jim August 26th 09 01:15 PM

bathroom electric towel rail connect
 
Seeking confirmation as to correct or 'normal' connection method for
an electric towel rail (around 500W) on a bathroom wall (which is well
away from the bath).

What I envisage is:

1 Spur from ring mains (RCD protected circuit) socket nearby outside
bathroom.
to
2 Fused switch on wall outside bathroom wall with a neon indicator
to
3 Unswitched spur connection unit with neon indicator near towel rail
(final connection by flying lead)

Intermediate cabling (1 mm^2 or 1.5mm^2) to be buried in chasing under
plaster.

Am doubtful about the cable spec from the ring connection to the first
fused switch. Should it be in 2.5mm^2 cable?

Any comments most appreciated.

TIA

Dave Plowman (News) August 26th 09 01:40 PM

bathroom electric towel rail connect
 
In article
, jim
wrote:
Seeking confirmation as to correct or 'normal' connection method for
an electric towel rail (around 500W) on a bathroom wall (which is well
away from the bath).


What I envisage is:


1 Spur from ring mains (RCD protected circuit) socket nearby outside
bathroom. to 2 Fused switch on wall outside bathroom wall with a neon
indicator to 3 Unswitched spur connection unit with neon indicator near
towel rail (final connection by flying lead)


Switched FCU outside the bathroom would be my choice with a cable outlet
beside the fitting to change from the TW&E to flex. If the FCU is to be
beside a lighting switch, you could make up one unit using grid switch
components, although this will cost much more. And even situate the fuse
elsewhere.

Intermediate cabling (1 mm^2 or 1.5mm^2) to be buried in chasing under
plaster.


Am doubtful about the cable spec from the ring connection to the first
fused switch. Should it be in 2.5mm^2 cable?


In general, yes. Although you could make a case that 1.5mm would be ok for
a short run.

--
*Never underestimate the power of stupid people in large groups

Dave Plowman London SW
To e-mail, change noise into sound.