Default Not mentioned in boiler instructions ?

I have a Baxi Combi 105HE Boiler.
We do not have a thermostat connected to it so we just use the one on the
boiler itself and also the integral timer.

We don't want the boiler on all the time and the wife, although been shown
many times what to do, is reluctant to touch it incase she damages it.

After having it recently serviced, I decided to put an external timer and
thermostat onto it The ones I have gone for are the Drayton LP111

timer and the Drayton RTS8 CombiStat.

WIRING CONNECTIONS A

Remove link from pin 1 & 2 on boiler

Connect pin 1 to timer LIVE and return switch wire to pin 2.

Neutral from timer to mains input neutral.

On the timer, LIVE from pin 2 of boiler to LIVE on timer with link to
connection 1.

Neutral from boiler to neutral on timer.

Switch return from connection 3 on timer to pin 2 on boiler.

Now the big switch on. Timer lights up and desired heating on/off times
installed.

Boiler did not start up at desired time. Manual override did not work,
although timer indicated that it was.

Only when I switched the integral timer to constant did the external timer
work as it should.

Is this right....? I thought the purpose of an external timer was to do away
completely with the integral timer,

but there was nothing in the instuctions. Am I supposed to remove integral
timer ?

Not fitted thermostat yet until I know everything is working correctly.

Oh by the way, timer switched boiler off at desired time.

Your thoughts and comments most welcomed

James


  #2   Report Post  
Posted to free.uk.diy.home,uk.d-i-y
external usenet poster
 
Posts: 7,688
Default Not mentioned in boiler instructions ?


"the_constructor" wrote in message
o.uk...
I have a Baxi Combi 105HE Boiler.
We do not have a thermostat connected to it so we just use the one on the
boiler itself and also the integral timer.

We don't want the boiler on all the time and the wife, although been shown
many times what to do, is reluctant to touch it incase she damages it.

After having it recently serviced, I decided to put an external timer and
thermostat onto it The ones I have gone for are the Drayton LP111

timer and the Drayton RTS8 CombiStat.

WIRING CONNECTIONS A

Remove link from pin 1 & 2 on boiler

Connect pin 1 to timer LIVE and return switch wire to pin 2.

Neutral from timer to mains input neutral.

On the timer, LIVE from pin 2 of boiler to LIVE on timer with link to
connection 1.

Neutral from boiler to neutral on timer.

Switch return from connection 3 on timer to pin 2 on boiler.

Now the big switch on. Timer lights up and desired heating on/off times
installed.

Boiler did not start up at desired time. Manual override did not work,
although timer indicated that it was.

Only when I switched the integral timer to constant did the external timer
work as it should.

Is this right....? I thought the purpose of an external timer was to do
away completely with the integral timer,

but there was nothing in the instuctions. Am I supposed to remove integral
timer ?

Not fitted thermostat yet until I know everything is working correctly.

Oh by the way, timer switched boiler off at desired time.

Your thoughts and comments most welcomed

James


You either need to remove the integral timer and link out the connections or
leave it in the ON position.

The two timers are in series so you need both timers to call for heat to
make the boiler fire up.

Adam

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
SPP as mentioned in SED for John Slaugther petrus bitbyter Electronic Schematics 0 October 6th 07 02:21 AM
poly v motor belt mentioned in some previous post bizHB Woodturning 5 July 4th 06 11:52 PM
Any opinons of Anant planes (mentioned in another thread)? [email protected] Woodworking 12 January 29th 06 03:19 AM
Kevin L. Mentioned that there is a problem with Pines dying in Southern KY [email protected] Woodworking 7 January 12th 06 12:19 PM


All times are GMT +1. The time now is 02:58 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"