Default Replacing main ground rods

Were removing a planter alongside my buddes home to widen his driveway.

His ground rods are in the planter. I think we should replace them to a
offset in the driveway. The home narrows a bit partway back.

Ny friend wants to either drive them deeper or pull them out and move
them.

he is cheap

Where does one buy that groundrod driver that fits in a hammer drill??
many electrical supply houses have closed around here and the home
depot person had no idea what I was talking about.

The existing ground is a single ground rod whats the current code?

  #2   Report Post  
Posted to alt.home.repair
RBM RBM is offline
external usenet poster
 
Posts: 1,690
Default Replacing main ground rods

2-eight foot rods, six feet apart or prove the ground resistance. Why not
drive the one in deep?
wrote in message
oups.com...
Were removing a planter alongside my buddes home to widen his driveway.

His ground rods are in the planter. I think we should replace them to a
offset in the driveway. The home narrows a bit partway back.

Ny friend wants to either drive them deeper or pull them out and move
them.

he is cheap

Where does one buy that groundrod driver that fits in a hammer drill??
many electrical supply houses have closed around here and the home
depot person had no idea what I was talking about.

The existing ground is a single ground rod whats the current code?



  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,199
Default Replacing main ground rods


RBM (remove this) wrote:
2-eight foot rods, six feet apart or prove the ground resistance. Why not
drive the one in deep?


groundrods would be driven over by vehicles and ground wire too short
anyway. wire woulld likely get short as rod is driven deeper.

my friend wants to pull the rod, its rustry and has anyone ever pulled
one out?

  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,746
Default Replacing main ground rods

" wrote:

RBM (remove this) wrote:
2-eight foot rods, six feet apart or prove the ground resistance. Why not
drive the one in deep?


groundrods would be driven over by vehicles and ground wire too short
anyway. wire woulld likely get short as rod is driven deeper.

my friend wants to pull the rod, its rustry and has anyone ever pulled
one out?


Don't try to pull it, just trash it. It's deteriorated and won't survive
re-driving somewhere else.

Buy two new ground rods to locate 6' (or more) apart as noted in another
post. Also purchase enough wire of the appropriate gauge to wire the new
rods contiguously back to the main panel. Splices are not allowed in the
ground rod connection.

For driving the rods, look to Home Depot's tool rental for a goof Hilti
rotary hammer. Since the bozos at HD won't know what a ground rod driver
is, call the local Hilti branch and they will in all probability loan
you one to go with the drill.

Pete C.
  #5   Report Post  
Posted to alt.home.repair
Bob Bob is offline
external usenet poster
 
Posts: 177
Default Replacing main ground rods


"RBM" rbm2(remove wrote in message
...
2-eight foot rods, six feet apart or prove the ground resistance. Why not
drive the one in deep?
__________________________________________________ _________
Two is, or should be, an absolute NO NO.
You can get ground current between the two.
__________________________________________________ _________



wrote in message
oups.com...
Were removing a planter alongside my buddes home to widen his driveway.

His ground rods are in the planter. I think we should replace them to a
offset in the driveway. The home narrows a bit partway back.

Ny friend wants to either drive them deeper or pull them out and move
them.

he is cheap

Where does one buy that groundrod driver that fits in a hammer drill??
many electrical supply houses have closed around here and the home
depot person had no idea what I was talking about.

The existing ground is a single ground rod whats the current code?






  #6   Report Post  
Posted to alt.home.repair
DAC DAC is offline
external usenet poster
 
Posts: 112
Default Replacing main ground rods

You don't need a driver...dig a small depression where you want to
place the rod.

Stick the rod in the soil, fill the depression with water. With-draw
the rod and the water will run into the the hole. As the water
provides lubrication, a gentle up and down motion will let you easily
slip the rod into the soil.

Depending on the moisture content of the soil, you may need to replace
the water in the depression. I always finish the last 2 feet or so
with a sledge hammer, many light strokes rather than a few large ones
will keep the end from mashing out of shape.

Good luck,

DAC

On Nov 27, 6:46 pm, " wrote:
Where does one buy that groundrod driver that fits in a hammer drill??


  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,746
Default Replacing main ground rods

Bob wrote:

"RBM" rbm2(remove wrote in message
...
2-eight foot rods, six feet apart or prove the ground resistance. Why not
drive the one in deep?
__________________________________________________ _________
Two is, or should be, an absolute NO NO.
You can get ground current between the two.
__________________________________________________ _________


Suggest reading the codes.

Pete C.
  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,199
Default Replacing main ground rods


Bob wrote:
"RBM" rbm2(remove wrote in message
...
2-eight foot rods, six feet apart or prove the ground resistance. Why not
drive the one in deep?
__________________________________________________ _________
Two is, or should be, an absolute NO NO.
You can get ground current between the two.
__________________________________________________ _________



ground rods MUST be unified together, all connected together with water
line and any other grounds like a satellite dish or a shock hazard can
occur.

unified its no problem

  #9   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 557
Default Replacing main ground rods

On 27 Nov 2006 16:46:18 -0800, "
wrote:

Were removing a planter alongside my buddes home to widen his driveway.

His ground rods are in the planter. I think we should replace them to a
offset in the driveway. The home narrows a bit partway back.

Ny friend wants to either drive them deeper or pull them out and move
them.


Ha Ha Ha, I actually cracked up, "pull them out and move them".


he is cheap

Where does one buy that groundrod driver that fits in a hammer drill??
many electrical supply houses have closed around here and the home
depot person had no idea what I was talking about.

The existing ground is a single ground rod whats the current code?


Get an electrician, they will check your whole grounding and bonding
system, and put ground rods in fast.

BTW, the NEC is Good, but many local codes are more restrictive, so
check with your local codes.

later,

tom @ www.MedJobSite.com



  #10   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 8,803
Default Replacing main ground rods


wrote in message
oups.com...
Were removing a planter alongside my buddes home to widen his driveway.

His ground rods are in the planter. I think we should replace them to a
offset in the driveway. The home narrows a bit partway back.

Ny friend wants to either drive them deeper or pull them out and move
them.

he is cheap


Pouring concrete? I have read that tieing the ground to properly
bonded rebar in concrete can make a very good ground.

Bob




  #11   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,185
Default Replacing main ground rods

Bob F wrote:

Pouring concrete? I have read that tieing the ground to properly
bonded rebar in concrete can make a very good ground.


Around here you can use wire embedded in concrete, but it has to be bare
copper wire embedded in the bottom two inches of the building footings.
(Uses the weight of the building pushing on it to help get better
ground contact.)

Chris
  #12   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,199
Default Replacing main ground rods


Chris Friesen wrote:
Bob F wrote:

Pouring concrete? I have read that tieing the ground to properly
bonded rebar in concrete can make a very good ground.


Around here you can use wire embedded in concrete, but it has to be bare
copper wire embedded in the bottom two inches of the building footings.
(Uses the weight of the building pushing on it to help get better
ground contact.)

Chris


he will go with gravel........ he tends to buy expensive toys like a
new harley every couple years but cheaps out on his home and it shows.

he REALLY needed a backhoe 3 years ago when he bought the home.

the driveway is sloped wrong, water coming off road above home washed
out back wall of garage.

a backhoe for a day, and some BIG dump truck loads of gravel can fix
the place.......''

his priorties are elsewhere and he is a nice guy and has helped me with
stuff, so I help him

personally I believe you should take good care of your home it saves
money.

example he has tree branches rubbing his roof, and with wind that will
ruin it.

yet he ignores it?

I dont understand folks like that, pole pruner can lob off those
branches.

I offered to help he isnt interested.

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Ground current through water main/meter Proctologically Violated©® Home Repair 17 October 31st 06 08:54 PM
Breaker box main ground help Todd H. Home Repair 7 September 30th 06 06:30 PM
EXPERTS PLEASE HELP - Ground Rods & Grounding & Multiple Meters Jim Beam Home Repair 4 September 17th 06 03:52 PM
GFI Neutral and distance to the main ground [email protected] Home Repair 7 December 5th 05 09:15 PM
main ground karla Home Repair 6 February 12th 05 04:59 AM


All times are GMT +1. The time now is 11:19 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"