#1
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
Enquiry from my son as dads know everything :-(
Would it be safe to use a 2 KW heater plugged into a 1.8 KW timer plug? The heater has options for 1250kw / 750kw or both, one option could be to disconnect a switch maybe. What do you reckon? |
#2
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
In article ,
ss writes: Enquiry from my son as dads know everything :-( Would it be safe to use a 2 KW heater plugged into a 1.8 KW timer plug? The heater has options for 1250kw / 750kw or both, one option could be to disconnect a switch maybe. What do you reckon? I've never seen a timer plug rated less than 13A. However, I wouldn't want to run one a max load for long, even so. TBH, I would consider an immersion heater timeswitch. What's the type of heater, and why the timeswitch? Portable heaters on timeswitches can be a really bad thing, as people can put things down too close or on top or move them when they're off, and then they come on when there's no one to smell the burning. -- Andrew Gabriel [email address is not usable -- followup in the newsgroup] |
#3
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On 20/10/2012 18:47, Andrew Gabriel wrote:
In , writes: Enquiry from my son as dads know everything :-( Would it be safe to use a 2 KW heater plugged into a 1.8 KW timer plug? The heater has options for 1250kw / 750kw or both, one option could be to disconnect a switch maybe. What do you reckon? I've never seen a timer plug rated less than 13A. However, I wouldn't want to run one a max load for long, even so. TBH, I would consider an immersion heater timeswitch. What's the type of heater, and why the timeswitch? Portable heaters on timeswitches can be a really bad thing, as people can put things down too close or on top or move them when they're off, and then they come on when there's no one to smell the burning. Quote... "I've a 2kw convection heater; And a timer plug - but it says its rated max 1.8kw" Its a count down timer so that it cuts off after so long max 1 hour. |
#4
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
Andrew Gabriel wrote:
In article , ss writes: Enquiry from my son as dads know everything :-( Would it be safe to use a 2 KW heater plugged into a 1.8 KW timer plug? The heater has options for 1250kw / 750kw or both, one option could be to disconnect a switch maybe. What do you reckon? I've never seen a timer plug rated less than 13A. However, I wouldn't want to run one a max load for long, even so. TBH, I would consider an immersion heater timeswitch. What's the type of heater, and why the timeswitch? Portable heaters on timeswitches can be a really bad thing, as people can put things down too close or on top or move them when they're off, and then they come on when there's no one to smell the burning. Andrew, you have perhaps had a sheltered life - at least when it comes to these things. Lots of timers and their near cousin the radio remote socket, are built with 10amp relays rather than the marginally dearer 16amp models. Although it is mentioned in the destructions - I feel is is bad practise as there is no fuse to limit the current to match the relay rating. Bob |
#5
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
In article ,
ss writes: On 20/10/2012 18:47, Andrew Gabriel wrote: In , writes: Enquiry from my son as dads know everything :-( Would it be safe to use a 2 KW heater plugged into a 1.8 KW timer plug? The heater has options for 1250kw / 750kw or both, one option could be to disconnect a switch maybe. What do you reckon? I've never seen a timer plug rated less than 13A. However, I wouldn't want to run one a max load for long, even so. TBH, I would consider an immersion heater timeswitch. What's the type of heater, and why the timeswitch? Portable heaters on timeswitches can be a really bad thing, as people can put things down too close or on top or move them when they're off, and then they come on when there's no one to smell the burning. Quote... "I've a 2kw convection heater; And a timer plug - but it says its rated max 1.8kw" Its a count down timer so that it cuts off after so long max 1 hour. Again, that's a feature included in some immersion heater timers. As a countdown timer needs someone there to switch it on, that is probably less of an issue than a timeswitch. You might be able to disable the "both" setting. -- Andrew Gabriel [email address is not usable -- followup in the newsgroup] |
#6
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On Saturday, October 20, 2012 6:28:09 PM UTC+1, ss wrote:
Enquiry from my son as dads know everything :-( Would it be safe to use a 2 KW heater plugged into a 1.8 KW timer plug? The heater has options for 1250kw / 750kw or both, one option could be to disconnect a switch maybe. What do you reckon? Truth is timers arent always safe at their rated current. The only way to find out for sure is run it a while and see if it gets hot. NT |
#7
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On Saturday, October 20, 2012 6:28:09 PM UTC+1, ss wrote:
Enquiry from my son as dads know everything :-( Would it be safe to use a 2 KW heater plugged into a 1.8 KW timer plug? The heater has options for 1250kw / 750kw or both, one option could be to disconnect a switch maybe. What do you reckon? A series cap is another option http://wiki.diyfaq.org.uk/index.php?title=Dropper NT |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
plug in timer | Home Repair | |||
Damaged Electric Plug on Appliance | Home Repair | |||
Plug in timer | UK diy | |||
Dial type countertop appliance timer for the kitchen? | Electronics | |||
Appliance Timer Advance Motor Help Here | Home Repair |