Questions for electrical experts about whirlpool bath
I pulled the wall switch for the whirlpool bath off of my bathroom
wall to replace it because it got cracked accidently. While replacing it I noticed that the black and white wires were wired as normal with the load going through the switch. But I noticed the bare ground wires were not connected which I thought was weird so I connected them together. When I turned the breaker on it immediately reset so then I unconnected the grounds it worked fine again. The circuit breaker in the basement is a 20 amp dedicated GFCI breaker. Is there something about the whirlpool being connected to the GFCI in the panel that needs the grounds not to be wired together in the wall switch. Thanks for any help! Sheila |
#3
Posted to alt.home.repair
|
|||
|
|||
Questions for electrical experts about whirlpool bath
If you can't determine what's causing the problem, the GFI breaker
will still work without the grounds connected as they only look at the current in the hot and neutral. But it should still be determined whats tripping the breaker. |
#4
Posted to alt.home.repair
|
|||
|
|||
Questions for electrical experts about whirlpool bath
On Aug 16, 6:51*pm, wrote:
I pulled the wall switch for the whirlpool bath off of my bathroom wall to replace it because it got cracked accidently. While replacing it I noticed that the black and white wires were wired as normal with the load going through the switch. But I noticed the bare ground wires were not connected which I thought was weird so I connected them together. When I turned the breaker on it immediately reset so then I unconnected the grounds it worked fine again. The circuit breaker in the basement is a 20 amp dedicated GFCI breaker. Is there something about the whirlpool being connected to the GFCI in the panel that needs the grounds not to be wired together in the wall switch. Thanks for any help! Sheila this COULD be quite dangerous, do not use the whirlpool until you figure out what is going on.. Mark |
#5
Posted to alt.home.repair
|
|||
|
|||
Questions for electrical experts about whirlpool bath
wrote in message ... I pulled the wall switch for the whirlpool bath off of my bathroom wall to replace it because it got cracked accidently. While replacing it I noticed that the black and white wires were wired as normal with the load going through the switch. But I noticed the bare ground wires were not connected which I thought was weird so I connected them together. When I turned the breaker on it immediately reset so then I unconnected the grounds it worked fine again. The circuit breaker in the basement is a 20 amp dedicated GFCI breaker. Is there something about the whirlpool being connected to the GFCI in the panel that needs the grounds not to be wired together in the wall switch. Thanks for any help! Sheila The grounds need to be connected. There is a problem somewhere that is causing the GFI circuit breaker to trip. Try disconnecting the spa motor and then see if the breaker trips with the grounds connected in the switch box. I usually install a GFI switch in the bathroom out of sight instead of a GFI breaker in the circuit breaker panel. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
More about strengthening a floor for a whirlpool bath | Home Repair | |||
Whirlpool bath surround | Home Repair | |||
Wiring for A Whirlpool Bath | UK diy | |||
switched spur for whirlpool bath. | UK diy | |||
Wiring in a whirlpool bath | UK diy |