  #41   Report Post  
Bill
 
Posts: n/a
Default

In message , tony sayer
writes

We've used one from RS components, was around 70 quid IIRC


You just reminded me I forgot to fetch their new CD home tonight,
thanks.
Do you have a part No by any chance Tony?
--
Bill
  #42   Report Post  
Bill
 
Posts: n/a
Default

In message , Andy Wade
writes
Bill wrote:


Hi Andy,

I doubt that the supply authority (distribution network operator, or
whatever they're called this week) would accept that. (You do realise
that you're supposed to liaise with them?)

No I didn't thanks. May be worth a call to them to see what they would
expect to see in the way of protection.

You'd need two contactors and it would only need the contacts on the
mains feed one to weld closed for your genny to be capable of
back-feeding the mains... A conventional generator change-over switch
is much safer and more straightforward bet.


Is a conventional change over switch automatic or manually operated? I
was looking at a contactor as that is what is in the control panel of
the genny at the moment, unfortunately it is only rated at 40A, it came
off a remote radio site and only had to back a fairly small load and so
didn't warrant a higher rated unit.
--
Bill
  #43   Report Post  
tony sayer
 
Posts: n/a
Default

In article , Bill
writes
In message , tony sayer
writes

We've used one from RS components, was around 70 quid IIRC


You just reminded me I forgot to fetch their new CD home tonight,
thanks.
Do you have a part No by any chance Tony?


Check yer mail
--
Tony Sayer

  #44   Report Post  
Andy Wade
 
Posts: n/a
Default

Bill wrote:

[Liaise with supplier]

No I didn't thanks. May be worth a call to them to see what they would
expect to see in the way of protection.


The difficult bit these days will be getting through to someone who
understands what you're talking about. Contact the distribution network
operator for your area, not the supplier who sends your bills.

Is a conventional change over switch automatic or manually operated?


I had the manual type in mind.

--
Andy
  #45   Report Post  
Dave Liquorice
 
Posts: n/a
Default

On Thu, 23 Sep 2004 22:40:38 GMT, Bill wrote:

No I didn't thanks. May be worth a call to them to see what they
would expect to see in the way of protection.


They'll probably be happy with a proper changeover switch with a fool
proof break before make action. This is normally arranged by having
the a 3 position switch with a center off. Indeed this makes sense
from safety point of view as you can the ensure that the supply
onwards is really off. Just in case you switch it to "generator" to
isolate then some bright spark starts the genny...

--
Cheers
Dave. pam is missing e-mail



Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Generator Bypass (here we go again! :+) Jay Home Repair 7 August 24th 04 04:34 PM
Replacement engine for Colemate Generator Robert Snyder Metalworking 12 August 23rd 04 03:31 AM
Old Man Winter Will Hit Us Tonight! Maryjoe Home Repair 29 February 2nd 04 06:26 AM
Generator FAQ Gunner Metalworking 0 January 23rd 04 05:24 PM
Generator Experience [email protected] Home Ownership 10 October 12th 03 01:28 AM


All times are GMT +1. The time now is 01:10 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"