I'm running both sides of a 2.5 T&E ring through the same 16x32mm
conduit
including running one 2.5 T&E unadulterated neatly through the back of
the
30mm pattress whilst the other one is cut, stripped, trimmed, and
twisted.

I've read through my books and I cannot see anything saying that I
cannot do that, but you guys seem to have an encyclopaedia's knowledge
of
the regs so I thought whilst I'm still early on I'll ask for
comments.
Better to fix things now then to be shot down by the BCO or P
Competant..

Any comments?
JJ

- this was on the bottom of a longer rambling post I have now deleted,
in the hope of tempting some replies
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,360
Default Simple mains question..

On Tue, 26 Jan 2010 06:02:21 -0800, JJ wibbled:

I'm running both sides of a 2.5 T&E ring through the same 16x32mm
conduit
including running one 2.5 T&E unadulterated neatly through the back of
the
30mm pattress whilst the other one is cut, stripped, trimmed, and
twisted.


I don't see any issues. Technically, with round conduit you would apply a
grouping factor for 2 circuits in one tube - but as 16x32 is likely to
leave the cables apart, each one should suffer less as it will
effectively have its own bit of conduit/plaster surface to lose heat
through and it's the heating/cooling that rates the current carrying
capacity of a cable.






--
Tim Watts

Managers, politicians and environmentalists: Nature's carbon buffer.
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 16
Default Simple mains question..

I don't see any issues. Technically, with round conduit you would apply a
grouping factor for 2 circuits in one tube - but as 16x32 is likely to
leave the cables apart, each one should suffer less as it will
effectively have its own bit of conduit/plaster surface to lose heat
through and it's the heating/cooling that rates the current carrying
capacity of a cable.



good point, the gap required for spaced circuits is something like 1
cable thickness?

so two 2.5 T&E in 32mm ducting taped to top and bottom of the duct
pretty much eliminates any grouping effects for the entire run in any
case?

the way I see it I'm unlikely to have any problems in any case, but if
I use some black nasty tape in a couple of places to ensure the two
cables are well separated I can make sure of it. no doubt that will
help with my "peace of mind"...



  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,360
Default Simple mains question..

JJ
wibbled on Tuesday 26 January 2010 15:30

I don't see any issues. Technically, with round conduit you would apply a
grouping factor for 2 circuits in one tube - but as 16x32 is likely to
leave the cables apart, each one should suffer less as it will
effectively have its own bit of conduit/plaster surface to lose heat
through and it's the heating/cooling that rates the current carrying
capacity of a cable.



good point, the gap required for spaced circuits is something like 1
cable thickness?

so two 2.5 T&E in 32mm ducting taped to top and bottom of the duct
pretty much eliminates any grouping effects for the entire run in any
case?

the way I see it I'm unlikely to have any problems in any case, but if
I use some black nasty tape in a couple of places to ensure the two
cables are well separated I can make sure of it. no doubt that will
help with my "peace of mind"...


I wouldn't worry too much - but you could shove a bit of small oval
(smallest size should fit) down the big oval between the cables if you
wished to guarantee separation.

--
Tim Watts

Managers, politicians and environmentalists: Nature's carbon buffer.

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Simple electric question NB UK diy 5 December 30th 09 07:27 PM
Simple Variac Question Matthew Rossiter Electronics Repair 17 March 17th 07 01:20 AM
v simple q: will a compression joint handle mains pressure? Jim UK diy 24 January 19th 06 08:59 AM
Simple Question from a Simpleton :-) Dale Hallmark Metalworking 8 June 5th 05 09:33 PM
Simple plumbing question! Adam Cohn Home Ownership 3 January 27th 05 07:11 AM


All times are GMT +1. The time now is 05:10 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"