  #1   Report Post  
Cicero
 
Posts: n/a
Default Consumer unit replacement / Certification

I will soon be replacing an existing consumer unit with a new unit and the
new unit will be located about 1 metre from its present position.

This will require the various circuit cables to be shortened but no other
changes will be made to circuits.

Also the existing tails from the meter to the new unit will need to be
extended (actually replaced with new) by 1 metre to reach the consumer unit
position. Total length of the new tails will be about 2.5 metres.

Bearing in mind that no circuit changes are to be made, can anybody tell me
if I need to provide some form of certification for the electricity board
people (nPower) who will connect the new tails from the meter to the
consumer unit?

Tia,

Cic.


  #2   Report Post  
Peter Crosland
 
Posts: n/a
Default

I will soon be replacing an existing consumer unit with a new unit and the
new unit will be located about 1 metre from its present position.

This will require the various circuit cables to be shortened but no other
changes will be made to circuits.

Also the existing tails from the meter to the new unit will need to be
extended (actually replaced with new) by 1 metre to reach the consumer
unit
position. Total length of the new tails will be about 2.5 metres.

Bearing in mind that no circuit changes are to be made, can anybody tell
me
if I need to provide some form of certification for the electricity board
people (nPower) who will connect the new tails from the meter to the
consumer unit?



They could quite reasonable ask for the whole house system to be tested but
I don't know if they would.

Peter Crosland


  #4   Report Post  
Sparks
 
Posts: n/a
Default

"Cicero" wrote in message
. uk...
Bearing in mind that no circuit changes are to be made, can anybody tell
me
if I need to provide some form of certification for the electricity board
people (nPower) who will connect the new tails from the meter to the
consumer unit?


About 18 months ago (maybe longer), I got my supply on a tempory disconnect.
Someone comes out AM to pull the fuse, then someone then comes back PM to
put it back (They take the fuse away, so you can't connect it back up
yourself!)

When I spoke to them on the phone, I explained I was going to be installing
an isolator between the meter and the CU myself, they didn't seem to have a
problem with this.

When it came to it being reconnected, the bloke who came asked to see the
test certificate. I said I didn't have one, as I had done the work myself,
he scratched his head and said he really needs to see a certificate, I
showed him what I had done, and told him there was no mention of this
certificate from the person I booked the disconnect with, he seemed happy
with it, and reconnected the fuse anyway - We didn't receive an electricity
bill for about a year after this, maybe it was co-incidental, or maybe he
had to fiddle something because he didn't have the certificate - who knows -
(We are paying the bills now, after a bloody huge bill hit the doormat (they
gave us a year to pay it though :-) )

This was all pre part P, so I would think this may well be different now!
If I were you, I would call your elec company, and ask them if any
certification is required for the reconnection.

If there is, you could just pull the fuse yourself and install an isolator
to extend the tails (This also has the added benefit of letting you isolate
the supply before the CU without pulling the fuse again)

Or, get a qualified electrician to do this bit if you don't want to pull the
fuse yourself although he would probably just pull the fuse, or maybe work
live (We had our CU replaced about 20 years ago (I was 5, so couldn't quite
manage it then!) he seemed to have done it live, as the fuse seal was not
broken - a braver man than me, especially as the CU back is metal!!)

Sparks...


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
consumer unit mounting board pistolknight UK diy 8 August 9th 05 09:42 PM
Hunter ceiling fan replacement switch -- do I snip wires and stab into new unit? Dolchas Home Repair 1 September 26th 04 07:48 PM
Fitting a Wylex Consumer unit with spur to shed [email protected] UK diy 3 December 10th 03 01:05 PM
old circuits, new consumer unit David Robinson UK diy 5 September 5th 03 11:49 AM
F&G Concept 2000 Consumer Unit Live Busbar Query Andy Taylor UK diy 1 September 3rd 03 01:52 PM


All times are GMT +1. The time now is 08:24 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"