Hi all,

I've just had an office PAT tested and to my surprise a number of newish (ie
bout within the last 12-24 months) TFT monitors have 'failed'. The guy doing
the testing has sort of shrugged his shoulders wehen I asked him exactly
what this meant, and has recommended that I change the power leads - which
seems daft as the power leads have been seperately checked and PASSED!

Any idea what I should do? Should I replace the units and if so, what is
likely to be the problem with them?

Best wishes,

Sky


  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 324
Default PAT tests



"Sky" wrote in message
. uk...
Hi all,

I've just had an office PAT tested and to my surprise a number of newish
(ie bout within the last 12-24 months) TFT monitors have 'failed'. The guy
doing the testing has sort of shrugged his shoulders wehen I asked him
exactly what this meant, and has recommended that I change the power
leads - which seems daft as the power leads have been seperately checked
and PASSED!

Any idea what I should do? Should I replace the units and if so, what is
likely to be the problem with them?

Best wishes,

Sky



What did they fail on, insulation or earth continuity?
if the latter, what part of the monitor did the guy
connect the crocodile clip to?
--
Graham

%Profound_observation%


  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 11,175
Default PAT tests

In article ,
"Sky" writes:
Hi all,

I've just had an office PAT tested and to my surprise a number of newish (ie
bout within the last 12-24 months) TFT monitors have 'failed'. The guy doing
the testing has sort of shrugged his shoulders wehen I asked him exactly
what this meant, and has recommended that I change the power leads - which
seems daft as the power leads have been seperately checked and PASSED!

Any idea what I should do? Should I replace the units and if so, what is
likely to be the problem with them?


What was the reason for the failure?
Do the monitors have external PSU's, or does the mains lead
plug into them directly?

I do wonder if the guy had the faintest idea what he was doing,
if he just shrugged his shoulders when asked for details. A lot
of PAT testers (most in fact) haven't got a clue. In future, I
would suggest you ask to see the tester's C&G 2377/2 certificate
before engaging them.

--
Andrew Gabriel
[email address is not usable -- followup in the newsgroup]
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 6,896
Default PAT tests

In article , Andrew Gabriel
scribeth thus
In article ,
"Sky" writes:
Hi all,

I've just had an office PAT tested and to my surprise a number of newish (ie
bout within the last 12-24 months) TFT monitors have 'failed'. The guy doing
the testing has sort of shrugged his shoulders wehen I asked him exactly
what this meant, and has recommended that I change the power leads - which
seems daft as the power leads have been seperately checked and PASSED!

Any idea what I should do? Should I replace the units and if so, what is
likely to be the problem with them?


What was the reason for the failure?
Do the monitors have external PSU's, or does the mains lead
plug into them directly?

I do wonder if the guy had the faintest idea what he was doing,
if he just shrugged his shoulders when asked for details. A lot
of PAT testers (most in fact) haven't got a clue. In future, I
would suggest you ask to see the tester's C&G 2377/2 certificate
before engaging them.


I suspect this might be Capactive leakage coupling from the L and/or N
conductors to the Earth line thats if they are kettle lead connected
types!...
--
Tony Sayer



  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 11,175
Default PAT tests

In article ,
tony sayer writes:
In article , Andrew Gabriel
scribeth thus
In article ,
"Sky" writes:
Hi all,

I've just had an office PAT tested and to my surprise a number of newish (ie
bout within the last 12-24 months) TFT monitors have 'failed'. The guy doing
the testing has sort of shrugged his shoulders wehen I asked him exactly
what this meant, and has recommended that I change the power leads - which
seems daft as the power leads have been seperately checked and PASSED!

Any idea what I should do? Should I replace the units and if so, what is
likely to be the problem with them?


What was the reason for the failure?
Do the monitors have external PSU's, or does the mains lead
plug into them directly?

I do wonder if the guy had the faintest idea what he was doing,
if he just shrugged his shoulders when asked for details. A lot
of PAT testers (most in fact) haven't got a clue. In future, I
would suggest you ask to see the tester's C&G 2377/2 certificate
before engaging them.


I suspect this might be Capactive leakage coupling from the L and/or N
conductors to the Earth line thats if they are kettle lead connected
types!...


It may be that he's done an insulation test on the monitors
without checking if they conform to BS EN 60950, and has destroyed
them in the process. He might even have flash tested them.
In either case, he should be paying for replacements.

--
Andrew Gabriel
[email address is not usable -- followup in the newsgroup]
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Video on joint tests [email protected] Woodworking 6 March 28th 07 04:52 PM
pregnancy tests davidrsalsbury UK diy 7 March 9th 07 09:59 AM
Shower pan tests? Savoire Faire Home Repair 4 July 20th 05 12:32 PM
Battery life tests Stormin Mormon Home Repair 1 September 22nd 04 08:39 PM
DPS Pandora - further performance tests Christian McArdle UK diy 11 August 12th 04 12:07 PM


All times are GMT +1. The time now is 12:31 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"