Default AC window unit keeps blowing fuses

Hello all. I'll try to make this brief, but I doubt such a thing is
possible.

I have a Whirlpool 24,000 BTU window unit that cools my whole house.
I've had it for a couple of years, and it's worked brilliantly up until
now. About a month ago, it started blowing fuses; it's an old house,
still have old electrical system, fuse boxes, etc. At the time, the
temp outside was mid-80's, so it's not like it was having to work
overtime to cool things down. Anyway, I replaced the fuse, and about a
week later, same thing happened. The problem escalated over the next
two weeks, finally had to call a repairman.

He checked it out, said he couldn't find anything wrong with it either
mechanically or electrically--the unit has its own 20 amp circuit, and
at peak operating time was only drawing maybe 12 amps. Thought that
the unit was having to come off/on too frequently, that might be the
cause. He suggested I switch to power-saving mode, where the fan stays
off until the compressor kicks in--in PS mode, compressor doesn't
alternate quite as often. If all else fails, he suggested I have them
install a "hard start device."

Unfortunately, PS mode is not an option; when the unit runs, it's loud,
but it's white noise, so I get used to it being on. Having the fan
alternate, especially at night, wouldn't work because the silence wakes
me up (plus I'd stay awake, wondering if the unit was working still or
had blown a fuse). That, and I've found that when the unit is off,
bugs find their way into my house (another issue).

My only solution thus far has been to bump up the thermostat, which has
worked for a couple of lukewarm weeks. But now it appears my cranky AC
doesn't like that, either.

What do I do now? Do I call him back, have him install the hard start
device? Could the problem be electrical, and if so, do I call an
electrician? Or should I just empty my bank account and throw cash at
the unit until it starts behaving again, like every other bleeding
thing in this house?

Any/all advice is appreciated. Thank you for your time.

  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 746
Default AC window unit keeps blowing fuses

nycknayme wrote:

Hello all. I'll try to make this brief, but I doubt such a thing is
possible.

I have a Whirlpool 24,000 BTU window unit that cools my whole house.
I've had it for a couple of years, and it's worked brilliantly up until
now. About a month ago, it started blowing fuses; it's an old house,
still have old electrical system, fuse boxes, etc. At the time, the
temp outside was mid-80's, so it's not like it was having to work
overtime to cool things down. Anyway, I replaced the fuse, and about a
week later, same thing happened. The problem escalated over the next
two weeks, finally had to call a repairman.

He checked it out, said he couldn't find anything wrong with it either
mechanically or electrically--the unit has its own 20 amp circuit, and
at peak operating time was only drawing maybe 12 amps.


SNIP

I assume you are already using some type of "Slow Blow" time Delay fuse.

Often, those old fuse holders OR the wire terminals will generate
enough heat due to resistance that the fuse will blow from
conducted heat rather than excessive Amp draw.

Look for discoloration of the fuse contacts or the lugs for
the wire termination. If this is indeed the problem, it may
take some kind of fuse/breaker replacement to solve.

Jim
  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 168
Default AC window unit keeps blowing fuses

Does the fuse blow when the AC is cycling to on? Or does it blow at random
time?
The fan doesn't draw much current so I don't think PS mode is going to help.

Someone already suggested a slow-blow fuse. If that doesn't help, a hard
start device may help. If I understand correctly, a hard start device is a
capacitor to "buffer" extra power for the compressor when it cycle to on.
When a motor load turns on, they can draw a very large current for a split
second. If the load on the motor is heavier (let's say the bearings grease
dried out), then this split second could become longer and more likely to
blow a fuse.

-p

"nycknayme" wrote in message
ups.com...
Hello all. I'll try to make this brief, but I doubt such a thing is
possible.

I have a Whirlpool 24,000 BTU window unit that cools my whole house.
I've had it for a couple of years, and it's worked brilliantly up until
now. About a month ago, it started blowing fuses; it's an old house,
still have old electrical system, fuse boxes, etc. At the time, the
temp outside was mid-80's, so it's not like it was having to work
overtime to cool things down. Anyway, I replaced the fuse, and about a
week later, same thing happened. The problem escalated over the next
two weeks, finally had to call a repairman.

He checked it out, said he couldn't find anything wrong with it either
mechanically or electrically--the unit has its own 20 amp circuit, and
at peak operating time was only drawing maybe 12 amps. Thought that
the unit was having to come off/on too frequently, that might be the
cause. He suggested I switch to power-saving mode, where the fan stays
off until the compressor kicks in--in PS mode, compressor doesn't
alternate quite as often. If all else fails, he suggested I have them
install a "hard start device."

Unfortunately, PS mode is not an option; when the unit runs, it's loud,
but it's white noise, so I get used to it being on. Having the fan
alternate, especially at night, wouldn't work because the silence wakes
me up (plus I'd stay awake, wondering if the unit was working still or
had blown a fuse). That, and I've found that when the unit is off,
bugs find their way into my house (another issue).

My only solution thus far has been to bump up the thermostat, which has
worked for a couple of lukewarm weeks. But now it appears my cranky AC
doesn't like that, either.

What do I do now? Do I call him back, have him install the hard start
device? Could the problem be electrical, and if so, do I call an
electrician? Or should I just empty my bank account and throw cash at
the unit until it starts behaving again, like every other bleeding
thing in this house?

Any/all advice is appreciated. Thank you for your time.



  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 3
Default AC window unit keeps blowing fuses

Thanks to both of you for your advice--but I think I might have
stumbled upon a solution.

Went to Lowe's to get another box of fuses--have been getting Buss 20
amp, time delay fuses--they didn't have any with a base that matched
mine. Then I noticed there was a cubbyhole that had fuses that looked
identical to the ones I have been using--same color, size, base. Only
these were labeled "heavy duty," and the innards looked slightly
different from the ones I'd been using.

I bought them instead, plugged them in yesterday, and so far, no
problems--I even bumped down the thermostat, and they've been able to
handle the load. I suspect that, last year, I might have bought the
wrong type fuses for that circuit, 20 amp fuses that looked exactly the
same as the old fuses, even said on the box they were meant for things
like AC's, etc. This year, when an old one got blown, I started
replacing them w/the new batch, and that's when the problems began...?
Seems like a valid theory, at least. I'll give it a week. (crosses
fingers)

Thanks again for your help--I might still look into that hard start
device if it starts getting cranky again.

Cheers,
David

  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 168
Default AC window unit keeps blowing fuses

"nycknayme" wrote in message
ups.com...
Thanks to both of you for your advice--but I think I might have
stumbled upon a solution.

Went to Lowe's to get another box of fuses--have been getting Buss 20
amp, time delay fuses--they didn't have any with a base that matched
mine. Then I noticed there was a cubbyhole that had fuses that looked
identical to the ones I have been using--same color, size, base. Only
these were labeled "heavy duty," and the innards looked slightly
different from the ones I'd been using.

I bought them instead, plugged them in yesterday, and so far, no
problems--I even bumped down the thermostat, and they've been able to


I trust you didn't replace a 20A fuse with a 30A fuse?
It would "fix" your problem alright, but you're putting the burden elsewhere
in your wiring.




  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 3
Default AC window unit keeps blowing fuses


I trust you didn't replace a 20A fuse with a 30A fuse?
It would "fix" your problem alright, but you're putting the burden elsewhere
in your wiring.


That's right--30 amp. How'd you know that?

*sniff-sniff* Hmm, wonder what that burning smell is...

Haha, no, Peter, they're also 20 amp fuses. Sorry, forgot to include
that in previous post. ..

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Neighbor's Window AC Unit Drips on Mine Julie P. Home Repair 22 July 3rd 19 08:14 PM
Window AC unit with cracked freon tube quietman Home Repair 6 April 28th 06 04:46 AM
Heat pump inside unit doesn't always start Kevin J. Phillips Home Repair 9 December 15th 05 04:04 PM
Central Air v. Window-unit Air? Nehmo Home Repair 147 August 20th 05 08:33 AM
Does A/C need maintenance? toller Home Repair 50 April 18th 05 01:12 PM


All times are GMT +1. The time now is 09:04 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"