rising main and hence the sound you hear. although you could replace the washer, its better to replace the whole thing. This is interesting. The 'argument' I alluded to is that two of my neighbours think the problem is with the toilet in the first floor flat. I think the noise is permeating the whole pipe and thought we should start at the top (where I assumed the air would be). Of course both these installations include a ballcock valve. Is there any way of knowing which of the two valves needs to be replaced. From my point of view, if it's in the downstairs flat, it's an enforcement problem and if it's in the loft it's a funding problem (though I would be inclined to go ahead with repairs in the loft if I could confirm the fault). |
#6
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On 09/04/2021 16:17, Scott wrote:
On Fri, 9 Apr 2021 15:52:07 +0100, SH wrote: On 09/04/2021 15:38, Scott wrote: We are having a problem with some sort of airlock - a buzzing noise. I live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. Its a worn out ball cock valve. The valve is not shutting off cleanly when the tank reaches its final water level. the buzzing sounds is caused by the ball bobbing up and down in the water which is causing a pressure ripple through the rising main and hence the sound you hear. although you could replace the washer, its better to replace the whole thing. This is interesting. The 'argument' I alluded to is that two of my neighbours think the problem is with the toilet in the first floor flat. I think the noise is permeating the whole pipe and thought we should start at the top (where I assumed the air would be). Of course both these installations include a ballcock valve. Is there any way of knowing which of the two valves needs to be replaced. From my point of view, if it's in the downstairs flat, it's an enforcement problem and if it's in the loft it's a funding problem (though I would be inclined to go ahead with repairs in the loft if I could confirm the fault). Tie up the ball cock in the loft tank with some string. Then flush all the toilets one by one in the building and use your ears or even a stethosope on teh pipework to see which one then buzzes as the toilet cistern approaches its final cistern water level. Once you've identified the problematic toilets, you can then release the ball valve in the loft tank. Listen to this to see if it buzzes as it reaches final tank level. (the loft tank will be several hundred litres of capacity and the typical toilet cistern is around 3 to 6 litres.) Then order and replace the toilet and/or ball cock valves as required. |
#7
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On Fri, 9 Apr 2021 16:34:53 +0100, SH wrote:
On 09/04/2021 16:17, Scott wrote: On Fri, 9 Apr 2021 15:52:07 +0100, SH wrote: On 09/04/2021 15:38, Scott wrote: We are having a problem with some sort of airlock - a buzzing noise. I live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. Its a worn out ball cock valve. The valve is not shutting off cleanly when the tank reaches its final water level. the buzzing sounds is caused by the ball bobbing up and down in the water which is causing a pressure ripple through the rising main and hence the sound you hear. although you could replace the washer, its better to replace the whole thing. This is interesting. The 'argument' I alluded to is that two of my neighbours think the problem is with the toilet in the first floor flat. I think the noise is permeating the whole pipe and thought we should start at the top (where I assumed the air would be). Of course both these installations include a ballcock valve. Is there any way of knowing which of the two valves needs to be replaced. From my point of view, if it's in the downstairs flat, it's an enforcement problem and if it's in the loft it's a funding problem (though I would be inclined to go ahead with repairs in the loft if I could confirm the fault). Tie up the ball cock in the loft tank with some string. Then flush all the toilets one by one in the building and use your ears or even a stethosope on teh pipework to see which one then buzzes as the toilet cistern approaches its final cistern water level. Once you've identified the problematic toilets, you can then release the ball valve in the loft tank. Listen to this to see if it buzzes as it reaches final tank level. (the loft tank will be several hundred litres of capacity and the typical toilet cistern is around 3 to 6 litres.) Then order and replace the toilet and/or ball cock valves as required. Thanks, but the problem is that I am not getting much in the way of co-operation from my neighbours. No-one really wants workmen in the flat during the Covid. The first floor flat is tenanted with an absentee landlord. I think he would want evidence of liability before carrying out any repairs. I don't even know if the toilet in question is fed by the loft tank or the rising main. |
#9
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On Fri, 09 Apr 2021 15:38:09 +0100, Scott
wrote: We are having a problem with some sort of airlock - a buzzing noise. I live in a block of flats. I believe the problem lies with the rising main, though neighbours disagree. The rising main terminates at a storage tank in the loft. I believe think various neighbours have taken feeds from it over the years. At the entry to the storage tank there is an vertical extension to the pipe, about 12 inches long. I *think* that was put there as a silencer previously. Should this extension contain water or air? Is there any action to take, such as bleeding it, if we are now getting water hammer? I have tried pushing down the ball cock in the hope of releasing air. This seems to have helped but not fully resolved the issue. Any advice welcome. Neighbours were correct. I was wrong. Problem was the toilet in one of the flats. The tenants reported it and now it is repaired. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
Plumbing Code - Can I tie my bathroom exaust fan into the main plumbing vent to the outside. | Home Repair | |||
Question on plumbing average cost- location New England...For newtoilet and change pedestal plumbing | Home Repair | |||
Concrete question (regarding previous plumbing question) | Home Repair | |||
plumbing question | UK diy | |||
Pushfit plumbing question | UK diy |