Default So the wires go on the inside....

I was poking around my basement, made all the more attractive now that
Seattle has broken 100 for 3 days straight (yeah I don't want to hear it
from all you hot climate people). Anyway I was contemplating putting up
some drywall, seeing as the walls don't have any. I noticed however that
the previous owner didn't bother to run the romex through the boards, but
rather stapled it on the side the drywall should go. I trust that I'll have
to pull that wire and re-route it through the studs before putting up
drywall.

I guess my question is, and I will get an inspector for this job as well,
but the wires should be routed through the middle of the wall stud -
correct?


  #2   Report Post  
Posted to alt.home.repair
RBM RBM is offline
external usenet poster
 
Posts: 1,690
Default So the wires go on the inside....

Yes
"Eigenvector" wrote in message
...
I was poking around my basement, made all the more attractive now that
Seattle has broken 100 for 3 days straight (yeah I don't want to hear it
from all you hot climate people). Anyway I was contemplating putting up
some drywall, seeing as the walls don't have any. I noticed however that
the previous owner didn't bother to run the romex through the boards, but
rather stapled it on the side the drywall should go. I trust that I'll
have to pull that wire and re-route it through the studs before putting up
drywall.

I guess my question is, and I will get an inspector for this job as well,
but the wires should be routed through the middle of the wall stud -
correct?



  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,199
Default So the wires go on the inside....

if you put in a dropped cieling it doesnt matter since the wires would
be protected

  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 100
Default So the wires go on the inside....


I guess my question is, and I will get an inspector for this job as well,
but the wires should be routed through the middle of the wall stud -
correct?


Through the middle of he stud, nail plate required when cable is
1-1/4in. of stud edge.

  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,079
Default So the wires go on the inside....


"MDT at Paragon Home Inspections, LLC"
wrote in message
ups.com...

I guess my question is, and I will get an inspector for this job as well,
but the wires should be routed through the middle of the wall stud -
correct?


Through the middle of he stud, nail plate required when cable is
1-1/4in. of stud edge.

So if the nail plates go on the outside of the stud, does that effect how
the wallboard sits.




  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 66
Default So the wires go on the inside....

just how does a drop ceiling have anything to do with wiring on wall studs?
I can agree with this if the OP had said anything about the ceiling, but he
specifically said walls.

wrote in message
ups.com...
if you put in a dropped cieling it doesnt matter since the wires would
be protected



  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 59
Default So the wires go on the inside....


Eigenvector wrote:
"MDT at Paragon Home Inspections, LLC"
wrote in message
ups.com...

I guess my question is, and I will get an inspector for this job as well,
but the wires should be routed through the middle of the wall stud -
correct?


Through the middle of he stud, nail plate required when cable is
1-1/4in. of stud edge.

So if the nail plates go on the outside of the stud, does that effect how
the wallboard sits.


Nah. Only if you get real unlucky and have one board end just on the
plate, and the next board not hit at all, resulting in a little 1mm
drop between boards. In that case, just stick a second plate under the
other board. Otherwise, the boards are plenty flexible to get around a
1mm bump with no noticeable change.

  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,079
Default So the wires go on the inside....


"Bob" wrote in message
ups.com...

Eigenvector wrote:
"MDT at Paragon Home Inspections, LLC"
wrote in message
ups.com...

I guess my question is, and I will get an inspector for this job as
well,
but the wires should be routed through the middle of the wall stud -
correct?

Through the middle of he stud, nail plate required when cable is
1-1/4in. of stud edge.

So if the nail plates go on the outside of the stud, does that effect how
the wallboard sits.


They're thin enough where you won't even notice it.

Is drywall over basement walls in Washington a good idea? I would
think it may trap moisture.

Bob


Maybe I should have clarified, but it is the staircase that leads to the
basement that needs the drywall.

BTW: Since you mentioned it, assuming moisture is a problem, what else
would you put on the walls to cover up the studs and wiring?


  #9   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 201
Default So the wires go on the inside....

EV,

Cloth treatments might be better than wallboard for the exterior walls.
Drapes, tapestries, hangings, et c.. Put dry wall on the interior walls to
create variety.

Dave M.


  #10   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 557
Default So the wires go on the inside....

On Sun, 23 Jul 2006 17:13:50 -0700, "Eigenvector"
wrote:

I was poking around my basement, made all the more attractive now that
Seattle has broken 100 for 3 days straight (yeah I don't want to hear it
from all you hot climate people). Anyway I was contemplating putting up
some drywall, seeing as the walls don't have any. I noticed however that
the previous owner didn't bother to run the romex through the boards, but
rather stapled it on the side the drywall should go. I trust that I'll have
to pull that wire and re-route it through the studs before putting up
drywall.

I guess my question is, and I will get an inspector for this job as well,
but the wires should be routed through the middle of the wall stud -
correct?


imho:

Depending on the stud size(2x4) and orientation(thinest edges facing
inside and out of the room), generally yes. The idea is to have the
wire(this case NM) atleast 1.25" from a nailing surface.

To save time, and provide you more insulation, have you thought of
picking up 2x2's and just notching out areas for the wire, and attach
them to the existing studs? This will provide you the insulation
potential of 2x6 construction(assuming the orginial is normal
studding). Also, if you want further nail protection, install nail
plates.

Now all this is based on teh limited description you provided, so only
use this for a starting point deciding what to do. Not a How-To.

hth,

tom @ www.WorkAtHomePlans.com




  #11   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,489
Default So the wires go on the inside....

On Sun, 23 Jul 2006 17:13:50 -0700, "Eigenvector"
wrote:

I was poking around my basement, made all the more attractive now that
Seattle has broken 100 for 3 days straight (yeah I don't want to hear it
from all you hot climate people). Anyway I was contemplating putting up
some drywall, seeing as the walls don't have any. I noticed however that
the previous owner didn't bother to run the romex through the boards, but
rather stapled it on the side the drywall should go. I trust that I'll have
to pull that wire and re-route it through the studs before putting up
drywall.

I guess my question is, and I will get an inspector for this job as well,
but the wires should be routed through the middle of the wall stud -
correct?



Ideally, yes. But you can run the wires along a board, pipe, or rail
that protects the wire. If the wire is out-of-code there are probably
other issues as well.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Tracking hot wires inside walls Sasha Home Repair 10 April 30th 06 06:07 PM
Staple wires to inside of rim joist - allowed? [email protected] Home Repair 2 November 9th 05 02:09 PM
Combining wires to avoid voltage drop? 12/4 cable? Toller Home Repair 11 October 26th 05 10:09 PM
fishing 6 gauge wires through conduit zxcvbob Home Repair 21 January 11th 05 04:42 AM
telephone wiring questions spoon2001 Home Repair 3 August 14th 04 11:57 PM


All times are GMT +1. The time now is 01:35 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"