UK diy (uk.d-i-y) For the discussion of all topics related to diy (do-it-yourself) in the UK. All levels of experience and proficency are welcome to join in to ask questions or offer solutions.

Reply
 
LinkBack Thread Tools Search this Thread Display Modes
  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,688
Default boiler 20mm condensate pipe

Simple question: can the boiler 20mm
condensate pipe commonly used be bent enough to get it fed through
25mm holes in joists that are 400mm apart ?
Thanks,
Simon.
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,688
Default boiler 20mm condensate pipe

On Mar 12, 10:31*am, sm_jamieson wrote:
Simple question: can the boiler 20mm
condensate pipe commonly used be bent enough to get it fed through
25mm holes in joists that are 400mm apart ?
Thanks,
Simon.


Just to clarify, I obviously mean getting the pipe into central holes
in the joists
when the next joist along is untouched, forcing it down between 2
joists and into the holes.
Simon.
  #3   Report Post  
Posted to uk.d-i-y
GB GB is offline
external usenet poster
 
Posts: 4,768
Default boiler 20mm condensate pipe

sm_jamieson wrote:
On Mar 12, 10:31 am, sm_jamieson wrote:
Simple question: can the boiler 20mm
condensate pipe commonly used be bent enough to get it fed through
25mm holes in joists that are 400mm apart ?
Thanks,
Simon.


Just to clarify, I obviously mean getting the pipe into central holes
in the joists
when the next joist along is untouched, forcing it down between 2
joists and into the holes.
Simon.


Can I just ask why a condensate pipe needs to be 20mm? I was looking at a
condensate pump recently, and the outlet pipe seemed to be about 5mm.



--
Murphy's ultimate law is that if something that could go wrong doesn't,
it turns out that it would have been better if it had gone wrong.


  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,688
Default boiler 20mm condensate pipe

On Mar 12, 12:00*pm, "GB" wrote:
sm_jamieson wrote:
On Mar 12, 10:31 am, sm_jamieson wrote:
Simple question: can the boiler 20mm
condensate pipe commonly used be bent enough to get it fed through
25mm holes in joists that are 400mm apart ?
Thanks,
Simon.


Just to clarify, I obviously mean getting the pipe into central holes
in the joists
when the next joist along is untouched, forcing it down between 2
joists and into the holes.
Simon.


Can I just ask why a condensate pipe needs to be 20mm? I was looking at a
condensate pump recently, and the outlet pipe seemed to be about 5mm.

I think 20mm is the "standard".
Actually I was thinking of running part in 32mm (!) just in case it
ever got blocked (and/or)
I could then use it for a basin if I ever wanted one in the room near
the boiler.
Anyway, 10mm is fine for central heating you might say.
The difference is the condensate is dribbling out and has to drain
using gravity so it is
moving slowly and more liable for deposits to collect (although it
should be pure water ?)
or even surface tension to have an affect (at 5mm).
If pumping you can allow for a smaller bore, but still 5mm seems a bit
small.
Simon.
  #5   Report Post  
Posted to uk.d-i-y
GB GB is offline
external usenet poster
 
Posts: 4,768
Default boiler 20mm condensate pipe

sm_jamieson wrote:
On Mar 12, 12:00 pm, "GB" wrote:
sm_jamieson wrote:
On Mar 12, 10:31 am, sm_jamieson wrote:
Simple question: can the boiler 20mm
condensate pipe commonly used be bent enough to get it fed through
25mm holes in joists that are 400mm apart ?
Thanks,
Simon.


Just to clarify, I obviously mean getting the pipe into central
holes in the joists
when the next joist along is untouched, forcing it down between 2
joists and into the holes.
Simon.


Can I just ask why a condensate pipe needs to be 20mm? I was looking
at a condensate pump recently, and the outlet pipe seemed to be
about 5mm.

I think 20mm is the "standard".
Actually I was thinking of running part in 32mm (!) just in case it
ever got blocked (and/or)
I could then use it for a basin if I ever wanted one in the room near
the boiler.
Anyway, 10mm is fine for central heating you might say.
The difference is the condensate is dribbling out and has to drain
using gravity so it is
moving slowly and more liable for deposits to collect (although it
should be pure water ?)
or even surface tension to have an affect (at 5mm).
If pumping you can allow for a smaller bore, but still 5mm seems a bit
small.
Simon.


--
Murphy's ultimate law is that if something that could go wrong doesn't,
it turns out that it would have been better if it had gone wrong.




  #6   Report Post  
Posted to uk.d-i-y
GB GB is offline
external usenet poster
 
Posts: 4,768
Default boiler 20mm condensate pipe

sm_jamieson wrote:

I think 20mm is the "standard".
Actually I was thinking of running part in 32mm (!) just in case it
ever got blocked (and/or)
I could then use it for a basin if I ever wanted one in the room near
the boiler.
Anyway, 10mm is fine for central heating you might say.
The difference is the condensate is dribbling out and has to drain
using gravity so it is
moving slowly and more liable for deposits to collect (although it
should be pure water ?)


No it's got some acid in it from the dissolved carbon dioxide. I'd have
thought that would prevent any carbonate build-up even in the presence of
air.

or even surface tension to have an affect (at 5mm).


If pumping you can allow for a smaller bore, but still 5mm seems a bit
small.


It might be more than 5mm. Take a look at picture 2 here
http://www.screwfix.com/prods/27313/...-Acid-Disposer
What size is the flexible tubing would you say?


  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,982
Default boiler 20mm condensate pipe

On Sat, 12 Mar 2011 02:53:12 -0800, sm_jamieson wrote:

On Mar 12, 10:31Â*am, sm_jamieson wrote:
Simple question: can the boiler 20mm
condensate pipe commonly used be bent enough to get it fed through 25mm
holes in joists that are 400mm apart ? Thanks,
Simon.


Just to clarify, I obviously mean getting the pipe into central holes in
the joists
when the next joist along is untouched, forcing it down between 2 joists
and into the holes.
Simon.



Possibly, otherwise use 22mm PB or PEX - the o/d of overflow is nominally
about 21.5mm (not 20mm) and can be joined using push-fit couplings.
(Since the pipework isn't under pressure mechanical grip onto the smaller
pipe isn't really an issue.)



--
John Stumbles

Pessimists are never disappointed
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Good old Boiler Condensate pipe freezing. Graham M UK diy 3 December 21st 10 05:24 PM
Condensing Boiler problem, but Not frozen condensate pipe. JonG[_2_] UK diy 21 January 12th 10 09:31 AM
Condensate Pipe On Combi Boiler ? the_constructor[_2_] UK diy 16 December 26th 09 10:07 AM
New boiler condensate pipe plumbing - advice please jim2000 UK diy 3 May 18th 06 11:16 PM
Boiler-attic, condensate into vent pipe from soil stack. Mike UK diy 5 April 27th 05 12:34 PM


All times are GMT +1. The time now is 06:57 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"