UK diy (uk.d-i-y) For the discussion of all topics related to diy (do-it-yourself) in the UK. All levels of experience and proficency are welcome to join in to ask questions or offer solutions.

Reply
 
LinkBack Thread Tools Search this Thread Display Modes
  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 33
Default Wood burning stove

We are considering having a wood burner installed as a secondary heat
source in our front room, we live in a rural area, have access to
plenty of fuel and no storage problems. Not using it to heat water.
However we do have one minor problem.... we have no chimney stack!
Previous owners have had it removed down to just above bedroom
ceiling. Having it rebuilt will not be a problem, but the question I
have is, do we need it lining?
There are four fireplaces in the house, two up and two down. We have
no intention of ever having fires upstairs and unlikely to have one in
the other downstairs room. I welcome the opinions/thoughts/suggestions
(polite ones please) of the 'team' .
If it has any bearing on the issue the fire would likely only be lit
during winter and then only three or four times a week of an evening,
in other words, light use.
House is a late Victorian terrace with a hideous gas fire in the
fireplace, was swept very recently; before gas fire fitted (by
previous owners)

  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 57
Default Wood burning stove

johno wrote:
We are considering having a wood burner installed as a secondary heat
source in our front room, we live in a rural area, have access to
plenty of fuel and no storage problems. Not using it to heat water.
However we do have one minor problem.... we have no chimney stack!
Previous owners have had it removed down to just above bedroom
ceiling. Having it rebuilt will not be a problem, but the question I
have is, do we need it lining?
There are four fireplaces in the house, two up and two down. We have
no intention of ever having fires upstairs and unlikely to have one in
the other downstairs room. I welcome the opinions/thoughts/suggestions
(polite ones please) of the 'team' .


If you're having the job done of reconstructing the stack through the
loft and the roof then it's absolutely worth having the chimney lined at
the same time.

Chimneys have a tendency to crack over time which means smoke and tar
deposit leak into the rooms, causing a smell and making stains behind
plaster.

The other advantages are that it'll probably draw better and it'll stay
clean longer and be easier to sweep.
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 6,938
Default Wood burning stove

In message , Jim
writes
johno wrote:
We are considering having a wood burner installed as a secondary heat
source in our front room, we live in a rural area, have access to
plenty of fuel and no storage problems. Not using it to heat water.
However we do have one minor problem.... we have no chimney stack!
Previous owners have had it removed down to just above bedroom
ceiling. Having it rebuilt will not be a problem, but the question I
have is, do we need it lining?
There are four fireplaces in the house, two up and two down. We have
no intention of ever having fires upstairs and unlikely to have one in
the other downstairs room. I welcome the opinions/thoughts/suggestions
(polite ones please) of the 'team' .


If you're having the job done of reconstructing the stack through the
loft and the roof then it's absolutely worth having the chimney lined
at the same time.

Chimneys have a tendency to crack over time which means smoke and tar
deposit leak into the rooms, causing a smell and making stains behind
plaster.

The other advantages are that it'll probably draw better and it'll stay
clean longer and be easier to sweep.


Would this be resolved by using the rigid style insulated flue. Costs an
arm and a leg but must be cheaper than bricking back up through the
loft?

regards

--
Tim Lamb
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,379
Default Wood burning stove


Would this be resolved by using the rigid style insulated flue. Costs an
arm and a leg but must be cheaper than bricking back up through the
loft?


Two downsides I can see, would look odd on a Victorian house, and
would require some rather good lead flashing to make a good seal
around a non-standard roof penetration (i.e. you can't use a standard
lead slate, nor can you cut and tuck lead sheeting into the
brickwork).

OTOH it must be done routinely where these pass through roofs (rather
than through walls) where there is no chimney to use at all. I haven't
seen the detail of how that is usually done though.

For that matter, if the stack has been taken below slate/tile level -
it will still require someone with the art of leadwork to make good
around a brick chimney.

  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 6,938
Default Wood burning stove

In message
,
" writes

For that matter, if the stack has been taken below slate/tile level -
it will still require someone with the art of leadwork to make good
around a brick chimney.


I have done that! Surprisingly easy. Once you know the roof pitch and
the brick gauge, each section of stepped flashing can be made up on the
bench and then carried up to the roof.

regards


--
Tim Lamb


  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 39,563
Default Wood burning stove

Tim Lamb wrote:
In message , Jim
writes
johno wrote:
We are considering having a wood burner installed as a secondary heat
source in our front room, we live in a rural area, have access to
plenty of fuel and no storage problems. Not using it to heat water.
However we do have one minor problem.... we have no chimney stack!
Previous owners have had it removed down to just above bedroom
ceiling. Having it rebuilt will not be a problem, but the question I
have is, do we need it lining?
There are four fireplaces in the house, two up and two down. We have
no intention of ever having fires upstairs and unlikely to have one in
the other downstairs room. I welcome the opinions/thoughts/suggestions
(polite ones please) of the 'team' .


If you're having the job done of reconstructing the stack through the
loft and the roof then it's absolutely worth having the chimney lined
at the same time.

Chimneys have a tendency to crack over time which means smoke and tar
deposit leak into the rooms, causing a smell and making stains behind
plaster.

The other advantages are that it'll probably draw better and it'll
stay clean longer and be easier to sweep.


Would this be resolved by using the rigid style insulated flue. Costs an
arm and a leg but must be cheaper than bricking back up through the loft?



Only rigid insulated flues are permissible really. Work SHOULD have a
building notice as well, or be carried out by registered installers.




regards

  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,379
Default Wood burning stove

From a building regulations point of view, it *may* not be required to
line the chimney - if putting it back into use is considered a
repair.

If OTOH it's regarded as disused, building regs would I think apply.

However there's several reasons why it's a good idea to line
regardless.

Stainless steel liners for solid fuel are far from cheap - think about
costs being similar to a good quality stove (also don't be misled by
the price for linings for gas boilers - they're much cheaper but
unsuitable for solid fuel).

However if you're having the chimney stack rebuilt, that's the ideal
time to have a liner put in. It isn't unusual to have to at least have
to take the pot off anyway, and often the flaunching requires repair.

Other important stuff is the chimney is well designed to draw well and
avoid downdraughts - which depends on a myriad of things, surrounding
terrain/buildings/trees, shape of your roof, height of chimney above
roof - some of which may have changed since the original build.

A liner helps the stove to draw well, which reduces sooting and
improves rapid heat-up (reducing the chances and consequences of a
chimney fire - which can be bloody scary) - and in some cases may be
important for safety.

Ideally you want to get a look at the state of the masonry inside the
chimney. The combination of many years of usage/sooting along with
rainwater can lead to considerable mortar erosion - in which case
definitely don't skip the liner.

If the chimney is significantly larger than the liner, filling the
space between with vermiculite is common practice.

Take Christmas as an opportunity to stuff smaller relatives up the
chimney for closer inspection.

Much good advice in Part J of the building regs:

http://www.planningportal.gov.uk/eng...documentslist/

  #9   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 282
Default Wood burning stove

If you have a woodburning stove then need to have a stainless steel
flexible flue flue of the correct diameter to go with it (I guess this
is what you mean by lining) otherwise it will not draw properly. I
think the question should be: do you need to re-build the stack or is
there a cheaper way of venting the fumes?
  #10   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 39,563
Default Wood burning stove

Rednadnerb wrote:
If you have a woodburning stove then need to have a stainless steel
flexible flue


Only premissible if te existing flue is sound.

And generally a Bad Idea for a wood stove. Use solid insulated double
walled STAINLESS STEEL. Aluminium corrugated will not survive a chimney
fire, or even a good roaring fire.



I
think the question should be: do you need to re-build the stack or is
there a cheaper way of venting the fumes?


It is permissible to take a stainless steel flue straight through a
timber framed roof with no stack whatsoever. Just a pipe sticking up,


  #11   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 565
Default Wood burning stove

Rednadnerb wrote:

If you have a woodburning stove then need to have a stainless steel
flexible flue flue of the correct diameter to go with it (I guess this
is what you mean by lining) otherwise it will not draw properly. I
think the question should be: do you need to re-build the stack or is
there a cheaper way of venting the fumes?



I've been following this thread with interest,
as I am thinking of installing a wood stove in a Victorian cottage,
which surprisingly has a chimney stack in the middle of the main room.
(The cottage was originally the wash-house for a neighbouring orphanage.)

Would I have to line the existing chimney up to the roof?
Surely it should not get very hot except close to the stove,
or the heat-loss would be very large?

--
Timothy Murphy
e-mail: gayleard /at/ eircom.net
tel: +353-86-2336090, +353-1-2842366
s-mail: School of Mathematics, Trinity College, Dublin 2, Ireland
  #12   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,005
Default Wood burning stove

johno
wibbled on Wednesday 09 December 2009 16:40

We are considering having a wood burner installed as a secondary heat
source in our front room, we live in a rural area, have access to
plenty of fuel and no storage problems. Not using it to heat water.
However we do have one minor problem.... we have no chimney stack!
Previous owners have had it removed down to just above bedroom
ceiling. Having it rebuilt will not be a problem, but the question I
have is, do we need it lining?
There are four fireplaces in the house, two up and two down. We have
no intention of ever having fires upstairs and unlikely to have one in
the other downstairs room. I welcome the opinions/thoughts/suggestions
(polite ones please) of the 'team' .
If it has any bearing on the issue the fire would likely only be lit
during winter and then only three or four times a week of an evening,
in other words, light use.
House is a late Victorian terrace with a hideous gas fire in the
fireplace, was swept very recently; before gas fire fitted (by
previous owners)


Abstract thought - do you need the whole stack or can you do something with
a twin walled flue, and maybe some fireproofed boxing in?

I don't actually know, but I'm thinking of all those log cabins (some 2
storey) with iron stoves...

--
Tim Watts

This space intentionally left blank...

  #13   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 477
Default Wood burning stove

Tim W wrote:

Abstract thought - do you need the whole stack or can you do something
with a twin walled flue, and maybe some fireproofed boxing in?


This is the way I would go and maybe make a feature of the flue pipe.
Failing that Poulat do some prefabbed coverings.

AJH
  #14   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 39,563
Default Wood burning stove

johno wrote:
We are considering having a wood burner installed as a secondary heat
source in our front room, we live in a rural area, have access to
plenty of fuel and no storage problems. Not using it to heat water.
However we do have one minor problem.... we have no chimney stack!
Previous owners have had it removed down to just above bedroom
ceiling. Having it rebuilt will not be a problem, but the question I
have is, do we need it lining?

Yes, but actually, sod the stack altogether. Simply use double skinned
insulated lining all the way to a cowl.


There are four fireplaces in the house, two up and two down. We have
no intention of ever having fires upstairs


You should. A stove in the bedroom is luvverly.

and unlikely to have one in
the other downstairs room. I welcome the opinions/thoughts/suggestions
(polite ones please) of the 'team' .
If it has any bearing on the issue the fire would likely only be lit
during winter and then only three or four times a week of an evening,
in other words, light use.
House is a late Victorian terrace with a hideous gas fire in the
fireplace, was swept very recently; before gas fire fitted (by
previous owners)


Just spend a grand on te liner and a grand on the stove and be happy.

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Do I need to put out wood burning stove? spj_uk Home Ownership 2 October 30th 06 03:46 PM
wood burning stove John Kelly UK diy 7 October 13th 06 03:01 PM
wood burning stove [email protected] UK diy 2 April 24th 05 05:28 AM
Wood burning stove PacKat Home Repair 3 December 21st 04 02:16 PM
Wood burning stove Martin Carroll UK diy 4 October 12th 03 08:44 PM


All times are GMT +1. The time now is 04:27 AM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
Copyright ©2004-2025 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"