Posted to alt.home.repair
|
|||
|
|||
![]()
My home is heated with a gas fired hot water boiler. The system is
presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? |
#2
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Feb 29, 5:54*am, topswage wrote:
My home is heated with a gas fired hot water boiler. *The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. *I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? I dought 120 is going to the thermostat, its likely 12v or so, to a relay. Do you have a Honeywell round thermostat. |
#3
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Feb 29, 8:37�am, ransley wrote:
On Feb 29, 5:54�am, topswage wrote: My home is heated with a gas fired hot water boiler. �The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. �I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? I dought 120 is going to the thermostat, its likely 12v or so, to a relay. Do you have a Honeywell round thermostat. there are 120 volt and even 240 volt thermostats in use today. ww grainger sells them call a local HVAC company they should have the set back type, not usually sold in stores because of the hazards installing. line voltage heavy current etc |
#4
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Feb 29, 5:54*am, topswage wrote:
My home is heated with a gas fired hot water boiler. *The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. *I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? Honeywell makes ( or made) a kit with a relay, etc. for converting line voltage systems to work with 24 V thermostats. Installed a couple of these in a shop some years ago, so I hope they are still available. That would solve your problem very neatly. HTH Joe |
#5
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
topswage wrote:
My home is heated with a gas fired hot water boiler. The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? What did Honeywell recommend when you E ailed their support function? Oh, you didn't bother to do that? What was the result of your Google search? Oh, you didn't bother to do that? Why do you think several thousand amateurs on here in an anonymous Usenet newsgroup have an answer to your esoteric problem? Please make an effort to do your own basic research. |
#6
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() "topswage" wrote in message . .. My home is heated with a gas fired hot water boiler. The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? I don't see any reason why a digital electronic electric heat thermostat wouldn't work. You have to be certain to get one for single pole, and one that doesn't require a neutral. They're available, I've installed them. There is another way you can go, which is how typical systems like yours are wired. You need a switching relay like Honeywell R845, they cost about $50. The 120 volts that's currently feeding the circulator and being broken by the line voltage stat, would power the relay. The cable going to the circulator gets connected to the switched load of the relay, and you can either run thermostat wire from the TT terminals of the relay to any series 80 (standard 24volt thermostat) that you like, or even use the existing line voltage cable for your thermostat wire |
#7
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Feb 29, 5:54 am, topswage wrote:
My home is heated with a gas fired hot water boiler. The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? Any of you guys want to tell me why this wouldn't work, as a simple solution? http://cgi.ebay.com/Programmable-Lin...QQcmdZViewItem JK |
#8
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Feb 29, 1:13*pm, jJim McLaughlin
wrote: topswage wrote: My home is heated with a gas fired hot water boiler. *The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. *I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? * * What did Honeywell recommend when you E ailed their support function? * * * Oh, you didn't bother to do that? * * *What was the result of your Google search? * * * * Oh, you didn't bother to do that? * * *Why do you think several thousand amateurs on here in an anonymous Usenet newsgroup have an answer to your *esoteric problem? * * * * Please make an effort to do your own basic research. It is not an esoteric problem. The exact same problem applies to everyone who has electric heat. |
#9
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() "Big_Jake" wrote in message ... On Feb 29, 5:54 am, topswage wrote: My home is heated with a gas fired hot water boiler. The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? Any of you guys want to tell me why this wouldn't work, as a simple solution? http://cgi.ebay.com/Programmable-Lin...QQcmdZViewItem JK That particular model won't work because it requires a 240 volt power supply to operate. They have other models that require a 120 volt power supply to work as well, and they too won't work in his application. He has two wires , a 120 volt hot leg, and a return, no neutral. Honeywell/Aube does make 120 volt two wire models that possibly will work for his application. |
#10
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
Joe wrote:
On Feb 29, 5:54 am, topswage wrote: My home is heated with a gas fired hot water boiler. The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? Honeywell makes ( or made) a kit with a relay, etc. for converting line voltage systems to work with 24 V thermostats. Installed a couple of these in a shop some years ago, so I hope they are still available. That would solve your problem very neatly. HTH Joe yup, I'd think a doorbell transformer and a relay with a low voltage coil would solve your problem nate -- replace "roosters" with "cox" to reply. http://members.cox.net/njnagel |
#11
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() "Nate Nagel" wrote in message ... Joe wrote: On Feb 29, 5:54 am, topswage wrote: My home is heated with a gas fired hot water boiler. The system is presently controlled with a 1950's style bimetal thermostat. I'd love to replace the thermostat with an electronic set-back unit, but have discovered that the thermostat is directly controlling the hot water circulating pump--there's 120volt current running through the thermostat, enough to fry most electronic ones. I see though that there are electronic thermostats designed to control electric baseboard heaters, and will control 120 volt circuits--can I use such a thermostat to control my circulating pump? Honeywell makes ( or made) a kit with a relay, etc. for converting line voltage systems to work with 24 V thermostats. Installed a couple of these in a shop some years ago, so I hope they are still available. That would solve your problem very neatly. HTH Joe yup, I'd think a doorbell transformer and a relay with a low voltage coil would solve your problem nate -- replace "roosters" with "cox" to reply. http://members.cox.net/njnagel And it's all contained in a box called Honeywell R845 switching relay. They're also made by Taco, Argo, White Rogers, and a host of others |