Default Replacing an FPE Stab Lock panel

Original panel dates to 1957. No issues with it but I've read about the
many bad things about this unit. Also, the local codes now require 100A
service and the present panel with two mains of 30 for the dryer circuit
and 50 for the rest of the panel is now obsolete.

So the question is whether anyone is offering replacement internal guts for
this unit. It's model 116-68C. If so I think I'd go that route.

Old box is flush in the wall.

If an entirely new box is needed, could one remove the existing guts and
leave the old box in place? Mount a new panel right inside the old and
maybe use the old cover, cut a big rectangle out leaving just a sort of
rectangular ring and place it so as to cover the area where wires are
emerging from their conduits (formerly the interor of the old box) and
going an inch or so to enter the new box.

OR

What if one got a new box that was intentially larger than the old and
mounted it on the surface in front of the old box? Again, the old box
would be stripped of guts, and the cover removed and the box left in the
wall. Wires could enter the new box from the rear. Those existing wires
able to reach a breaker could go directly in. Those too short would just
have new, longer runs pulled from their first place they go to (outlet box
typically).
  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 545
Default Replacing an FPE Stab Lock panel

On Mon, 15 Dec 2014 11:14:16 -0600, Chet Kincaid
wrote:

Original panel dates to 1957. No issues with it but I've read about the
many bad things about this unit. Also, the local codes now require 100A
service and the present panel with two mains of 30 for the dryer circuit
and 50 for the rest of the panel is now obsolete.

So the question is whether anyone is offering replacement internal guts for
this unit. It's model 116-68C. If so I think I'd go that route.

Old box is flush in the wall.

If an entirely new box is needed, could one remove the existing guts and
leave the old box in place? Mount a new panel right inside the old and
maybe use the old cover, cut a big rectangle out leaving just a sort of
rectangular ring and place it so as to cover the area where wires are
emerging from their conduits (formerly the interor of the old box) and
going an inch or so to enter the new box.

OR

What if one got a new box that was intentially larger than the old and
mounted it on the surface in front of the old box? Again, the old box
would be stripped of guts, and the cover removed and the box left in the
wall. Wires could enter the new box from the rear. Those existing wires
able to reach a breaker could go directly in. Those too short would just
have new, longer runs pulled from their first place they go to (outlet box
typically).


I have a FPE Stab Lock panel in my house from 1979. It has a 100A main.
I've never had any problems with it. I also considered replacing it,
but I was told by a local electrician that they were improved in the
70's and a 1979 panel is as safe as any other breaker panel. While
everyone has their opinions, I am not sure what to believe.....

However, in your case that is a really old panel, and with the main's
problems, I'd be more inclined to change it.

I'm sure the guts of any panel can be modified to fit the panel, as long
as it is not too large, but you'll have to modify the cover door too, so
the breakers fit. That seems like a lot more trouble than just changing
the whole box. Either way, you'll have to pull the meter. If you have
to cut away a little plaster, why not just fill it in with some sort of
decorative molding.


  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 18,538
Default Replacing an FPE Stab Lock panel

On Mon, 15 Dec 2014 22:36:32 -0600, wrote:

On Mon, 15 Dec 2014 11:14:16 -0600, Chet Kincaid
wrote:

Original panel dates to 1957. No issues with it but I've read about the
many bad things about this unit. Also, the local codes now require 100A
service and the present panel with two mains of 30 for the dryer circuit
and 50 for the rest of the panel is now obsolete.

So the question is whether anyone is offering replacement internal guts for
this unit. It's model 116-68C. If so I think I'd go that route.

Old box is flush in the wall.

If an entirely new box is needed, could one remove the existing guts and
leave the old box in place? Mount a new panel right inside the old and
maybe use the old cover, cut a big rectangle out leaving just a sort of
rectangular ring and place it so as to cover the area where wires are
emerging from their conduits (formerly the interor of the old box) and
going an inch or so to enter the new box.

OR

What if one got a new box that was intentially larger than the old and
mounted it on the surface in front of the old box? Again, the old box
would be stripped of guts, and the cover removed and the box left in the
wall. Wires could enter the new box from the rear. Those existing wires
able to reach a breaker could go directly in. Those too short would just
have new, longer runs pulled from their first place they go to (outlet box
typically).


I have a FPE Stab Lock panel in my house from 1979. It has a 100A main.
I've never had any problems with it. I also considered replacing it,
but I was told by a local electrician that they were improved in the
70's and a 1979 panel is as safe as any other breaker panel. While
everyone has their opinions, I am not sure what to believe.....

However, in your case that is a really old panel, and with the main's
problems, I'd be more inclined to change it.

I'm sure the guts of any panel can be modified to fit the panel, as long
as it is not too large, but you'll have to modify the cover door too, so
the breakers fit. That seems like a lot more trouble than just changing
the whole box. Either way, you'll have to pull the meter. If you have
to cut away a little plaster, why not just fill it in with some sort of
decorative molding.

Remember, any modification to the panel voids the certification on the
panel. The only exception is installation of a conversion unit
specifically designed and certified to fit your box.
  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 18,538
Default Replacing an FPE Stab Lock panel

On Tue, 16 Dec 2014 01:34:32 -0500, wrote:

On Mon, 15 Dec 2014 23:41:16 -0500,
wrote:

On Mon, 15 Dec 2014 22:36:32 -0600,
wrote:

On Mon, 15 Dec 2014 11:14:16 -0600, Chet Kincaid
wrote:

Original panel dates to 1957. No issues with it but I've read about the
many bad things about this unit. Also, the local codes now require 100A
service and the present panel with two mains of 30 for the dryer circuit
and 50 for the rest of the panel is now obsolete.

So the question is whether anyone is offering replacement internal guts for
this unit. It's model 116-68C. If so I think I'd go that route.

Old box is flush in the wall.

If an entirely new box is needed, could one remove the existing guts and
leave the old box in place? Mount a new panel right inside the old and
maybe use the old cover, cut a big rectangle out leaving just a sort of
rectangular ring and place it so as to cover the area where wires are
emerging from their conduits (formerly the interor of the old box) and
going an inch or so to enter the new box.

OR

What if one got a new box that was intentially larger than the old and
mounted it on the surface in front of the old box? Again, the old box
would be stripped of guts, and the cover removed and the box left in the
wall. Wires could enter the new box from the rear. Those existing wires
able to reach a breaker could go directly in. Those too short would just
have new, longer runs pulled from their first place they go to (outlet box
typically).

I have a FPE Stab Lock panel in my house from 1979. It has a 100A main.
I've never had any problems with it. I also considered replacing it,
but I was told by a local electrician that they were improved in the
70's and a 1979 panel is as safe as any other breaker panel. While
everyone has their opinions, I am not sure what to believe.....

However, in your case that is a really old panel, and with the main's
problems, I'd be more inclined to change it.

I'm sure the guts of any panel can be modified to fit the panel, as long
as it is not too large, but you'll have to modify the cover door too, so
the breakers fit. That seems like a lot more trouble than just changing
the whole box. Either way, you'll have to pull the meter. If you have
to cut away a little plaster, why not just fill it in with some sort of
decorative molding.

Remember, any modification to the panel voids the certification on the
panel. The only exception is installation of a conversion unit
specifically designed and certified to fit your box.


Generally speaking, the listing for the panelboard is separate from
the listing for the enclosure.

Not on residential panels in Canada. They have one listing number for
the total assembly (generally speaking)


  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 10,730
Default Replacing an FPE Stab Lock panel

On 12/15/2014 12:14 PM, Chet Kincaid wrote:
Original panel dates to 1957. No issues with it but I've read about the
many bad things about this unit. Also, the local codes now require 100A
service and the present panel with two mains of 30 for the dryer circuit
and 50 for the rest of the panel is now obsolete.

So the question is whether anyone is offering replacement internal guts for
this unit. It's model 116-68C. If so I think I'd go that route.

Old box is flush in the wall.

If an entirely new box is needed, could one remove the existing guts and
leave the old box in place? Mount a new panel right inside the old and
maybe use the old cover, cut a big rectangle out leaving just a sort of
rectangular ring and place it so as to cover the area where wires are
emerging from their conduits (formerly the interor of the old box) and
going an inch or so to enter the new box.

OR

What if one got a new box that was intentially larger than the old and
mounted it on the surface in front of the old box? Again, the old box
would be stripped of guts, and the cover removed and the box left in the
wall. Wires could enter the new box from the rear. Those existing wires
able to reach a breaker could go directly in. Those too short would just
have new, longer runs pulled from their first place they go to (outlet box
typically).

I'm also a thinker, and also prefer not to throw
out things that work. This is one case where it's
not wise to mess around with saving old stuff.

I'd call several electricians to get estimates.
Hire the guy (gal) who talks slowly, makes sense,
and seem to know the task.

-
..
Christopher A. Young
Learn about Jesus
www.lds.org
..
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Does Federal Pacific stab and lock make tandem breakers? Aaron Home Repair 19 August 4th 16 02:22 AM
Replacing door lock barrels chudford UK diy 7 December 9th 11 01:27 PM
Problem replacing Euro cylinder lock Reentrant UK diy 2 December 8th 08 01:13 PM
Replacing a lock in a uPvc door. Dee UK diy 5 June 20th 08 10:05 AM
Replacing a Euro Lock diy-newby UK diy 14 April 9th 08 12:27 PM


All times are GMT +1. The time now is 01:01 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"