  #1   Report Post  
Posted to uk.d-i-y
jim jim is offline
external usenet poster
 
Posts: 217
Default bathroom electric towel rail connect

Seeking confirmation as to correct or 'normal' connection method for
an electric towel rail (around 500W) on a bathroom wall (which is well
away from the bath).

What I envisage is:

1 Spur from ring mains (RCD protected circuit) socket nearby outside
bathroom.
to
2 Fused switch on wall outside bathroom wall with a neon indicator
to
3 Unswitched spur connection unit with neon indicator near towel rail
(final connection by flying lead)

Intermediate cabling (1 mm^2 or 1.5mm^2) to be buried in chasing under
plaster.

Am doubtful about the cable spec from the ring connection to the first
fused switch. Should it be in 2.5mm^2 cable?

Any comments most appreciated.

TIA
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 43,017
Default bathroom electric towel rail connect

In article
, jim
wrote:
Seeking confirmation as to correct or 'normal' connection method for
an electric towel rail (around 500W) on a bathroom wall (which is well
away from the bath).


What I envisage is:


1 Spur from ring mains (RCD protected circuit) socket nearby outside
bathroom. to 2 Fused switch on wall outside bathroom wall with a neon
indicator to 3 Unswitched spur connection unit with neon indicator near
towel rail (final connection by flying lead)


Switched FCU outside the bathroom would be my choice with a cable outlet
beside the fitting to change from the TW&E to flex. If the FCU is to be
beside a lighting switch, you could make up one unit using grid switch
components, although this will cost much more. And even situate the fuse
elsewhere.

Intermediate cabling (1 mm^2 or 1.5mm^2) to be buried in chasing under
plaster.


Am doubtful about the cable spec from the ring connection to the first
fused switch. Should it be in 2.5mm^2 cable?


In general, yes. Although you could make a case that 1.5mm would be ok for
a short run.

--
*Never underestimate the power of stupid people in large groups

Dave Plowman London SW
To e-mail, change noise into sound.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Bathroom radiator/ towel rail GB UK diy 8 October 18th 08 05:36 PM
electric towel rail installation [email protected] UK diy 7 July 17th 06 12:25 PM
extending towel rail for bathroom Kevin UK diy 3 September 27th 05 05:20 PM
Electric or CH Towel Rail? [email protected] UK diy 3 July 3rd 05 11:39 AM
Electric-only towel rail Dave Plowman UK diy 1 July 29th 03 06:59 PM


All times are GMT +1. The time now is 08:16 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"