Default Honeywell CM927 - Multiple units and binding to a single boiler relay

Hi all,

Judging by GoogleGroups, there's a bit of installer expertise here

Looking at Honeywell's CM927 4-zone wireless programmer/stat for the new
house.

I'd like to employ 3 units giving me a zone per room with a bit of spare. So
the question that none of Honeywells downloadable manuals seem to answer
is:

Can an HC60NG boiler relay receiver unit be bound or associated with 3
CM927s? Or am I going to need 3 HC60NG "ORed" together?

In which case it's jacking the price up.



The manual does answer the inverse question, in that it says that multiple
HC60NG relays can be bound to a zone which itself is useful as in 3 cases I
need to power either a valve or a pump for a fan convector and upto two
sets of UFH (not enough to justify a fancy manifold system really). The
rest of the zones will be HR80 wireless rad valves.

It looks like a nice system.

Cheers + TIA

Tim

  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 886
Default Honeywell CM927 - Multiple units and binding to a single boilerrelay

On Sun, 28 Sep 2008 20:53:09 +0100, Tim S wrote:

Hi all,

Judging by GoogleGroups, there's a bit of installer expertise here

Looking at Honeywell's CM927 4-zone wireless programmer/stat for the new
house.


4-zone wireless progstat? Unless they've changed something recently the
927 is a single zone progstat which can be used to build multiple zone
controls.

I'd like to employ 3 units giving me a zone per room with a bit of spare. So
the question that none of Honeywells downloadable manuals seem to answer
is:

Can an HC60NG boiler relay receiver unit be bound or associated with 3
CM927s? Or am I going to need 3 HC60NG "ORed" together?


Unless they've radiaclly changed things under the hood you're going to
need 3 OR-ed together.

In which case it's jacking the price up.


Indeed :-|


The manual does answer the inverse question, in that it says that multiple
HC60NG relays can be bound to a zone which itself is useful as in 3 cases I
need to power either a valve or a pump for a fan convector and upto two
sets of UFH (not enough to justify a fancy manifold system really). The
rest of the zones will be HR80 wireless rad valves.


Sounds like an expensive alternative to driving a relay from a single
HC60NG :-/

It looks like a nice system.


It's not bad, but having messed around with them for a while I think it's
crying out for an ability to link it (Wi-Fi/bluetooth?) to something with a
bit more IQ.


--
YAPH http://yaph.co.uk

militant pacifist
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,538
Default Honeywell CM927 - Multiple units and binding to a single boiler relay

YAPH coughed up some electrons that declared:

On Sun, 28 Sep 2008 20:53:09 +0100, Tim S wrote:

Hi all,

Judging by GoogleGroups, there's a bit of installer expertise here

Looking at Honeywell's CM927 4-zone wireless programmer/stat for the new
house.


4-zone wireless progstat? Unless they've changed something recently the
927 is a single zone progstat which can be used to build multiple zone
controls.


Oh ********. I know how I came to the incorrect conclusion:

The spec sheet says: "CM927 can be used to control a zoning system with up
to 4 zones"

However, the CM67z can do 2 zones, provided Zone 2 is handled by HR80's
which have their own sensor. I saw "4", assumed the CM927 was a fancy
replacement for the CM67 and interpolated

So it seems a little less than useful for me.

4 CM67's would seem to do the job ( 8 zones is really enough ) and the
manual does mention binding upto 4[1] to a single HC60NG (plus an extra
HC60NG on Zone 1 of each if desired to operate valves/pumps for that zone
only).

Based on the application examples he

http://www.cm-zone.com/application.php?language=en

[1] That snippet was gleaned from the CM67RFMV datasheet - what's the
difference between that and the CM67z - I'm really having trouble with
Honeywell's website and quasi-random part numbers(!)


But thanks - that saved a painful wallet bruising with an expensive mistake!


I'd like to employ 3 units giving me a zone per room with a bit of spare.
So the question that none of Honeywells downloadable manuals seem to
answer is:

Can an HC60NG boiler relay receiver unit be bound or associated with 3
CM927s? Or am I going to need 3 HC60NG "ORed" together?


Unless they've radiaclly changed things under the hood you're going to
need 3 OR-ed together.

In which case it's jacking the price up.


Indeed :-|


The manual does answer the inverse question, in that it says that
multiple HC60NG relays can be bound to a zone which itself is useful as
in 3 cases I need to power either a valve or a pump for a fan convector
and upto two sets of UFH (not enough to justify a fancy manifold system
really). The rest of the zones will be HR80 wireless rad valves.


Sounds like an expensive alternative to driving a relay from a single
HC60NG :-/


Slight misunderstanding - I need one HC60 to respond to Zone 1 only and the
other to respond to either zone.

It looks like a nice system.


It's not bad, but having messed around with them for a while I think it's
crying out for an ability to link it (Wi-Fi/bluetooth?) to something with
a bit more IQ.


I think the end peripherals at nice - eg the HR80's, HCU23 and HC60NG. What
I love is a "dumb" transmitter with an RS232 link that I could interface
the lot from a little embedded system.

I work with people who hack digital RF comms in the 868MHz band all day for
a living, but alas we're all too busy right now to try to reverse engineer
the RF protocols.

Cheers

Tim
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
CM927 Honeywell stockist required. James Salisbury[_2_] UK diy 2 April 21st 08 04:34 PM
Honeywell CM927 pdf John Stumbles UK diy 16 November 9th 07 11:59 PM
Fused Connection Units with Multiple Fuses [email protected] UK diy 8 March 22nd 06 02:57 PM
placement of multiple air filtration units AND modine heater elburts Woodworking 0 August 29th 05 03:05 AM
Honeywell Fan control units Peter Home Repair 3 December 31st 04 07:03 AM


All times are GMT +1. The time now is 07:48 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"