Grizzly G0500 8" Jointer on 220/20A circuit
I jut received my G0500. It is pre-wired for 220V and the 2HP motor
pulls 12A at that voltage. Currently (no pun intended) the main tools in my shop are a 2 1/2 HP Bandsaw and a 3HP table saw. I am a one-man shop and have no need for the bandsaw and table saw to be running simultaneously. So, they both run on a single 220V 20A 'dedicated' circuit. Neither tool manual suggested a maximum CB amperage. The Grizzly manual is very specific about running the Jointer on a (220) 15A circuit because "circuit breakers rated any higher are not adequate to protect the circuit." Earlier in the same paragraph, though, they talk about "...the following guidelines when choosing a circuit breaker." So, guidelines or edicts? I had planned on using the same 20A circuit for the jointer. If it pulls 12A under normal conditions, placing it on a 15A circuit seems to be hoping for the best. The internal wiring from the starter and switch on the jointer are 14 gauge. It appears to me from other sources that 14 gauge can easily handle 20A. I don't know about the other components, though. I am reluctant to disreguard a manufacturer's guidance. I suppose I will check with Grizzly support for their answer, but I am curious about how the rec feels about this question. Thanks for your help, Charlie |
#2
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
Seawulf wrote:
snip I am reluctant to disreguard a manufacturer's guidance. I suppose I will check with Grizzly support for their answer, but I am curious about how the rec feels about this question. Thanks for your help, Charlie Circuit breaker are meant to protect the wires to the outlets. The 20 amp cuicuit will be fine for the jointer. -- Jack Novak Buffalo, NY - USA (Remove -SPAM- to send email) |
#3
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
Seawulf wrote:
I jut received my G0500. It is pre-wired for 220V and the 2HP motor pulls 12A at that voltage. Currently (no pun intended) the main tools in my shop are a 2 1/2 HP Bandsaw and a 3HP table saw. I am a one-man shop and have no need for the bandsaw and table saw to be running simultaneously. So, they both run on a single 220V 20A 'dedicated' circuit. Neither tool manual suggested a maximum CB amperage. The Grizzly manual is very specific about running the Jointer on a (220) 15A circuit because "circuit breakers rated any higher are not adequate to protect the circuit." Earlier in the same paragraph, though, they talk about "...the following guidelines when choosing a circuit breaker." So, guidelines or edicts? I had planned on using the same 20A circuit for the jointer. If it pulls 12A under normal conditions, placing it on a 15A circuit seems to be hoping for the best. The internal wiring from the starter and switch on the jointer are 14 gauge. It appears to me from other sources that 14 gauge can easily handle 20A. I don't know about the other components, though. I am reluctant to disreguard a manufacturer's guidance. I suppose I will check with Grizzly support for their answer, but I am curious about how the rec feels about this question. Thanks for your help, Charlie What is the gauge of the power cord on the jointer, 14 gauge ? If something fails you could draw 19 + amps on that power cord. Bet I can find a bottom feeding lawyer that would love someone telling you to plug your jointer into a 20 amp circuit. Guideline: A circuit should not normally draw more than 80% of the rated amperage of the breaker. 15 amps x .8 = 12 amps. Edict: 14 Gauge Wire max 15 Amps. Your on your own Seawulf. Hope you can swim. BTW I have a King 15" planer, identical to a Grizzly 15", See thread titled "Twins" a few days ago. 2 HP, probably the same motor as yours. Runs fine on a 15 amp. 240 V circuit. |
#4
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
I run my G0500 on a 220v 20 amp circuit. I haven't let the smoke out of it
so far. If you have a short that would cause the breaker to go, it shouldn't be a problem. "Seawulf" wrote in message news:Q3vcf.18$7B.1@fed1read02... I jut received my G0500. It is pre-wired for 220V and the 2HP motor pulls 12A at that voltage. Currently (no pun intended) the main tools in my shop are a 2 1/2 HP Bandsaw and a 3HP table saw. I am a one-man shop and have no need for the bandsaw and table saw to be running simultaneously. So, they both run on a single 220V 20A 'dedicated' circuit. Neither tool manual suggested a maximum CB amperage. The Grizzly manual is very specific about running the Jointer on a (220) 15A circuit because "circuit breakers rated any higher are not adequate to protect the circuit." Earlier in the same paragraph, though, they talk about "...the following guidelines when choosing a circuit breaker." So, guidelines or edicts? I had planned on using the same 20A circuit for the jointer. If it pulls 12A under normal conditions, placing it on a 15A circuit seems to be hoping for the best. The internal wiring from the starter and switch on the jointer are 14 gauge. It appears to me from other sources that 14 gauge can easily handle 20A. I don't know about the other components, though. I am reluctant to disreguard a manufacturer's guidance. I suppose I will check with Grizzly support for their answer, but I am curious about how the rec feels about this question. Thanks for your help, Charlie |
#5
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
I am reluctant to disreguard a manufacturer's guidance. I suppose I will check with Grizzly support for their answer, but I am curious about how the rec feels about this question. My desk lamp has #18 wire, and it is plugged into a 20a circuit. By Grizzley's reasoning, it should have a 7a breaker instead. I suppose it is possible that they know something we don't; that defective design or components cause the machine to draw too much current for a period of time, and is resulting in damaged machines. Rather than fix it, they are requiring you to prevent it will small breakers. Unlikely, but possible. Personally I would use the 20a circuit. BTW, my cottage's 23.5a water heater was hooked up with #12 for 20 years without any problems; if that gives you any confidence. Still, I replaced it with #10. |
#6
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
14 gauge wire is rated for 20 amp service. He'll be fine using the 20
amp circuit. Bob |
#7
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
Bob wrote:
14 gauge wire is rated for 20 amp service. He'll be fine using the 20 amp circuit. Bob http://tinyurl.com/9v26p |
#8
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
"LM" wrote in message ... Seawulf wrote: Bet I can find a bottom feeding lawyer that would love someone telling you to plug your jointer into a 20 amp circuit. I bet you could. Some lawyers are that stupid. He'd loose. |
#9
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
That's very interesting, considering I've got the G0586, which is
supposed to be the replacement for the 500, and the spec says it pulls 12A at 220V and that it's a 2HP motor, and recommends a 20A fuse. http://images.grizzly.com/grizzlycom...s/G0586_ds.pdf |
#10
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
I installed the starter switch box on this jointer a few days ago. It
includes a "Thermal Overload" device with a dial setting. The dial was set to 15 at the factory. This would appear to me - non-electrician - to protect the motor from high temp from, for example, an over-current situation, which is the subject of this thread. If that is the case, the 15A CB on the circuit would be a back-up not the sole protection. I still have not received a reply from Grizzly tech support on this question. Charlie |
#12
Posted to rec.woodworking
|
|||
|
|||
Grizzly G0500 8" Jointer on 220/20A circuit
I received the reply from Grizzly Technical Support on this question.
First, let me say that the delay was apparently my fault. They attempted to email me over a week ago, but I did not receive the message. This was apparently due to my SPAM controls. After I entered their email address into my Address Book, I had no problems. The reply simply said that I could use the Jointer on a 20A circuit. No surprise to most of you who responded. Thanks for your help, Charlie |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Should I purchase this used 8" jointer & 15" planer??? | Woodworking | |||
Locating Circuit Breaker( | Home Repair | |||
Electric circuit breaker | Home Repair | |||
Simple circuit to hold relay on after input falls | Electronics | |||
Is it a radial or ring circuit? | UK diy |