Default When gas boiler fires up hob flames dim

I notice a big drop in pressure when my gas boiler fires up and I am
cooking - is something wrong? it's always been like this - bothe the
boiler and hob have seperate runs from near the gas meter so they're
not both on teh same piece of pipe or anything.

If the gas is on low on the hob when the boiler kicks in it can put
the hob out occassionally - the pressure drop seems worst when the
boiler first fires up. - also the boiler is 10 or 20 years old.

  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 11,175
Default When gas boiler fires up hob flames dim

In article . com,
405 TD Estate writes:
I notice a big drop in pressure when my gas boiler fires up and I am
cooking - is something wrong? it's always been like this - bothe the
boiler and hob have seperate runs from near the gas meter so they're
not both on teh same piece of pipe or anything.

If the gas is on low on the hob when the boiler kicks in it can put
the hob out occassionally - the pressure drop seems worst when the
boiler first fires up. - also the boiler is 10 or 20 years old.


It's going to be necessary to measure the gas pressure with
either one and both appliances operating. Would also be useful
to know the power inputs of both appliances and the size, length
and number of bends on the common pipe before they split apart.
From the too little information provided, it sounds like it
could be Transco's regulator which isn't working correctly.

--
Andrew Gabriel
[email address is not usable -- followup in the newsgroup]
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,231
Default When gas boiler fires up hob flames dim

On Mon, 05 Nov 2007 00:55:34 -0800, 405 TD Estate wrote:

I notice a big drop in pressure when my gas boiler fires up and I am
cooking - is something wrong? it's always been like this - bothe the
boiler and hob have seperate runs from near the gas meter so they're
not both on teh same piece of pipe or anything.

If the gas is on low on the hob when the boiler kicks in it can put
the hob out occassionally - the pressure drop seems worst when the
boiler first fires up. - also the boiler is 10 or 20 years old.


Read the relevant section in the gas fitting FAQ.
You have a fairly serious problem which might just be someone else
responsibility.


--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at http://www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html
Choosing a Boiler FAQ http://www.makewrite.demon.co.uk/BoilerChoice.html
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 6,896
Default When gas boiler fires up hob flames dim

In article . com, 405
TD Estate scribeth thus
I notice a big drop in pressure when my gas boiler fires up and I am
cooking - is something wrong? it's always been like this - bothe the
boiler and hob have seperate runs from near the gas meter so they're
not both on teh same piece of pipe or anything.

If the gas is on low on the hob when the boiler kicks in it can put
the hob out occassionally - the pressure drop seems worst when the
boiler first fires up. - also the boiler is 10 or 20 years old.


Suggest you get Transco out, and soon, to see if their regulator is
delivering what it should.

This just shouldn't happen!...
--
Tony Sayer

  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,861
Default When gas boiler fires up hob flames dim

In message . com, 405
TD Estate writes
I notice a big drop in pressure when my gas boiler fires up and I am
cooking - is something wrong? it's always been like this - bothe the
boiler and hob have seperate runs from near the gas meter so they're
not both on teh same piece of pipe or anything.

If the gas is on low on the hob when the boiler kicks in it can put
the hob out occassionally - the pressure drop seems worst when the
boiler first fires up. - also the boiler is 10 or 20 years old.

HAve you accidentally knocked the lever on the gas inlet so that it's
not fully open ?

--
geoff
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Oil Boiler fires intermittently Clint Home Repair 4 March 9th 07 10:13 PM
When boiler fires hob flames go down Seri UK diy 17 December 17th 04 09:37 AM
Whirlpool gas dryer, flames out after start Raymond Cruz Home Repair 3 October 14th 04 12:49 PM
boiler fires on and off constantly - Biasi Riva Jon UK diy 4 July 18th 04 11:17 AM
Gas Cooktop and Yellow Flames Mark Jaggers Home Repair 12 November 29th 03 07:46 AM


All times are GMT +1. The time now is 11:46 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"