Default Combi periodically cuts out on DHW

I've got an Ariston Microgenus 27 combi boiler. Recently it's developed
the annoying habit of happily producing domestic hot water for a couple
of minutes, but then shutting down for perhaps five seconds before
starting up again. This means that you get periodic slugs of cold
water, which is especially distressing when showering.

The boiler's thermostat for hot water is on max and just by feeling the
temerature of the flow pipe for DHW coming out of the boiler it does
not seem that it's cutting out on the thermostat, so what else could it
be? It's due its service soon, but I'd like to have some clue as to
what could be going wrong before letting the engineer loose on it.

  #2   Report Post  
Posted to uk.d-i-y
gasman pete
 
Posts: n/a
Default Combi periodically cuts out on DHW


Martin Pentreath wrote:
I've got an Ariston Microgenus 27 combi boiler. Recently it's developed
the annoying habit of happily producing domestic hot water for a couple
of minutes, but then shutting down for perhaps five seconds before
starting up again. This means that you get periodic slugs of cold
water, which is especially distressing when showering.

The boiler's thermostat for hot water is on max and just by feeling the
temerature of the flow pipe for DHW coming out of the boiler it does
not seem that it's cutting out on the thermostat, so what else could it
be? It's due its service soon, but I'd like to have some clue as to
what could be going wrong before letting the engineer loose on it.


what you need to do is see if the boiler flow is turning off the boiler
and what temp it is doing it at.
also is the dhw heat exchanger working ok.... it may be blocked or
scaled up.
check this by running the water and monitor the temp.of the boiler flow
and return at the heat exchanger.
if it is really hot on the inlet and cool on the outlet and the boiler
is tripping out you have a flow problem within the heat exchanger.
try this and let me know
pete

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Combi Boiler - water heating then cuts out P Lavers UK diy 7 December 2nd 14 07:44 PM
Baxi bahama 100 cuts out after 5 to 20 seconds [email protected] UK diy 1 November 20th 05 12:27 AM
combi boiler - efficiency and cost ARWadsworth UK diy 23 January 4th 05 02:12 PM
new combi experience report Fred UK diy 12 December 5th 04 09:11 PM
How to correctly size combi boilers Dean UK diy 16 December 25th 03 10:49 PM


All times are GMT +1. The time now is 10:01 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"