Default Replacing pressure vessel on old CH system (conventional boiler)

I have a conventional CH boiler (it's an old Thorn Apollo 50/65B, not a
modern combi/condenser type), and piping the system is standard apart from a
pressure vessel in the loft and a mains refilling/pressurising stop-cock
instead of the usual F/E tank. There's a pressure gauge one floor down next
to the immersion tank and CH pump. The wall-mounted boiler is another floor
down again.

The system no longer maintains pressure and I can see from tell-tale stains
that the globe-type pressure vessel is leaking around its circumferential
seal. As it's high above the top of the system, can I just replace this
vessel with a similar unit and then repressurise with the mains inlet? Or
will I have to drain the system right down and refill? There is no pressure
left in the system - due to the leak it is at normal atmospheric.

While old, the system is otherwise very reliable. The pressure vessel was
included originally as we thought we might convert the loft and add a
radiator, but that never happened so a pressurised system wasn't really
necessary after all.

-neil f.


  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,488
Default Replacing pressure vessel on old CH system (conventional boiler)

In an earlier contribution to this discussion,
neil f wrote:

I have a conventional CH boiler (it's an old Thorn Apollo 50/65B, not
a modern combi/condenser type), and piping the system is standard
apart from a pressure vessel in the loft and a mains
refilling/pressurising stop-cock instead of the usual F/E tank.
There's a pressure gauge one floor down next to the immersion tank
and CH pump. The wall-mounted boiler is another floor down again.

The system no longer maintains pressure and I can see from tell-tale
stains that the globe-type pressure vessel is leaking around its
circumferential seal. As it's high above the top of the system, can I
just replace this vessel with a similar unit and then repressurise
with the mains inlet? Or will I have to drain the system right down
and refill? There is no pressure left in the system - due to the leak
it is at normal atmospheric.
While old, the system is otherwise very reliable. The pressure vessel
was included originally as we thought we might convert the loft and
add a radiator, but that never happened so a pressurised system
wasn't really necessary after all.

-neil f.


There's no need to drain the system - just remove it and replace it with a
new one of the same or greater capacity.

Are you sure that there are no other leaks, and that the pressure relief
valve isn't faulty - or, indeed, that the pressure vessel doesn't simply
need re-charging with air? There are a few things which I would try before
lashing out on a new one - such as checking the charge pressure with a car
tyre pressure gauge with the water system unpressurised. This needs to be
about 0.7 bar (~10psi). If it isn't, charge it up with a foot pump, then
re-pressurise the water system and see whether it *still* loses pressure.

[OK, you *know* you've got a (slight?) leak from the vessel - but this may
or may not be the root cause of your loss of pressure, so it would be best
to do a bit more diagnosis].
--
Cheers,
Roger
______
Email address maintained for newsgroup use only, and not regularly
monitored.. Messages sent to it may not be read for several weeks.
PLEASE REPLY TO NEWSGROUP!


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Replacing conventional boiler with combi condensed boiler [email protected] UK diy 8 July 20th 06 09:29 AM
replacing conventional boiler with a condensing boiler [email protected] UK diy 11 July 18th 06 06:39 PM
replacing back boiler system Nis UK diy 5 February 5th 06 10:48 AM
Replacing conventional gas boiler v.installing combi Late Learner UK diy 17 January 14th 06 08:28 AM
Replacing Conventional with Combi Boiler - How DIY is this ? Kevin UK diy 7 October 24th 03 11:07 PM


All times are GMT +1. The time now is 10:24 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"