Condensation in dryer vent line
I noticed the other day that when my wife was doing a considerable amount of
drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David |
#2
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
Sounds like the vent pipe may be to long. Check with the dryer manufacturer
as to the maximum length and bends allowable for the machine. You have hot,moist air flowing through it, and the longer it is, the more opportunity it has to cool and condense "DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David |
#3
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
"DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David I had a similar problem with my dryer vent passing through the attic. I insulated the duct with duct wrap and it has been fine since. You might want to make sure that your vent pipe is clean. Too much lint will absorb moisture and restrict air flow. |
#4
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
Good point. I will look into it.
The day she was doing the laundry and I noticed the condensation, it was a very very cold day, which makes me think that I need to check the outside vent to see if any cold air could be getting in. I am also thinking about purchasing a dryer vent cleaning kit to make sure that there is no major buildup of lint so that the dryer is able to properly vent. David "RBM" rbm2(remove wrote in message ... Sounds like the vent pipe may be to long. Check with the dryer manufacturer as to the maximum length and bends allowable for the machine. You have hot,moist air flowing through it, and the longer it is, the more opportunity it has to cool and condense "DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David |
#5
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
Thanks for the advice.
Being in a heated basement, I am not sure the duct wrap is necessary, though I did see a very lousy / non-existent attempt to tape the joints between the sections of vent pipe. I agree that I should make sure that the ducts have been cleaned. David "John Grabowski" wrote in message ... "DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David I had a similar problem with my dryer vent passing through the attic. I insulated the duct with duct wrap and it has been fine since. You might want to make sure that your vent pipe is clean. Too much lint will absorb moisture and restrict air flow. |
#6
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
In my own situation, while I did not have moisture dripping, I found that
aluminium pipe draws the heat out causing condensation. The moisture inside the pipe quickly gathers lint, so much that I was having to clean out the pipes every 3 months. The 4 inch diameter tubes had about 1/2 to 3/4" of lint stuck to the tube walls. I replaced the run (this is for an electric dryer, do not do this for a gas dryer) with 4" PVC sewer/drain pipe. I have not had to clean it out for the past 12 years. The plastic pipe holds the heat in and prevents or reduces any condensation. My idea to use PVC was based on seeing furnaces that used ABS or PVC drain pipe as a vent. "DL" wrote in message news:tFgOf.28426$2c4.22227@dukeread11... Thanks for the advice. Being in a heated basement, I am not sure the duct wrap is necessary, though I did see a very lousy / non-existent attempt to tape the joints between the sections of vent pipe. I agree that I should make sure that the ducts have been cleaned. David "John Grabowski" wrote in message ... "DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David I had a similar problem with my dryer vent passing through the attic. I insulated the duct with duct wrap and it has been fine since. You might want to make sure that your vent pipe is clean. Too much lint will absorb moisture and restrict air flow. |
#7
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
your dryer vent is definatly too long, no doubt about it. -- whodat ------------------------------------------------------------------------ whodat's Profile: http://www.HomeOutfit.com/member.php?userid=35 View this thread: http://www.HomeOutfit.com/showthread.php?t=67674 |
#8
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
Really good idea. though it would be major surgery to replace the 16' run
from the dryer upstairs (3rd level) to the basement.the basement run would be simple. How did you connect from the dryer to the PVC? I am almost scared as to what I will find in the vent ducts when I clean them. David "EXT" etonks@sunstormADD-DOT-COM wrote in message anews.com... In my own situation, while I did not have moisture dripping, I found that aluminium pipe draws the heat out causing condensation. The moisture inside the pipe quickly gathers lint, so much that I was having to clean out the pipes every 3 months. The 4 inch diameter tubes had about 1/2 to 3/4" of lint stuck to the tube walls. I replaced the run (this is for an electric dryer, do not do this for a gas dryer) with 4" PVC sewer/drain pipe. I have not had to clean it out for the past 12 years. The plastic pipe holds the heat in and prevents or reduces any condensation. My idea to use PVC was based on seeing furnaces that used ABS or PVC drain pipe as a vent. "DL" wrote in message news:tFgOf.28426$2c4.22227@dukeread11... Thanks for the advice. Being in a heated basement, I am not sure the duct wrap is necessary, though I did see a very lousy / non-existent attempt to tape the joints between the sections of vent pipe. I agree that I should make sure that the ducts have been cleaned. David "John Grabowski" wrote in message ... "DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David I had a similar problem with my dryer vent passing through the attic. I insulated the duct with duct wrap and it has been fine since. You might want to make sure that your vent pipe is clean. Too much lint will absorb moisture and restrict air flow. |
#9
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
I used a short length of flexible vinyl tubing, just enough to allow me to
make the connection and move the dryer that last few inches against the wall after I had extracted myself. Had to reduce the diameter of the PVC sewer pipe slightly to fit the vinyl tubing over it. Used a heat gun to soften the pipe and a tightened large gear clamp to shrink the diameter until it was the right size. Worked like a charm. "DL" wrote in message news:7VhOf.28448$2c4.11702@dukeread11... Really good idea. though it would be major surgery to replace the 16' run from the dryer upstairs (3rd level) to the basement.the basement run would be simple. How did you connect from the dryer to the PVC? I am almost scared as to what I will find in the vent ducts when I clean them. David "EXT" etonks@sunstormADD-DOT-COM wrote in message anews.com... In my own situation, while I did not have moisture dripping, I found that aluminium pipe draws the heat out causing condensation. The moisture inside the pipe quickly gathers lint, so much that I was having to clean out the pipes every 3 months. The 4 inch diameter tubes had about 1/2 to 3/4" of lint stuck to the tube walls. I replaced the run (this is for an electric dryer, do not do this for a gas dryer) with 4" PVC sewer/drain pipe. I have not had to clean it out for the past 12 years. The plastic pipe holds the heat in and prevents or reduces any condensation. My idea to use PVC was based on seeing furnaces that used ABS or PVC drain pipe as a vent. "DL" wrote in message news:tFgOf.28426$2c4.22227@dukeread11... Thanks for the advice. Being in a heated basement, I am not sure the duct wrap is necessary, though I did see a very lousy / non-existent attempt to tape the joints between the sections of vent pipe. I agree that I should make sure that the ducts have been cleaned. David "John Grabowski" wrote in message ... "DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David I had a similar problem with my dryer vent passing through the attic. I insulated the duct with duct wrap and it has been fine since. You might want to make sure that your vent pipe is clean. Too much lint will absorb moisture and restrict air flow. |
#10
Posted to alt.home.repair
|
|||
|
|||
Condensation in dryer vent line
16' is not too long for a dryer vent, although the shorter the better.
Have you considered terminating the vent to the exterior near the dryer? If you need help with the cleanout, which is clearly needed, visit http://CleanYourOwnDryerVent.com DL wrote: Really good idea. though it would be major surgery to replace the 16' run from the dryer upstairs (3rd level) to the basement.the basement run would be simple. How did you connect from the dryer to the PVC? I am almost scared as to what I will find in the vent ducts when I clean them. David "EXT" etonks@sunstormADD-DOT-COM wrote in message anews.com... In my own situation, while I did not have moisture dripping, I found that aluminium pipe draws the heat out causing condensation. The moisture inside the pipe quickly gathers lint, so much that I was having to clean out the pipes every 3 months. The 4 inch diameter tubes had about 1/2 to 3/4" of lint stuck to the tube walls. I replaced the run (this is for an electric dryer, do not do this for a gas dryer) with 4" PVC sewer/drain pipe. I have not had to clean it out for the past 12 years. The plastic pipe holds the heat in and prevents or reduces any condensation. My idea to use PVC was based on seeing furnaces that used ABS or PVC drain pipe as a vent. "DL" wrote in message news:tFgOf.28426$2c4.22227@dukeread11... Thanks for the advice. Being in a heated basement, I am not sure the duct wrap is necessary, though I did see a very lousy / non-existent attempt to tape the joints between the sections of vent pipe. I agree that I should make sure that the ducts have been cleaned. David "John Grabowski" wrote in message ... "DL" wrote in message news:Rr8Of.28419$2c4.23147@dukeread11... I noticed the other day that when my wife was doing a considerable amount of drying, that there was condensation in the dryer vent piping. The piping comes from the upper floor, down through the main level into the basement and then goes to an exterior wall and exits our home. I noticed dripping from the vent piping at the 90 degree turn in the basement where it comes from the upper levels. Is this normal? Don't know that I have ever noticed this before, mainly because it is not something have ever looked for. David I had a similar problem with my dryer vent passing through the attic. I insulated the duct with duct wrap and it has been fine since. You might want to make sure that your vent pipe is clean. Too much lint will absorb moisture and restrict air flow. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Home clothes dryer vent lets cold in | Home Repair | |||
Inline Dryer Vent | Home Repair | |||
Dryer Vent Inline Diverter Energy Saver - Advice wanted | Home Repair | |||
dryer vent location | Home Repair | |||
Dryer vent to garage? | Home Repair |