Home |
Search |
Today's Posts |
|
UK diy (uk.d-i-y) For the discussion of all topics related to diy (do-it-yourself) in the UK. All levels of experience and proficency are welcome to join in to ask questions or offer solutions. |
Reply |
|
LinkBack | Thread Tools | Display Modes |
#1
Posted to uk.d-i-y
|
|||
|
|||
boiler 20mm condensate pipe
Simple question: can the boiler 20mm
condensate pipe commonly used be bent enough to get it fed through 25mm holes in joists that are 400mm apart ? Thanks, Simon. |
#2
Posted to uk.d-i-y
|
|||
|
|||
boiler 20mm condensate pipe
On Mar 12, 10:31*am, sm_jamieson wrote:
Simple question: can the boiler 20mm condensate pipe commonly used be bent enough to get it fed through 25mm holes in joists that are 400mm apart ? Thanks, Simon. Just to clarify, I obviously mean getting the pipe into central holes in the joists when the next joist along is untouched, forcing it down between 2 joists and into the holes. Simon. |
#3
Posted to uk.d-i-y
|
|||
|
|||
boiler 20mm condensate pipe
sm_jamieson wrote:
On Mar 12, 10:31 am, sm_jamieson wrote: Simple question: can the boiler 20mm condensate pipe commonly used be bent enough to get it fed through 25mm holes in joists that are 400mm apart ? Thanks, Simon. Just to clarify, I obviously mean getting the pipe into central holes in the joists when the next joist along is untouched, forcing it down between 2 joists and into the holes. Simon. Can I just ask why a condensate pipe needs to be 20mm? I was looking at a condensate pump recently, and the outlet pipe seemed to be about 5mm. -- Murphy's ultimate law is that if something that could go wrong doesn't, it turns out that it would have been better if it had gone wrong. |
#4
Posted to uk.d-i-y
|
|||
|
|||
boiler 20mm condensate pipe
On Mar 12, 12:00*pm, "GB" wrote:
sm_jamieson wrote: On Mar 12, 10:31 am, sm_jamieson wrote: Simple question: can the boiler 20mm condensate pipe commonly used be bent enough to get it fed through 25mm holes in joists that are 400mm apart ? Thanks, Simon. Just to clarify, I obviously mean getting the pipe into central holes in the joists when the next joist along is untouched, forcing it down between 2 joists and into the holes. Simon. Can I just ask why a condensate pipe needs to be 20mm? I was looking at a condensate pump recently, and the outlet pipe seemed to be about 5mm. I think 20mm is the "standard". Actually I was thinking of running part in 32mm (!) just in case it ever got blocked (and/or) I could then use it for a basin if I ever wanted one in the room near the boiler. Anyway, 10mm is fine for central heating you might say. The difference is the condensate is dribbling out and has to drain using gravity so it is moving slowly and more liable for deposits to collect (although it should be pure water ?) or even surface tension to have an affect (at 5mm). If pumping you can allow for a smaller bore, but still 5mm seems a bit small. Simon. |
#5
Posted to uk.d-i-y
|
|||
|
|||
boiler 20mm condensate pipe
sm_jamieson wrote:
On Mar 12, 12:00 pm, "GB" wrote: sm_jamieson wrote: On Mar 12, 10:31 am, sm_jamieson wrote: Simple question: can the boiler 20mm condensate pipe commonly used be bent enough to get it fed through 25mm holes in joists that are 400mm apart ? Thanks, Simon. Just to clarify, I obviously mean getting the pipe into central holes in the joists when the next joist along is untouched, forcing it down between 2 joists and into the holes. Simon. Can I just ask why a condensate pipe needs to be 20mm? I was looking at a condensate pump recently, and the outlet pipe seemed to be about 5mm. I think 20mm is the "standard". Actually I was thinking of running part in 32mm (!) just in case it ever got blocked (and/or) I could then use it for a basin if I ever wanted one in the room near the boiler. Anyway, 10mm is fine for central heating you might say. The difference is the condensate is dribbling out and has to drain using gravity so it is moving slowly and more liable for deposits to collect (although it should be pure water ?) or even surface tension to have an affect (at 5mm). If pumping you can allow for a smaller bore, but still 5mm seems a bit small. Simon. -- Murphy's ultimate law is that if something that could go wrong doesn't, it turns out that it would have been better if it had gone wrong. |
#6
Posted to uk.d-i-y
|
|||
|
|||
boiler 20mm condensate pipe
sm_jamieson wrote:
I think 20mm is the "standard". Actually I was thinking of running part in 32mm (!) just in case it ever got blocked (and/or) I could then use it for a basin if I ever wanted one in the room near the boiler. Anyway, 10mm is fine for central heating you might say. The difference is the condensate is dribbling out and has to drain using gravity so it is moving slowly and more liable for deposits to collect (although it should be pure water ?) No it's got some acid in it from the dissolved carbon dioxide. I'd have thought that would prevent any carbonate build-up even in the presence of air. or even surface tension to have an affect (at 5mm). If pumping you can allow for a smaller bore, but still 5mm seems a bit small. It might be more than 5mm. Take a look at picture 2 here http://www.screwfix.com/prods/27313/...-Acid-Disposer What size is the flexible tubing would you say? |
#7
Posted to uk.d-i-y
|
|||
|
|||
boiler 20mm condensate pipe
On Sat, 12 Mar 2011 02:53:12 -0800, sm_jamieson wrote:
On Mar 12, 10:31Â*am, sm_jamieson wrote: Simple question: can the boiler 20mm condensate pipe commonly used be bent enough to get it fed through 25mm holes in joists that are 400mm apart ? Thanks, Simon. Just to clarify, I obviously mean getting the pipe into central holes in the joists when the next joist along is untouched, forcing it down between 2 joists and into the holes. Simon. Possibly, otherwise use 22mm PB or PEX - the o/d of overflow is nominally about 21.5mm (not 20mm) and can be joined using push-fit couplings. (Since the pipework isn't under pressure mechanical grip onto the smaller pipe isn't really an issue.) -- John Stumbles Pessimists are never disappointed |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Good old Boiler Condensate pipe freezing. | UK diy | |||
Condensing Boiler problem, but Not frozen condensate pipe. | UK diy | |||
Condensate Pipe On Combi Boiler ? | UK diy | |||
New boiler condensate pipe plumbing - advice please | UK diy | |||
Boiler-attic, condensate into vent pipe from soil stack. | UK diy |