  #1   Report Post  
 
Posts: n/a
Default Furnace/Humidifier question

I just purchased a new humidifier (attaches to the furnace). Do I wire
it from the blower and if so, how do I know what wires to attach from
the blower to the humidifier? It's a mess of wires in there!

I wired it from the switch straight to the humidifier. It works but
continuously flows water. I assume this needs to be wired to the
blower but I want to be sure I wire it correctly.

  #2   Report Post  
Mikepier
 
Posts: n/a
Default Furnace/Humidifier question

I do not think it gets wired to the blower simply because if you just
turn your fan on at the thermostat, the humidifier will constantly be
on.
On my furnace, the humidifier kicks on only when the heat is on, but
once the heat has been satisfied and the gas burner kicks off, the
humidifier also goes off, even if the fan stays on. I do not think the
humidifier will do it's job correctly if just the fan is on and no heat
passing through it.
On my Trane XR 80 furnace, the humidifier is hooked up to the C and Y
terminals on the board. This is not to say you furnace is similiar,
but just to give you a reference.
What does the instructions say that came with the humidifier when you
purchased it?

  #3   Report Post  
Dr. Hardcrab
 
Posts: n/a
Default Furnace/Humidifier question


wrote in message
oups.com...
I just purchased a new humidifier (attaches to the furnace). Do I wire
it from the blower and if so, how do I know what wires to attach from
the blower to the humidifier? It's a mess of wires in there!

I wired it from the switch straight to the humidifier. It works but
continuously flows water. I assume this needs to be wired to the
blower but I want to be sure I wire it correctly.


Best thing to do is purchase a current sensing realy OR get a "sail" switch.


  #5   Report Post  
 
Posts: n/a
Default Furnace/Humidifier question

Part of my problem is that the installation instructions that came with
the humidifier are extremely vague. They don't tell me anything.

I bought a Honeywell Humidifier, and for $70 more, I could have
purchased the installation kit to go with it. I didn't need any more
parts except the installation kit comes with a video tape installation
instructions.

I couldn't justify spending the $$ for a video tape.

Anyway, since I have it wired directly from the power source to the
transformer to the humidifier, the humidifier will run all the time,
whether the furnace is on or off. That is why I thought the wiring
needed to be changed but I am still confused.

Help!



  #6   Report Post  
 
Posts: n/a
Default Furnace/Humidifier question

Dr. Hardcrab wrote:

wrote:


I just purchased a new humidifier (attaches to the furnace). Do I wire
it from the blower and if so, how do I know what wires to attach from
the blower to the humidifier? It's a mess of wires in there!

I wired it from the switch straight to the humidifier. It works but
continuously flows water. I assume this needs to be wired to the
blower but I want to be sure I wire it correctly.


Best thing to do is purchase a current sensing realy OR get a "sail" switch.


Best thing to do is caulk the house and trash the humidifier.

Nick

  #7   Report Post  
m Ransley
 
Posts: n/a
Default Furnace/Humidifier question

You say it runs all the time, do you mean it pours water. Humidifers
for forced air do not need the wasted cost of running a fan, air blowes
over an evaporator pad.

  #8   Report Post  
 
Posts: n/a
Default Furnace/Humidifier question

You sure the install kit didn't include a current sensing relay, or a
sail switch?

How a specific unit should be wired will vary. But in general, there
are several options:

1 - Wired direct to go on when the blower turns on

2 - Wired direct to go on when the burner is on

3 - Wired using a current sensing relay to go on either with the blower
or burner

4 - Wired with a sail switch to go on with the blower.

Whic option is best depends on the furnace, the humidifier, and how
easy/hard any of these options is for that particular install.

  #11   Report Post  
 
Posts: n/a
Default Furnace/Humidifier question

"Isn't there some sort of controller which mounts in the living area
to sense humidity? "

Most have a humidistat that mounts on the return air plenum. But that
doesn't solve the problem of having the unit only turn on when the
furnace and/or blower are running. The humidistat is just another
on/off that will only turn it on when the humidity in the return air is
below the set point.

  #12   Report Post  
Scott
 
Posts: n/a
Default Furnace/Humidifier question

Check out the Aprilaire 600. It has a control that mounts on the furnace.
The more expensive Aprilaire 700 ( I believe it is) has a unit that mounts
by the upstairs thermostat. I don't mind going down stairs to my furnace to
adjust it. I just set to around 45% and forget it till Summer.


wrote in message
oups.com...
"Isn't there some sort of controller which mounts in the living area
to sense humidity? "

Most have a humidistat that mounts on the return air plenum. But that
doesn't solve the problem of having the unit only turn on when the
furnace and/or blower are running. The humidistat is just another
on/off that will only turn it on when the humidity in the return air is
below the set point.



  #13   Report Post  
 
Posts: n/a
Default Furnace/Humidifier question

I have determined that this will need to be wired to either the blower
or the burner. Since I am new to this, I am assuming this can be done?

What it is doing now is when the furnace is on or off, the water
continues to flow through the pad into the drain hose, non stop.

Can anyone easily explain how to wire this up?

By the way, there was an existing humidifer on the furnace but I made a
mistake and forgot to label how it was installed when I removed it.

  #15   Report Post  
hvactech2
 
Posts: n/a
Default Furnace/Humidifier question

On Tue, 18 Oct 2005 10:32:54 GMT, "Joseph Meehan"
wrote:

wrote:
I have determined that this will need to be wired to either the blower
or the burner. Since I am new to this, I am assuming this can be
done?

What it is doing now is when the furnace is on or off, the water
continues to flow through the pad into the drain hose, non stop.

Can anyone easily explain how to wire this up?

By the way, there was an existing humidifer on the furnace but I made
a mistake and forgot to label how it was installed when I removed it.


You need to know what voltage it needs (generally 12 - 24 or 120V) and
what amperage it needs, then you need to find a switched source with
sufficient excess capacity for it or use a relay to reduce the load.

The more I think about it, the more I think you should junk this thing
and buy a good humidifier like Aprilair.


I see you are back spreading misinformation again Mr. Meehan. he
already got the proper advice but you are of course wrong again!!
++++++++++++++++++++++++++++++++++++++++++++++++++ +++++++++++
spam protection measure, Please remove the 33 to send e-mail
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Good morning or good evening depending upon your location. I want to ask you the most important question of your life. Your joy or sorrow for all eternity depends upon your answer. The question is: Are you saved? It is not a question of how good mac davis Woodworking 0 April 21st 05 05:38 PM
To anyone sick of alt.hvac Matt Morgan Home Repair 87 April 8th 05 05:17 PM
OT Guns more Guns Cliff Metalworking 519 December 12th 04 05:52 AM
Plumbing Question Jeff UK diy 4 December 1st 03 01:49 PM
Question????? Sir Edgar Woodworking 8 July 20th 03 05:22 PM


All times are GMT +1. The time now is 07:10 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"