Ideal Logic combi. The mfr's instructions show the combi boiler condensate drain running into a branch waste pipe downstream of any other appliances (bath, basin etc).

I understand this is so CO from the flue can't or is less likely to find its way into the house if there's a fault with the boiler and the U-bend of one of the appliances has evaporated no longer forming a seal.

Is this an inviolable rule or is there a way round it? A Macalpine has been mentioned, but I don't know if this is a special trap, a condensate pump, or what.

I've had previous boilers condense into the branch below the kitchen sink without comment from a Gas Safe person.

I have a long way between the boiler and the stack, and a bath, basin, sink, washing machine, and potentially a dishwasher all on that branch pipe. Getting a dedicated condensate pipe all the way to the stack is almost impossible. External condensate soakaway is not viable.

Boiler will be put in by a Gas Safe but I'm trying to anticipate difficulties rather than them happening on the day (and it is only one day allocated for a full heating system in 6 rooms, so everything's got to run smoothly!)

Owain

  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4,564
Default Boiler condensate drain

On Wednesday, 7 October 2020 21:29:06 UTC+1, newshound wrote:
IIRC a condensate pump can feed something like a 6mm hose which can be
routed almost anywhere.


That might work if they can feed it round the corner bath.

I think the Macalpine referred to might have been a waterless seal trap.

Owain

  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 297
Default Boiler condensate drain

On Wed, 7 Oct 2020 12:38:53 -0700 (PDT),
wrote:

Ideal Logic combi. The mfr's instructions show the combi boiler condensate drain running into a branch waste pipe downstream of any other appliances (bath, basin etc).

I understand this is so CO from the flue can't or is less likely to find its way into the house if there's a fault with the boiler and the U-bend of one of the appliances has evaporated no longer forming a seal.

Is this an inviolable rule or is there a way round it? A Macalpine has been mentioned, but I don't know if this is a special trap, a condensate pump, or what.

I've had previous boilers condense into the branch below the kitchen sink without comment from a Gas Safe person.

I have a long way between the boiler and the stack, and a bath, basin, sink, washing machine, and potentially a dishwasher all on that branch pipe. Getting a dedicated condensate pipe all the way to the stack is almost impossible. External condensate soakaway is not viable.

Boiler will be put in by a Gas Safe but I'm trying to anticipate difficulties rather than them happening on the day (and it is only one day allocated for a full heating system in 6 rooms, so everything's got to run smoothly!)

Owain

My Worcester Bosch boiler has an integral syphon in the condensate
outlet. It allows a quantity of condensate to collect before it
releases it all in one go (helps prevent freezing) and it also
performs as an internal U bend seal to prevent the escape of CO.

Because of the location of the boiler (internal airing cupboard) the
condensate then goes to a condensate pump, from where it gets pumped
up into the loft, and then across the loft (down sloping pipe) to the
vented soil stack.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Drain connection to sewer for condensate drain? [email protected][_2_] Home Repair 18 December 27th 11 07:20 PM
boiler condensate into cast iron drain RobertL UK diy 3 October 6th 09 07:08 PM
boiler condensate drain Stephen[_2_] UK diy 4 August 30th 08 09:52 AM
boiler condensate drain Andrew L. UK diy 2 January 28th 07 05:29 PM
Boiler Condensate Drain options Ron Lowe UK diy 12 January 9th 07 10:15 PM


All times are GMT +1. The time now is 12:45 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"