Wiring load question
Just looking at my house ring main and a bit bothered with my kitchen
sockets. The socket ring is one loop from a 30 amp fuse using 2.5 T&E. In the corner of the kitchen the ring goes down from the ceiling into an above worktop double socket and then down under the worktop into another double socket. I always assumed the ring would go into the top socket with one wire unbroken and on to the bottom one and the other wire into and out of the socket. ie both sockets on the full ring. I have just found the ring stops at the above worktop socket and the bottom one is a spur. Fine, except the bottom one has a washing machine and a dishwasher plugged in. If both machines are on and the heaters go on, it seems to me that the load on the spur wire is near maximum. To do what I thought would be the accepted thing would have involved only an extra meter of cable and avoided three sets of wires in the top socket terminals. Any comments please? |