Apparent leak on CH system
Every three or four weeks I need to de-air the towel radiator in the bathroom.
This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. Can anyone suggest the best way of solving this. I have searched the visible pipe work, but to no affect. A Worcester Bosch Greenstar 25 combi boiler is fitted. Peter -- A Conservative Government is an organised hypocrisy. Benjamin Disraeli 1804 - 1881 |
#2
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19/12/2020 09:06, Chris Hogg wrote:
On 19 Dec 2020 08:08:22 GMT, Peter James wrote: Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. Can anyone suggest the best way of solving this. I have searched the visible pipe work, but to no affect. A Worcester Bosch Greenstar 25 combi boiler is fitted. Peter Is it a vented or sealed system? If the latter, is the expansion vessel doing what it ought to, or is it knackered and the pressure relief valve is leaking? But that would show up as a regular need to repressurise, which hopefully the OP would have reported. Might it not suggest a system with no inhibitor that is consequently still corroding? |
#3
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19 Dec 2020 08:08:22 GMT, Peter James wrote:
Every three or four weeks I need to de-air the towel radiator in the bathroom. Hydrogen, liberated from the water as iron takes up the oxygen. Does the system have inhibitor? This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. On the basis that for something to get in something needs to come out, yes but it's not the whole story. If a vented system is it pumping over? Even a tiny little bit just as the pump starts (or stops) will circulate oxygenated water into the system. -- Cheers Dave. |
#4
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19/12/2020 09:06, Chris Hogg wrote:
On 19 Dec 2020 08:08:22 GMT, Peter James wrote: Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. Can anyone suggest the best way of solving this. I have searched the visible pipe work, but to no affect. A Worcester Bosch Greenstar 25 combi boiler is fitted. Peter Is it a vented or sealed system? If the latter, is the expansion vessel doing what it ought to, or is it knackered and the pressure relief valve is leaking? If the former is the system pumping over? Pump running too fast and the water is circulating up the expansion pipe and into the open expansion tank. This can aerate the water and when drawn back into your CH pipework the air has to go somewhere. You may only see a pump-over as some of the system closes down such as when thermostatic radiator valves close down once temperature is reached etc. -- mailto : news {at} admac {dot} myzen {dot} co {dot} uk |
#5
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19/12/2020 08:08, Peter James wrote:
Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. That's a possibility. Another is that its not air, but hydrogen accumulating from corrosion processes. Do you know if there is adequate corrosion inhibitor in there? (you could test by trying to ignite the gas as its bled from the rad). In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. Such products still exist. Probably best only used as a last resort though. Can anyone suggest the best way of solving this. I have searched the visible pipe work, but to no affect. Very small leaks can evaporate away before you see liquid water. In hard water areas you may see a small verdigris or scale stain though. You could add a small quantity of Fluorescein dye to the primary water, and then go round with a UV torch to see if you can fine a leak location then. -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ |
#6
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19 Dec 2020 08:08:22 GMT, Peter James wrote:
Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. No they haven't. |
#7
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19/12/2020 08:08, Peter James wrote:
Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. Can anyone suggest the best way of solving this. I have searched the visible pipe work, but to no affect. A Worcester Bosch Greenstar 25 combi boiler is fitted. Peter Probably not even worth doing. Mine has similar, but two years after the plumber noted a weeping gate valve on the primary of the boiler ' not worth fixing mate, it will scale up if you keep refilling ' the frequency of bleed and recharge is down to about 6-monthly -- Renewable energy: Expensive solutions that don't work to a problem that doesn't exist instituted by self legalising protection rackets that don't protect, masquerading as public servants who don't serve the public. |
#8
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19 Dec 2020 at 09:06:45 GMT, "Chris Hogg" wrote:
On 19 Dec 2020 08:08:22 GMT, Peter James wrote: Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. Can anyone suggest the best way of solving this. I have searched the visible pipe work, but to no affect. A Worcester Bosch Greenstar 25 combi boiler is fitted. Peter Is it a vented or sealed system? If the latter, is the expansion vessel doing what it ought to, or is it knackered and the pressure relief valve is leaking? It's a sealed system. Only 7 month old from new. Peter -- A Conservative Government is an organised hypocrisy. Benjamin Disraeli 1804 - 1881 |
#9
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19 Dec 2020 at 12:21:04 GMT, "John Rumm"
wrote: On 19/12/2020 08:08, Peter James wrote: Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. That's a possibility. Another is that its not air, but hydrogen accumulating from corrosion processes. Do you know if there is adequate corrosion inhibitor in there? Yes there us, I watched the Engineer run it into the system Peter |
#10
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 20/12/2020 07:23, Peter James wrote:
On 19 Dec 2020 at 09:06:45 GMT, "Chris Hogg" wrote: On 19 Dec 2020 08:08:22 GMT, Peter James wrote: Is it a vented or sealed system? If the latter, is the expansion vessel doing what it ought to, or is it knackered and the pressure relief valve is leaking? It's a sealed system. Only 7 month old from new. Peter By that I assume you mean the whole system is new, not just the boiler? In which case you may find it is just the air coming out of all that fresh water used to fill the system. I have just (2 years ago) gone though a similar experience and had to be bleeding the towel rail for the biggest part of 9 months or so. Not needed bleeds or any top ups in the last year. -- Chris B (News) |
#11
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
In article ,
Chris B wrote: On 20/12/2020 07:23, Peter James wrote: On 19 Dec 2020 at 09:06:45 GMT, "Chris Hogg" wrote: On 19 Dec 2020 08:08:22 GMT, Peter James wrote: Is it a vented or sealed system? If the latter, is the expansion vessel doing what it ought to, or is it knackered and the pressure relief valve is leaking? It's a sealed system. Only 7 month old from new. Peter By that I assume you mean the whole system is new, not just the boiler? In which case you may find it is just the air coming out of all that fresh water used to fill the system. I have just (2 years ago) gone though a similar experience and had to be bleeding the towel rail for the biggest part of 9 months or so. Not needed bleeds or any top ups in the last year. It's odd. My towel rail also needs bleeding from time to time. It's not the highest rad in the system either - by a long way. System is pressurized and doesn't seem to have any leaks to speak of - I'd guess I add some water to it every couple of years. There is plenty inhibitor, and the rad is stainless steel. Never have to bleed any other rad in the system. -- *The best cure for sea sickness, is to sit under a tree. Dave Plowman London SW To e-mail, change noise into sound. |
#12
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On Sun, 20 Dec 2020 11:15:04 +0000 (GMT), Dave Plowman (News) wrote:
It's odd. My towel rail also needs bleeding from time to time. It's not the highest rad in the system either - by a long way. Is it the first inverted "U" from the boiler? Air released from the water by the heating will collect there. This doesn't have to be the highest point in the system 'cause air won't travel down wards very easily. -- Cheers Dave. |
#13
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
In article l.net,
Dave Liquorice wrote: On Sun, 20 Dec 2020 11:15:04 +0000 (GMT), Dave Plowman (News) wrote: It's odd. My towel rail also needs bleeding from time to time. It's not the highest rad in the system either - by a long way. Is it the first inverted "U" from the boiler? Air released from the water by the heating will collect there. This doesn't have to be the highest point in the system 'cause air won't travel down wards very easily. That could well be it - boiler is in the bathroom too. It's no big deal - certainly not worth the effort of investigating why. There could well be a tiny leak somewhere - but doesn't show. -- *How's my driving? Call 999* Dave Plowman London SW To e-mail, change noise into sound. |
#14
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 19/12/2020 08:08, Peter James wrote:
Every three or four weeks I need to de-air the towel radiator in the bathroom. This is the highest Radiator in the system. A friend, who is a retired plumber, suggested that I have a small leak somewhere in the system. In his day he would have solved it with the addition to the system of a "leak fixing additive". But he does admit he is totally out of date and things might have moved on from this. Can anyone suggest the best way of solving this. I have searched the visible pipe work, but to no affect. A Worcester Bosch Greenstar 25 combi boiler is fitted. Peter Skillbuilder posted this only yesterday: https://www.youtube.com/watch?v=KHogrs_OkxM (Basically, put some cheap perfume into the system, run it for a week or two, then go round the house sniffing). -- Reentrant |
#15
Posted to uk.d-i-y
|
|||
|
|||
Apparent leak on CH system
On 20/12/2020 17:46, Reentrant wrote:
(Basically, put some cheap perfume into the system, run it for a week or two, then go round the house sniffing). Zoflora would probably work for this https://www.tesco.com/groceries/en-G...ucts/262483441 -- mailto : news {at} admac {dot} myzen {dot} co {dot} uk |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
She may upwards entitle into Abduljalil when the apparent investigators rent out of the furious training. | Metalworking | |||
Consumer unit trips at odd times for no apparent reason | UK diy | |||
Apparent Backup in Basement | Home Repair | |||
Toshiba 32A42, apparent uP problem | Electronics Repair | |||
RCA CTC 177BH2, model 27GT613, excessive width and apparent pincushion problem | Electronics Repair |