Vaillant condensate circuit information:

It is not necessary to provide air breaks or extra traps
in the discharge pipe as there is already a 75mm high
trap inside the boiler. Fitting an extra trap may cause
the boiler siphon to work incorrectly.

(b) Connecting into the internal discharge branch
(e.g. sink waste or washing machine) with an external
termination, the condensate drain pipe should have a
minimum diameter of 22mm with no length restriction
and should incorporate a trap with a 75mm (3)
seal. The connection should preferably made down
stream of the sink waste trap, if the connection is
only possible up stream, then an air break is needed
between the two traps. This is normally provided by
the sink waste.

Don't those two contradict each other?


NT
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 25,191
Default Plumbing instructions self contradictory?

On 25/08/2016 12:21, wrote:
Vaillant condensate circuit information:

It is not necessary to provide air breaks or extra traps
in the discharge pipe as there is already a 75mm high
trap inside the boiler. Fitting an extra trap may cause
the boiler siphon to work incorrectly.

(b) Connecting into the internal discharge branch
(e.g. sink waste or washing machine) with an external
termination, the condensate drain pipe should have a
minimum diameter of 22mm with no length restriction
and should incorporate a trap with a 75mm (3)
seal. The connection should preferably made down
stream of the sink waste trap, if the connection is
only possible up stream, then an air break is needed
between the two traps. This is normally provided by
the sink waste.

Don't those two contradict each other?


Not quite (although it could have been worded better)! What they are
seeking to avoid is having the condensate drain connected directly to a
second trap without any air break. So into an open waste pipe before a
trap is fine, and into a waste pipe that is open at the far end but
after a trap is also ok.

(I find that a washing machine stand pipe waste is often a handy place
to take a condensate drain - but a tee on the top and a reducing bush to
take the 22mm pipe, then the side branch can be left open for the hose
from the washing machine etc)


--
Cheers,

John.

/================================================== ===============\
| Internode Ltd -
http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 12,364
Default Plumbing instructions self contradictory?

On Thursday, 25 August 2016 18:41:46 UTC+1, John Rumm wrote:
On 25/08/2016 12:21, tabbypurr wrote:


Vaillant condensate circuit information:

It is not necessary to provide air breaks or extra traps
in the discharge pipe as there is already a 75mm high
trap inside the boiler. Fitting an extra trap may cause
the boiler siphon to work incorrectly.

(b) Connecting into the internal discharge branch
(e.g. sink waste or washing machine) with an external
termination, the condensate drain pipe should have a
minimum diameter of 22mm with no length restriction
and should incorporate a trap with a 75mm (3)
seal. The connection should preferably made down
stream of the sink waste trap, if the connection is
only possible up stream, then an air break is needed
between the two traps. This is normally provided by
the sink waste.

Don't those two contradict each other?


Not quite (although it could have been worded better)! What they are
seeking to avoid is having the condensate drain connected directly to a
second trap without any air break. So into an open waste pipe before a
trap is fine, and into a waste pipe that is open at the far end but
after a trap is also ok.

(I find that a washing machine stand pipe waste is often a handy place
to take a condensate drain - but a tee on the top and a reducing bush to
take the 22mm pipe, then the side branch can be left open for the hose
from the washing machine etc)


ahh, makes sense Cheers.


NT
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Plumbing Code - Can I tie my bathroom exaust fan into the main plumbing vent to the outside. johnnymo Home Repair 29 December 9th 18 02:08 AM
Read the instructions! The Medway Handyman UK diy 20 April 3rd 11 11:03 AM
Question on plumbing average cost- location New England...For newtoilet and change pedestal plumbing KOS Home Repair 17 March 26th 10 10:37 PM
instructions Luke Price Electronics Repair 0 March 10th 09 01:21 AM
co-ax instructions Mike Metalworking 30 March 26th 04 05:12 AM


All times are GMT +1. The time now is 11:37 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"