Default Sub-panel questins

Hello, I'm getting ready to install a sub-panel next to the main panel. Probably be using #6 wire to feed into it. Couple of questions:

Do I use 50a or 60a breaker feeding the sub?

I wanted to connect both boxes with 3/4" pipe. Can I use Pvc or does it need to be EMT?

Can I fit 4- #6 wires in 3/4" pipe?

Any recommendations for subs ? ( square D, GE, Eaton, Murray). The main panel is a Westinghouse.

Thanks
  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 964
Default Sub-panel questins

In ,
Mikepier typed:
Hello, I'm getting ready to install a sub-panel next to the main
panel. Probably be using #6 wire to feed into it. Couple of
questions:

Do I use 50a or 60a breaker feeding the sub?

I wanted to connect both boxes with 3/4" pipe. Can I use Pvc or does
it need to be EMT?

Can I fit 4- #6 wires in 3/4" pipe?

Any recommendations for subs ? ( square D, GE, Eaton, Murray). The
main panel is a Westinghouse.

Thanks


I don't know the answers to any of the above questions, but I do remember
(almost) that there is something that needs to be kept in mind when adding a
subpanel. If I remember correctly, I think it is that the neutral bar and
the ground bar in the subpanel have to be insulated/separated from each
other -- meaning that the ground and neutral cannot be combined in the
subpanel the way that they can in a main panel. I forget the exact details.

You probably already know about that, but I thought that I would mention it
just in case.

And, to be honest, I never really completely understood the explanation of
why that is even though a number of people here tried to explain it. But, I
do remember that it was something that I had to keep in mind with subpanels.


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Adding extra ground/neutral buss bar in electrical panel or add sub-panel? Mikepier Home Repair 84 April 4th 13 03:15 PM
Replacement of old MAIN all-fuse panel with a circut breaker panel Hat Home Repair 45 May 17th 10 02:04 PM
2nd panel running off of primary electrical panel Gary Home Repair 10 December 18th 06 06:56 PM
gluing panel in flat panel door igor Woodworking 2 November 29th 04 01:57 PM


All times are GMT +1. The time now is 04:40 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"