  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2
Default Potterton Suprima 50 HE Boiler problem

Hi,
I have a Potterton Suprima HE 50 boiler that was working fine until Saturday.

The boiler will fire up as normal for a few moments but then go on to lockdown.

According to the fault board indicator (the lockdown light is the only one alight and is flashing) that this is an air pressure signal fault.

Any ideas what the problem may be and what is needed to fix this?

Many thanks
Jaime
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2
Default Potterton Suprima 50 HE Boiler problem

Thanks Tony.

Had suspected that.

Regards
Jaime

  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,819
Default Potterton Suprima 50 HE Boiler problem

In message , tony sayer
writes
In article ,
scribeth thus
Hi,
I have a Potterton Suprima HE 50 boiler that was working fine until Saturday.

The boiler will fire up as normal for a few moments but then go on to
lockdown.

According to the fault board indicator (the lockdown light is the only one
alight and is flashing) that this is an air pressure signal fault.

Any ideas what the problem may be and what is needed to fix this?

Many thanks
Jaime




Give Geoff Raden a bell..

http://www.cetltd.com/

Potterton Suprima;!..

Dead cert a replacement PCB required...

He emailed me today


--
geoff


  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,819
Default Potterton Suprima 50 HE Boiler problem

In message , Tim Lamb
writes
In message ,
writes
Thanks Tony.

Had suspected that.


Don't know about the 50 HE but my Suprima cct. board failed after a
service visit.

Check the solder joints with a magnifying glass where the mains
connector is mounted. In my case, flow solder bath techniques did not
provide enough time/heat to make sound joints.

No Tim -

The HE is completely different


--
geoff
  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 5,386
Default Potterton Suprima 50 HE Boiler problem

On 19/11/2012 22:22, geoff wrote:
In message , tony sayer
writes
In article ,
scribeth thus
Hi,
I have a Potterton Suprima HE 50 boiler that was working fine until
Saturday.

The boiler will fire up as normal for a few moments but then go on to
lockdown.

According to the fault board indicator (the lockdown light is the
only one
alight and is flashing) that this is an air pressure signal fault.

Any ideas what the problem may be and what is needed to fix this?

Many thanks
Jaime




Give Geoff Raden a bell..

http://www.cetltd.com/

Potterton Suprima;!..

Dead cert a replacement PCB required...

He emailed me today


I too have a Suprima question.

Apparently the "green" light sometimes comes on, boiler does not start
up, and only works again when the green light is pushed. Of course, it
behaved perfectly when I was there. (And it is a two-hour drive away.)
Is this a symptom of the PCB issues that others have been going on
about? Or have I got wrong end of stick?

https://dl.dropbox.com/u/318411/Suprima%2060.jpg

--
Rod
  #8   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,819
Default Potterton Suprima 50 HE Boiler problem

In message , polygonum
writes

I too have a Suprima question.


Pcb or module?


Apparently the "green" light sometimes comes on, boiler does not start
up, and only works again when the green light is pushed


You mean the reset button? Pushing the LED won't achieve an awful lot

. Of course, it behaved perfectly when I was there. (And it is a
two-hour drive away.) Is this a symptom of the PCB issues that others
have been going on about?


Probably, but not really possible to say anything for definite

As Ed Sirett (ex of this parish) once said, its the only boiler where he
changes the pcb then looks to see what else might be wrong


Or have I got wrong end of stick?

https://dl.dropbox.com/u/318411/Suprima%2060.jpg


--
geoff
  #9   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 5,386
Default Potterton Suprima 50 HE Boiler problem

On 19/11/2012 22:44, geoff wrote:
In message , polygonum
writes

I too have a Suprima question.


Pcb or module?


Apparently the "green" light sometimes comes on, boiler does not start
up, and only works again when the green light is pushed


You mean the reset button? Pushing the LED won't achieve an awful lot

. Of course, it behaved perfectly when I was there. (And it is a
two-hour drive away.) Is this a symptom of the PCB issues that others
have been going on about?


Probably, but not really possible to say anything for definite

As Ed Sirett (ex of this parish) once said, its the only boiler where he
changes the pcb then looks to see what else might be wrong


Or have I got wrong end of stick?

https://dl.dropbox.com/u/318411/Suprima%2060.jpg


Well she said she pressed the green light - but I suspect that it is the
reset button really. Her eyes are somewhat challenged.

I'll email.

--
Rod
  #10   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 11,175
Default Potterton Suprima 50 HE Boiler problem

In article ,
geoff writes:
In message , polygonum
writes

I too have a Suprima question.


Pcb or module?


Apparently the "green" light sometimes comes on, boiler does not start
up, and only works again when the green light is pushed


You mean the reset button? Pushing the LED won't achieve an awful lot


Flex the circuit board? ;-)
Which in a Suprima, might even work...

--
Andrew Gabriel
[email address is not usable -- followup in the newsgroup]


  #11   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,819
Default Potterton Suprima 50 HE Boiler problem

In message , Andrew Gabriel
writes
In article ,
geoff writes:
In message , polygonum
writes

I too have a Suprima question.


Pcb or module?


Apparently the "green" light sometimes comes on, boiler does not start
up, and only works again when the green light is pushed


You mean the reset button? Pushing the LED won't achieve an awful lot


Flex the circuit board? ;-)
Which in a Suprima, might even work...

Shredder's more the mark

Flexing a suprima pcb ?

how many pads do you think you can break away from the tracks in one go
?

--
geoff
  #12   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 6,938
Default Potterton Suprima 50 HE Boiler problem

In message , geoff
writes
In message , Tim Lamb
writes
In message ,
writes
Thanks Tony.

Had suspected that.


Don't know about the 50 HE but my Suprima cct. board failed after a
service visit.

Check the solder joints with a magnifying glass where the mains
connector is mounted. In my case, flow solder bath techniques did not
provide enough time/heat to make sound joints.

No Tim -

The HE is completely different


You mean it is worse?:-)

--
Tim Lamb
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Another Potterton Suprima problem [email protected] UK diy 13 May 10th 07 05:18 PM
Potterton Suprima Boiler GaryEwer UK diy 5 November 29th 06 08:08 PM
Potterton Suprima Boiler - Avoid or not ? Jim UK diy 15 August 6th 06 10:24 PM
Potterton Suprima 80 boiler John Edgar UK diy 5 June 24th 05 09:25 PM
CH boiler - making droning noise - Potterton Suprima 60 Eric the Red UK diy 2 September 29th 03 03:01 PM