Default Extending single core.

Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed insulation
and three are 2 single core cables (6181Y 1.5mm2) right through centre
of where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number of
8x4 dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to
allow reroute.

The is not enough slack in the singles to do this .... and easy solution
would be to cut each single and splice in a 12" extension. I can make
the cut so this happens above the header plate, and it can be clipped to
joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.
Is this acceptable under 17th Edition ?

Not that any inspection taking place .... but prefer to do things right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley J804
junction boxes.
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 8,019
Default Extending single core.

On 22/08/2019 11:16, rick wrote:
Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed insulation
and three are 2 single core cables (6181Y 1.5mm2) right through centre
of where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number of
8x4 dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to
allow reroute.

The is not enough slack in the singles to do this .... and easy solution
would be to cut each single and splice in a 12" extension.Â*Â* I can make
the cut so this happens above the header plate, and it can be clipped to
joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.
Is this acceptable under 17th Edition ?

Not that any inspection taking place .... but prefer to do things right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley J804
junction boxes.


If it were me, solder and heat shrink would be a no brainer. I think
it's still regs compliant. So maybe crimps are quicker and (even) more
reliable done in a factory environment, but in awkward spaces I am very
confident of my ability to make a good solder joint. I keep one of those
butane "Cooks" torches in my box of soldering kit, sometimes easier than
a soldering iron. Plus they are good for heat shrink too.
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 25,191
Default Extending single core.

On 22/08/2019 11:16, rick wrote:
Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed insulation
and three are 2 single core cables (6181Y 1.5mm2) right through centre
of where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number of
8x4 dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to
allow reroute.

The is not enough slack in the singles to do this .... and easy solution
would be to cut each single and splice in a 12" extension.Â*Â* I can make
the cut so this happens above the header plate, and it can be clipped to
joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.


Solder and heatshrink is fine. Crimps and heatshrink would be the more
commonly used way.

Is this acceptable under 17th Edition ?


Yup, and the 18th, which is what now applies :-)

Not that any inspection taking place .... but prefer to do things right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley J804
junction boxes.


Wago terminals and a wago box would also be ok.


--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
  #4   Report Post  
Posted to uk.d-i-y
ARW ARW is offline
external usenet poster
 
Posts: 10,161
Default Extending single core.

On 22/08/2019 14:13, John Rumm wrote:
On 22/08/2019 11:16, rick wrote:
Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed insulation
and three are 2 single core cables (6181Y 1.5mm2) right through centre
of where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number of
8x4 dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to
allow reroute.

The is not enough slack in the singles to do this .... and easy
solution would be to cut each single and splice in a 12" extension.
I can make the cut so this happens above the header plate, and it can
be clipped to joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.


Solder and heatshrink is fine. Crimps and heatshrink would be the more
commonly used way.

Is this acceptable under 17th Edition ?


Yup, and the 18th, which is what now applies :-)

Not that any inspection taking place .... but prefer to do things right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley
J804 junction boxes.


Wago terminals and a wago box would also be ok.


Or Wago connectors in a choc box. I believe the wago boxes are bulky.

--
Adam
  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 10,998
Default Extending single core.

What do these cables feed, I wonder?
Brian

--
----- --
This newsgroup posting comes to you directly from...
The Sofa of Brian Gaff...

Blind user, so no pictures please
Note this Signature is meaningless.!
"newshound" wrote in message
o.uk...
On 22/08/2019 11:16, rick wrote:
Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed insulation and
three are 2 single core cables (6181Y 1.5mm2) right through centre of
where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number of 8x4
dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to allow
reroute.

The is not enough slack in the singles to do this .... and easy solution
would be to cut each single and splice in a 12" extension. I can make the
cut so this happens above the header plate, and it can be clipped to
joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.
Is this acceptable under 17th Edition ?

Not that any inspection taking place .... but prefer to do things right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley J804
junction boxes.


If it were me, solder and heat shrink would be a no brainer. I think it's
still regs compliant. So maybe crimps are quicker and (even) more reliable
done in a factory environment, but in awkward spaces I am very confident
of my ability to make a good solder joint. I keep one of those butane
"Cooks" torches in my box of soldering kit, sometimes easier than a
soldering iron. Plus they are good for heat shrink too.





  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,554
Default Extending single core.

On 22/08/2019 11:16, rick wrote:
Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed insulation
and three are 2 single core cables (6181Y 1.5mm2) right through centre
of where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number of
8x4 dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to
allow reroute.

The is not enough slack in the singles to do this .... and easy solution
would be to cut each single and splice in a 12" extension.Â*Â* I can make
the cut so this happens above the header plate, and it can be clipped to
joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.
Is this acceptable under 17th Edition ?

Not that any inspection taking place .... but prefer to do things right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley J804
junction boxes.



Its a lot easier to crimp and its more reliable than soldering.

Wago push fit would be better than soldering.

  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 25,191
Default Extending single core.

On 22/08/2019 17:31, ARW wrote:
On 22/08/2019 14:13, John Rumm wrote:
On 22/08/2019 11:16, rick wrote:
Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed insulation
and three are 2 single core cables (6181Y 1.5mm2) right through
centre of where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number of
8x4 dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to
allow reroute.

The is not enough slack in the singles to do this .... and easy
solution would be to cut each single and splice in a 12" extension. I
can make the cut so this happens above the header plate, and it can
be clipped to joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.


Solder and heatshrink is fine. Crimps and heatshrink would be the more
commonly used way.

Is this acceptable under 17th Edition ?


Yup, and the 18th, which is what now applies :-)

Not that any inspection taking place .... but prefer to do things right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley
J804 junction boxes.


Wago terminals and a wago box would also be ok.


Or Wago connectors in a choc box. I believe the wago boxes are bulky.


Yup true, although the cable grips are easier to use...


--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
  #8   Report Post  
Posted to uk.d-i-y
ARW ARW is offline
external usenet poster
 
Posts: 10,161
Default Extending single core.

On 22/08/2019 23:43, John Rumm wrote:
On 22/08/2019 17:31, ARW wrote:
On 22/08/2019 14:13, John Rumm wrote:
On 22/08/2019 11:16, rick wrote:
Typical a job just got bigger
Having to fit a 200x90 extract duct through an external wall (Timber
fame-cavity-brick)
Brickwork cut neat, cut inside dry lining fine ... removed
insulation and three are 2 single core cables (6181Y 1.5mm2) right
through centre of where duct needs to go.
Had no option duct has to go though a this point.

It is not an easy job to replace these - would need a large number
of 8x4 dry lining sheets removed.
No option to remove floor above due to underfloor heating

I have drilled in a new hole in timber frame header (horizontal) to
allow reroute.

The is not enough slack in the singles to do this .... and easy
solution would be to cut each single and splice in a 12" extension.
I can make the cut so this happens above the header plate, and it
can be clipped to joist for mechanical support.

The splice ... is it acceptable to solder connect ? .,.... I could
solder, insulate & sheath with double layers of heat shrink, and
mechanically fix .... simple & neat.

Solder and heatshrink is fine. Crimps and heatshrink would be the
more commonly used way.

Is this acceptable under 17th Edition ?

Yup, and the 18th, which is what now applies :-)

Not that any inspection taking place .... but prefer to do things
right.

Alternative but bulky & not so easy is to splice in with 2 x Ashley
J804 junction boxes.

Wago terminals and a wago box would also be ok.


Or Wago connectors in a choc box. I believe the wago boxes are bulky.


Yup true, although the cable grips are easier to use...



The OP did suggest he could clip the cables. That would IMHO meet the
regs without any cord grip.

--
Adam
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
guide sleeves, polit bit, core bit, core lifter, core barrel, TUDEX, ODEX, DTH hammer, drilling wangsbin Woodturning 0 September 1st 06 10:45 AM
Underground, quarrying, mining, air-leg, jack-leg, hand-held rock drills, button bit, drag bits,drill rod, drill tube, drill bit, core bit, core barrel, diamonde core bit, DTH hammer, taper rod, integral drill rod, taper bit, rock drilling tools wangsbin Woodturning 0 September 1st 06 07:34 AM
Extending a two core power cable with a figure 8 connector [email protected] UK diy 13 November 28th 04 03:37 PM
2 Core to 3 Core Lighting circuit The Question Asker UK diy 13 November 25th 04 05:09 PM
Change hollow core door to solid core door terry Woodworking 15 September 27th 04 12:48 PM


All times are GMT +1. The time now is 03:34 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"