  #1   Report Post  
CL (dnoyeB) Gilbert
 
Posts: n/a
Default Adding Aux HVAC fan

I am adding an auxillery fan to my HVAC. Actually two; One for my
computer room where the computers keep it rather toasty, and one for my
bedroom where the large number of windows keep it rather 'outsidey.'

I want to start with the bedroom one which is already installed in the
duct. I have run the wiring to the furnace area. 3 wires; power and
ground. Wiring nailed into ceiling floor joists, etc.

The question is what to do now? I want to use a relay so the aux fan
comes on when the HVAC blower is on.

So I have a relay that I need to mount somehwere. Its coil will be on
the HVAC control which IIRC is 24vac. Its NO contact will connect from
a switch which will be powered by the main furnace switch next to the
furnace. This is lookin nasty though as it seems I need to install some
connectors on the wires and plug them in, or maybe find a relay with
screw terminals!?

I am assuming this relay needs to be mounted to something and in some
kind of enclosure? I intend to put it in a normal switch box mounted to
a floor joist in the ceiling.

I am assuming the wiring needs to be in metal pipes? Also does the
24vac need a seperate pipe from the 120vac wiring?

Is there a simpler way?

This is a pretty small fan which I believe is 1A load for 120VAC. I'm
an electrical engineer but not an electrician. I don't know the rules
but I'd like to follow them if I can learn them.


--
Respectfully,


CL Gilbert
  #2   Report Post  
Carolina Breeze HVAC
 
Posts: n/a
Default


"CL (dnoyeB) Gilbert" wrote in message
...
I am adding an auxillery fan to my HVAC. Actually two; One for my computer
room where the computers keep it rather toasty, and one for my bedroom
where the large number of windows keep it rather 'outsidey.'

I want to start with the bedroom one which is already installed in the
duct. I have run the wiring to the furnace area. 3 wires; power and
ground. Wiring nailed into ceiling floor joists, etc.

The question is what to do now? I want to use a relay so the aux fan
comes on when the HVAC blower is on.

So I have a relay that I need to mount somehwere. Its coil will be on the
HVAC control which IIRC is 24vac. Its NO contact will connect from a
switch which will be powered by the main furnace switch next to the
furnace. This is lookin nasty though as it seems I need to install some
connectors on the wires and plug them in, or maybe find a relay with screw
terminals!?

I am assuming this relay needs to be mounted to something and in some kind
of enclosure? I intend to put it in a normal switch box mounted to a
floor joist in the ceiling.

I am assuming the wiring needs to be in metal pipes? Also does the 24vac
need a seperate pipe from the 120vac wiring?

Is there a simpler way?

This is a pretty small fan which I believe is 1A load for 120VAC. I'm
an electrical engineer but not an electrician. I don't know the rules but
I'd like to follow them if I can learn them.


--
Respectfully,


CL Gilbert


With all due respect:

Adding aux fans is the LAST thing you do.

If you have a cooling problem due to airflow, the fans may mask it, but they
will not cure it.

You can only get X-CFM down a duct of X-Diameter at the proper static
pressure.
Velocity of the air has to be taken into consideration and if your aux fan
will not handle what you need to equal the proper airflow to deliver enough
BTUh back to the unit, then you have wasted time.
Normally, air flow issues are due to poor duct design, or proper duct design
based upon the original use of the home, or room, and if you have added a
heat load to it, then adding a fan to try to increase the air flow to the
room prob wont help, and even if it does, what have you done to the balance
of the system?



  #3   Report Post  
CL (dnoyeB) Gilbert
 
Posts: n/a
Default

Carolina Breeze HVAC wrote:
"CL (dnoyeB) Gilbert" wrote in message
...

I am adding an auxillery fan to my HVAC. Actually two; One for my computer
room where the computers keep it rather toasty, and one for my bedroom
where the large number of windows keep it rather 'outsidey.'

I want to start with the bedroom one which is already installed in the
duct. I have run the wiring to the furnace area. 3 wires; power and
ground. Wiring nailed into ceiling floor joists, etc.

The question is what to do now? I want to use a relay so the aux fan
comes on when the HVAC blower is on.

So I have a relay that I need to mount somehwere. Its coil will be on the
HVAC control which IIRC is 24vac. Its NO contact will connect from a
switch which will be powered by the main furnace switch next to the
furnace. This is lookin nasty though as it seems I need to install some
connectors on the wires and plug them in, or maybe find a relay with screw
terminals!?

I am assuming this relay needs to be mounted to something and in some kind
of enclosure? I intend to put it in a normal switch box mounted to a
floor joist in the ceiling.

I am assuming the wiring needs to be in metal pipes? Also does the 24vac
need a seperate pipe from the 120vac wiring?

Is there a simpler way?

This is a pretty small fan which I believe is 1A load for 120VAC. I'm
an electrical engineer but not an electrician. I don't know the rules but
I'd like to follow them if I can learn them.


--
Respectfully,


CL Gilbert



With all due respect:

Adding aux fans is the LAST thing you do.

If you have a cooling problem due to airflow, the fans may mask it, but they
will not cure it.

You can only get X-CFM down a duct of X-Diameter at the proper static
pressure.
Velocity of the air has to be taken into consideration and if your aux fan
will not handle what you need to equal the proper airflow to deliver enough
BTUh back to the unit, then you have wasted time.
Normally, air flow issues are due to poor duct design, or proper duct design
based upon the original use of the home, or room, and if you have added a
heat load to it, then adding a fan to try to increase the air flow to the
room prob wont help, and even if it does, what have you done to the balance
of the system?




Well this is all I could think of. As I stated, the bedroom's
temperature is off in my opinion due to higher heat loss than other
rooms due to so many windows. It also has a vaulted ceiling.

The computer room stays HOT, even in the winter due to added heat
sources within the room. The rest of the house is pretty nice,
including even the basement. I can't keep the doors open since my Son
would enter the room and put his signature on it...

So increasing cooling in summer and heating in winder to the bedroom is
my objective. So I added a fan...For the computer room I could drill
holes in the wall, and run a radiator outside and cool my computers with
a water cooling system. But im hoping for something less obtrusive.

The master bedroom is the farthest room from the furnace, being on the
2nd floor and other side of the house. The computer room is on the 2nd
floor, but basically above the furnace.

Perhaps for the computer room I could put the fan on the return?



Ideas?


--
Respectfully,


CL Gilbert
  #4   Report Post  
 
Posts: n/a
Default

Have you considered putting a window unit in the computer room?

  #5   Report Post  
Steve Stone
 
Posts: n/a
Default

I don't know how hot your computer room gets.
In my home office there is a 2k VA Tripplite UPS, 4 tower PC's, 2 of
which run 24x7 along with ham radio gear that runs all the time and big
old 20 amp dc power supplies to run the ham gear. Add to that 3 CRT
style displays a laptop computer, battery chargers, printer, 2 routers,
a switch, a couple of police scanners, and a small Merlin PBX. Room size
is 9 x 15.
A/C in room next to it but no A/C duct in this room. A ceiling fan in
the computer / office seems to keep the air mixed up enough to be
comfortable even when it is 98 degrees outside.



  #6   Report Post  
CL (dnoyeB) Gilbert
 
Posts: n/a
Default

Steve Stone wrote:
I don't know how hot your computer room gets.
In my home office there is a 2k VA Tripplite UPS, 4 tower PC's, 2 of
which run 24x7 along with ham radio gear that runs all the time and big
old 20 amp dc power supplies to run the ham gear. Add to that 3 CRT
style displays a laptop computer, battery chargers, printer, 2 routers,
a switch, a couple of police scanners, and a small Merlin PBX. Room size
is 9 x 15.
A/C in room next to it but no A/C duct in this room. A ceiling fan in
the computer / office seems to keep the air mixed up enough to be
comfortable even when it is 98 degrees outside.


Thats amazing. Im running an AMD XP3200+ and an Ati 9700Pro graphics
card. This computer is a heat box. Its the real heat generator and the
room is hot but bearable before I turn it on. Laser printer is there
too but the heat is not too much.

Im seriously considering the 'Reserator' silent water cooling system to
get the heat out from under the desk.

I should also mention this room is 1/2 over the garage, and the garage
gets HOT as well.

--
Respectfully,


CL Gilbert
  #7   Report Post  
G Henslee
 
Posts: n/a
Default

CL (dnoyeB) Gilbert wrote:



Thats amazing. Im running an AMD XP3200+ and an Ati 9700Pro graphics
card. This computer is a heat box. Its the real heat generator and the
room is hot but bearable before I turn it on. Laser printer is there
too but the heat is not too much.



Might want to see what kind of temps you're running.
http://www.almico.com/sfdownload.php
  #8   Report Post  
Ken
 
Posts: n/a
Default


CL (dnoyeB) Gilbert wrote:
I am adding an auxillery fan to my HVAC. Actually two; One for my
computer room where the computers keep it rather toasty, and one for my
bedroom where the large number of windows keep it rather 'outsidey.'

I want to start with the bedroom one which is already installed in the
duct. I have run the wiring to the furnace area. 3 wires; power and
ground. Wiring nailed into ceiling floor joists, etc.

The question is what to do now? I want to use a relay so the aux fan
comes on when the HVAC blower is on.

So I have a relay that I need to mount somehwere. Its coil will be on
the HVAC control which IIRC is 24vac. Its NO contact will connect from
a switch which will be powered by the main furnace switch next to the
furnace. This is lookin nasty though as it seems I need to install some
connectors on the wires and plug them in, or maybe find a relay with
screw terminals!?

I am assuming this relay needs to be mounted to something and in some
kind of enclosure? I intend to put it in a normal switch box mounted to
a floor joist in the ceiling.

I am assuming the wiring needs to be in metal pipes? Also does the
24vac need a seperate pipe from the 120vac wiring?

Is there a simpler way?

This is a pretty small fan which I believe is 1A load for 120VAC. I'm
an electrical engineer but not an electrician. I don't know the rules
but I'd like to follow them if I can learn them.


--
Respectfully,


CL Gilbert


As others have said, I would look first to rebalance the HVAC system,
etc. before using a booster fan.

If the final conclusion is to use a booster fan, one alternative to
adding a relay is to put an airflow sensor in the duct. That way, once
the heat or A/C comes on and starts blowing air through the ducts, the
sensors picks that up and will close a NO switch. All you have to do is
run 120 VAC to the sensor, and then he switched 120 VAC to the booster
fan. No electrical connections to the HVAC system are required.

My furnace has a relay on the circuit board for activating auxillary
equipment, such as a humidifier that I have for during the heating
season. Check the manual to see if you have this and if it will
support the load your fan will put on it.

If you have to add a relay, then see if you can add an electrical box
right on your HVAC system. I was able to do this on my system (just to
make some connections, no relay was required...) by just putting a
regular junction box and attaching with standard electrical fittings to
the electrical box that was part of the furnace. It already had
knockouts for just such a connection. I know nothing about this, but
if I was in your shoes I would call an HVAC place and I'm sure they
have some sort of relays for just these sort of purposes that they
would be willing to sell you.

Ken

  #9   Report Post  
Stretch
 
Posts: n/a
Default

Get an Aprilaire current relay #50 or #51. It clamps around the common
blower wire and senses the blower motor current. One switches 120
volts, the other switches 24 bolts, I don't remember which is which.
Each relay will carry 1 amp.

That being said, the best solution would be to run a load calculation
to determine how much air each room needs and resize your ducts to get
the right amount of air in every room. Note that is not a job for an
amateur. It would be the best solution to your problem.

Most "booster fans" are propeller fans. They do not produce the high
static pressures needed for duct systems and are not very effective.
You may not want to run it that way for the computer room in the winter
since it is too hot there anyway. In the summer run the computer room
fan 24/7. Just plug it in to a wall outlet.

The bedroom fan unit can be on a relay. The relay can be mounted
inside the furnace control cabinet for safety.

Good luck.

Stretch

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
HVAC Refrigerant indicator Barr Home Repair 1 April 27th 05 10:33 AM
HVAC WTF SteveB Home Repair 68 February 6th 05 06:10 PM
Checking Air Conditioner in Cold Weather Decij Home Repair 15 January 6th 05 05:12 AM
HVAC Dilemma Hell Toupee Home Repair 5 July 2nd 04 01:11 PM
Residential HVAC contractor recommendation in Houston, TX? TURTLE Home Repair 6 July 24th 03 08:23 PM


All times are GMT +1. The time now is 06:58 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"