I am trying to solve a 3-way switch circuit issue in an old house. The
wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? |
#2
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote:
I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Since there are only 3 wires at each location, that makes it easy, assuming everything was wired correctly originally. You need a no contact voltage tester like this: http://www.specialized.net/Specializ...0VAC-7281.aspx Take one set of 3 ways and disconnect all of the wires. Turn the power on and test all of the wires. Only 1 of the 6 should be hot. When you find it, turn the power back off and mark that wire with black tape. Wire this location with a 3-way using the wire with black tape as the common. The order of the other two don't matter. Turn the power back on and go to the 3 wires at the other switch. Only 1 of those 3 will be hot. Get a helper to flip the other switch. The original hot wire will go dead another wire will become hot. Turn the power back off. The wire that is never hot at that switch location will be the common. Mark it with black tape and wire the other 3 way. That should work. |
#3
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
"Metspitzer" wrote in message
... On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Since there are only 3 wires at each location, that makes it easy, assuming everything was wired correctly originally. You need a no contact voltage tester like this: http://www.specialized.net/Specializ...0VAC-7281.aspx Take one set of 3 ways and disconnect all of the wires. Turn the power on and test all of the wires. Only 1 of the 6 should be hot. When you find it, turn the power back off and mark that wire with black tape. Wire this location with a 3-way using the wire with black tape as the common. The order of the other two don't matter. Turn the power back on and go to the 3 wires at the other switch. Only 1 of those 3 will be hot. Get a helper to flip the other switch. The original hot wire will go dead another wire will become hot. Turn the power back off. The wire that is never hot at that switch location will be the common. Mark it with black tape and wire the other 3 way. That should work. Thanks Metspitzer. Great explanation, and I think that will do the trick. I have a no contact voltage tester, and I was already doing a little testing with it on Friday afternoon; but I decided that I should do some more searching and research first and then get back to it this coming week and do it the right way. It never occurred to me that the wire on the second 3-way switch that never gets hot (when doing what you said) would be the one that is the common. But, that makes sense, and I think it will work. |
#4
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Sun, 24 Nov 2013 20:21:35 -0500, "TomR"
wrote: "Metspitzer" wrote in message .. . On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Since there are only 3 wires at each location, that makes it easy, assuming everything was wired correctly originally. You need a no contact voltage tester like this: http://www.specialized.net/Specializ...0VAC-7281.aspx Take one set of 3 ways and disconnect all of the wires. Turn the power on and test all of the wires. Only 1 of the 6 should be hot. When you find it, turn the power back off and mark that wire with black tape. Wire this location with a 3-way using the wire with black tape as the common. The order of the other two don't matter. Turn the power back on and go to the 3 wires at the other switch. Only 1 of those 3 will be hot. Get a helper to flip the other switch. The original hot wire will go dead another wire will become hot. Turn the power back off. The wire that is never hot at that switch location will be the common. Mark it with black tape and wire the other 3 way. That should work. Thanks Metspitzer. Great explanation, and I think that will do the trick. I have a no contact voltage tester, and I was already doing a little testing with it on Friday afternoon; but I decided that I should do some more searching and research first and then get back to it this coming week and do it the right way. It never occurred to me that the wire on the second 3-way switch that never gets hot (when doing what you said) would be the one that is the common. But, that makes sense, and I think it will work. You are welcome. Let us know. |
#5
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
"Metspitzer" wrote in message
... On Sun, 24 Nov 2013 20:21:35 -0500, "TomR" wrote: "Metspitzer" wrote in message . .. On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Since there are only 3 wires at each location, that makes it easy, assuming everything was wired correctly originally. You need a no contact voltage tester like this: http://www.specialized.net/Specializ...0VAC-7281.aspx Take one set of 3 ways and disconnect all of the wires. Turn the power on and test all of the wires. Only 1 of the 6 should be hot. When you find it, turn the power back off and mark that wire with black tape. Wire this location with a 3-way using the wire with black tape as the common. The order of the other two don't matter. Turn the power back on and go to the 3 wires at the other switch. Only 1 of those 3 will be hot. Get a helper to flip the other switch. The original hot wire will go dead another wire will become hot. Turn the power back off. The wire that is never hot at that switch location will be the common. Mark it with black tape and wire the other 3 way. That should work. Thanks Metspitzer. Great explanation, and I think that will do the trick. I have a no contact voltage tester, and I was already doing a little testing with it on Friday afternoon; but I decided that I should do some more searching and research first and then get back to it this coming week and do it the right way. It never occurred to me that the wire on the second 3-way switch that never gets hot (when doing what you said) would be the one that is the common. But, that makes sense, and I think it will work. You are welcome. Let us know. I will do that. |
#6
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Sun, 24 Nov 2013 20:21:35 -0500, "TomR" wrote:
Thanks Metspitzer. Great explanation, and I think that will do the trick. I have a no contact voltage tester, and I was already doing a little testing with it on Friday afternoon; but I decided that I should do some more searching and research first and then get back to it this coming week and do it the right way. It never occurred to me that the wire on the second 3-way switch that never gets hot (when doing what you said) would be the one that is the common. But, that makes sense, and I think it will work. Here is a tip that might help. On K+T wiring, the ceiling boxes were almost always the power source. The reason is that back then, lighting was the top priority. Outlets were rare and few and even those were mostly for lamps. So, almost all the power source wires went across a ceiling. The light you want to control most likely has the "source" wires. Therefore, both common wires on one switches go to the light fixture box. One to the bulb, the other to the "source". If nothing else works, get a multimeter (Walmart for $10) and some cheap wire long enough to go from both switches to the fixture. Set meter to OHMS, Shut off power in house, and remove the wires from both switches. Attach one lead from the meter to the wire going to the bulb. (alligator clips help). Use your long wire on the other meter lead, and find the one in the switch box that matches (meter will indicate continuity). Then do the same for the source wire. Those two are the common wires. I always have a multimeter and a 50ft roll of single strand automotive or doorbell wire handy to do this sort of thing. I worked many years doing handyman work and mostly in old homes that had K+T wiring. Over the years that wiring was changed, modified, and/or simply disconnected and even cut off, when a wall or doorway was added or something. Some of those jobs were a total nightmare, but I always managed to get the wires to work. What complicated those homes was that some were huge single family homes that originally had servant quarters and were built for the wealthy in those days. Then they were changed into multi-family apartments and supposedly rewired so each apartment had it's own electric meter. More often than not, apartments had the wrong meter feeding part of their apt., and tenants would complain that their electric bill was very high, while others paid nearly nothing. It would be my job to straighten out this mess, and a mess it was..... I'd shut off the power to that apt. and suddenly hit a live wire, or disconnect something in another apt. I recall one huge home taking me over 2 weeks of 8 hour days to get it all straightened out. But I'll admit now, I liked the challenge! |
#7
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
replying to Metspitzer, Patrick wrote:
Awesome. This helped me a bunch! -- for full context, visit https://www.homeownershub.com/mainte...ng-771957-.htm |
#8
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? I would suggest by process of elimination. Using the pic at Option 8. After you identify the incoming Hot, get first switch installed, then the "red" or "white" at the 2nd switch will become hot, depending on position of first switch. The black at the 2nd switch will stay cold regardless of pos. of 1st switch. Of course you want all the "loose" wires clear and not touching anything. Do not assume that the first incoming Hot is in the downstairs boxes !! |
#9
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
"Retired" wrote in message
... But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? I would suggest by process of elimination. Using the pic at Option 8. After you identify the incoming Hot, get first switch installed, then the "red" or "white" at the 2nd switch will become hot, depending on position of first switch. The black at the 2nd switch will stay cold regardless of pos. of 1st switch. Of course you want all the "loose" wires clear and not touching anything. Do not assume that the first incoming Hot is in the downstairs boxes !! Makes sense. Thanks. |
#10
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
probably best to safely abandon the current wiring and replace it with all new..
messing with knob and tube isnt really a good idea....... |
#11
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Sun, 24 Nov 2013 15:14:53 -0800 (PST), bob haller
wrote: probably best to safely abandon the current wiring and replace it with all new.. messing with knob and tube isnt really a good idea....... Why is is not a good idea? K+T wires always worked, and they were quite durable considering how long they last. If the wall plaster is removed, such as during a remodel, by all means replace the wiring, but there is no sense ripping open walls as long as the old wiring is still in good shape, especially for just simple lighting. The downfall of K+T wiring has always been that the color came off the wires, lack of a ground, and unsafe *IF* people would put oversize fuses in (which was far too common). If you still have fuses, by all means replace the fuse box with modern breakers. Or at least use the proper fuse. But for low amperage lighting, particularly if modern CFL or LED lights are used, there is no reason to have to rip a house apart to replace K+T wiring. You can buy colored electrical tape. Make your job easier by putting the proper colored tape on each wire. Black - White - Red. Then do as others have told you in this thread to identify which are the HOT wires. Here are some diagrams: http://www.electrical-online.com/wp-...way-switch.jpg http://home-garden.blurtit.com/var/q...y_wiring_1.jpg |
#12
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
wrote in message
... On Sun, 24 Nov 2013 15:14:53 -0800 (PST), bob haller wrote: probably best to safely abandon the current wiring and replace it with all new.. messing with knob and tube isnt really a good idea....... Why is is not a good idea? K+T wires always worked, and they were quite durable considering how long they last. If the wall plaster is removed, such as during a remodel, by all means replace the wiring, but there is no sense ripping open walls as long as the old wiring is still in good shape, especially for just simple lighting. The downfall of K+T wiring has always been that the color came off the wires, lack of a ground, and unsafe *IF* people would put oversize fuses in (which was far too common). If you still have fuses, by all means replace the fuse box with modern breakers. Or at least use the proper fuse. But for low amperage lighting, particularly if modern CFL or LED lights are used, there is no reason to have to rip a house apart to replace K+T wiring. I agree. No need to build a new house. I just want to get these 3-way switches working correctly. You can buy colored electrical tape. Make your job easier by putting the proper colored tape on each wire. Black - White - Red. Then do as others have told you in this thread to identify which are the HOT wires. Makes sense. |
#13
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() |
#15
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Mon, 25 Nov 2013 11:16:56 -0500, "TomR" wrote:
micky wrote: On Sun, 24 Nov 2013 17:42:26 -0600, wrote: The downfall of K+T wiring has always been that the color came off the wires, lack of a ground, and unsafe *IF* people would put oversize fuses in (which was far too common). I lived for 12 years in a 1930 apartment building in Brooklyn. It had fuses of course, but the owner had put Fuzestat (spelling??) sockets in each fuse socket, in the basement and in each of the 49 apartments. Blue was 15 amps, and only a 15 amp Fuzestat fuse would screw into a 15-amp Fuzestat socket. The threads were at the wrong angle or too narrow for other size fuses. The Fuzestat socket had raspy teeth so that unscrewing one from the fuse socket it was in was hard to do. I think 20 amps was orange. Each apartment got 20 amps in a basement fuse, and one or two 15 amp fuses in the apartment itsellf. My 6-room 3-bath apartment ran on 20 amps, which was enough, even most of the time with a small air conditioner. . BTW, with Fuzestats, there is no easy way to put a penny in the socket and bypass the fuse. Another big advantage of them. There is a button conductor in the bottom of the hole, but there isn't the typical side-of-the-hole conductor. Instead there are are two metal tabs that slide along the top of the Fuzestat socket as the fuse is screwed in, and make contact when it's all the way in. It's hard or impossible to touch these tabs because the fuse is big enough to cover the whole thing. This all kept any idiot tenants from putting in fuses that were bigger than they should be. They were more expensive, maybe a lot more, than regular fuses, but worth it. In my case, the tenant paid for them. BTW, I was the tenant. I certainly paid for the fuses in my apt. but I didn't want to wait for the super or wake him up in the middle of the night, so even after he locked the button to go to the basement, I bypassed the lock switch, went myself, and changed my fuse myself. If you still have fuses, by all means replace the fuse box with modern breakers. Or at least use the proper fuse. But for low amperage lighting, particularly if modern CFL or LED lights are used, there is no reason to have to rip a house apart to replace K+T wiring. Interesting info. In my case, the building has a modern circuit breaker panel and a lot of newer wiring with grounded 3-prong outlets etc. But, some of the circuits -- such as these 3-way switches -- are on the old wiring. Also interesting. |
#16
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
unmolested K&T is marginally ok. but tapping into it, modifying it, can add new hazards. a good friend had a small home fire where a solder joint detoriated and overheated, fortunately he cauht it just in time. it was smoldering he could of lost the entire house. his dad had soldered that joint over 30 years ago....
which is why i said just replace the entire thing..... all the 3 way light switches etc, that the OP said he had intentionally miss wired |
#17
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Sun, 24 Nov 2013 17:27:26 -0800 (PST), bob haller
wrote: unmolested K&T is marginally ok. but tapping into it, modifying it, can add new hazards. a good friend had a small home fire where a solder joint detoriated and overheated, fortunately he cauht it just in time. it was smoldering he could of lost the entire house. his dad had soldered that joint over 30 years ago.... which is why i said just replace the entire thing..... all the 3 way light switches etc, that the OP said he had intentionally miss wired ------- Yea, but he's not tampering with the actual wires, just moving them around inside a box to get them on the right screws on the switches. That solder joint was apparently not soldered well in the first place. Soldered wires were some of the best connections made, if they were done properly. I also would bet that they had a 30A fuse in use on some #14 wire, and had plugged in an electric heating device. When I had to tap into existing K+T wiring on my jobs, I would install a box and use wirenuts. But on a few jobs, I did also solder them when it was impractical to install a box, such as in an attic where the wires did not provide enough length to use a box, and I only needed to add a tap to provide another light. I'd just bare the wires, attach some romex, and solder them and apply tape. Safety was always a main concern, but customers were not willing to pay to have their whole house ripped apart, and repaired just to add a ceiling fan or some track lights. By the way, here is another tip I forgot to mention. Colored heat shrink tubing works great to color the wires the way they should be. Costs a little more than tape, but is real easy to use, and even protects the wires from fraying on their ends which that old cloth wire was known to do. |
#18
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote:
I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. I'm confused, so all I can say is write things down, to make a diagram of what wires you know about, at least the swtiches and an inch of wire whereever there's a wire, indicating what color every wire is (the real color too, in case any wire has been painted.) . And make a chart of what they should do. LIke Switch 1, turn on lights A and B. Then start enlarging the chart and the wiring diagram to show what wires you would need to make it do what the chart says you want it to do. When you're not sure which switch is for which, see which actual switch and wires is closer to which item on the chart. Also, normally when both switches are near the bottom of the stairs, the switch for the living room will be closer to the living room than the switch for the stairs will be. When I bought my house, the front hall was miswired so one switch only worked if the other switch was in the right position. And of the switches by the stairs. the one closer to the basement stairs controlled the landing near the second floor. The switches worked but they were in the wrong place. The electrician lived in the n'hood. A house might have been part of his payment for doing the wiring. You coudl tell his house because it had more lights than the rest of us, and he had a vent from the range hood above his sliding glass door. (For the rest of us, the air went through a filter and right back into the kitchen) Anyhow, I saw him at a party 10 or 15 years after he'd wired our houses, and I told him about the two mistakes. I thought he'd think it was funny after all these years -- I thought it was funny when I had to fix them --, but I was totally wrong. He was annoyed, didn't believe me iirc, and I was sorry I said anything. |
#19
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote:
I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . http://imgur.com/mlB47zL I marked what should be going on. 1 (common) will be hot all the time. a and b will be the travelers and 2 (common) will go to the light. (BTW the color code on the ledger is wrong.) White is a traveler, not common. Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? |
#20
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
Metspitzer wrote:
On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. . . . , I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . http://imgur.com/mlB47zL I marked what should be going on. 1 (common) will be hot all the time. a and b will be the travelers and 2 (common) will go to the light. (BTW the color code on the ledger is wrong.) White is a traveler, not common. Thanks. You're right. Where it says "White Wire (Common)", it should say something like "White Wire, coded black (Traveler). And, it looks like they coded the white wire black where needed to distinguish it from being a typical neutral wire. |
#21
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 11/25/2013 04:16 PM, TomR wrote:
Metspitzer wrote: On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. . . . , I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . http://imgur.com/mlB47zL I marked what should be going on. 1 (common) will be hot all the time. a and b will be the travelers and 2 (common) will go to the light. (BTW the color code on the ledger is wrong.) White is a traveler, not common. Thanks. You're right. Where it says "White Wire (Common)", it should say something like "White Wire, coded black (Traveler). And, it looks like they coded the white wire black where needed to distinguish it from being a typical neutral wire. That's correct; electricians don't always do that but any time a white is used as a non-neutral conductor it should be relabeled with a ring of colored tape (any color other than white, grey, or green that is. "normal" colors for residential 120V wiring would be black or red.) This isn't a suggestion but a code requirement. nate -- replace "roosters" with "cox" to reply. http://members.cox.net/njnagel |
#22
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Tue, 26 Nov 2013 17:40:30 -0500, Nate Nagel
wrote: On 11/25/2013 04:16 PM, TomR wrote: Metspitzer wrote: On Sun, 24 Nov 2013 15:25:16 -0500, "TomR" wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. . . . , I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . http://imgur.com/mlB47zL I marked what should be going on. 1 (common) will be hot all the time. a and b will be the travelers and 2 (common) will go to the light. (BTW the color code on the ledger is wrong.) White is a traveler, not common. Thanks. You're right. Where it says "White Wire (Common)", it should say something like "White Wire, coded black (Traveler). And, it looks like they coded the white wire black where needed to distinguish it from being a typical neutral wire. That's correct; electricians don't always do that but any time a white is used as a non-neutral conductor it should be relabeled with a ring of colored tape (any color other than white, grey, or green that is. "normal" colors for residential 120V wiring would be black or red.) This isn't a suggestion but a code requirement. I "paint" white wires that are repurposed as hots, with a red Sharpie. I keep one in my "electrical" toolbox. I don't know if it's kosher but it works. |
#23
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() "TomR" wrote in message ... I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Given the age of the house and wiring method, keep in mind there may be a possibility it's a "California 3 way" |
#24
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() "Rick" wrote in message ... "TomR" wrote in message ... I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Given the age of the house and wiring method, keep in mind there may be a possibility it's a "California 3 way" A variation, with both hots on same leg H--------o o--------H o--------light----------o N--------o o--------N |
#25
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Mon, 25 Nov 2013 14:42:54 -0500, "Rick"
wrote: "Rick" wrote in message m... "TomR" wrote in message ... I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Given the age of the house and wiring method, keep in mind there may be a possibility it's a "California 3 way" A variation, with both hots on same leg H--------o o--------H o--------light----------o N--------o o--------N I know there is always that possibility, but since I worked in mostly hospitals I have never encountered one. If he finds a hot at each switch with everything disconnected, that should tell us. |
#26
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
Metspitzer wrote:
On Mon, 25 Nov 2013 14:42:54 -0500, "Rick" wrote: "Rick" wrote in message ... "TomR" wrote in message ... I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Given the age of the house and wiring method, keep in mind there may be a possibility it's a "California 3 way" A variation, with both hots on same leg H--------o o--------H o--------light----------o N--------o o--------N I know there is always that possibility, but since I worked in mostly hospitals I have never encountered one. If he finds a hot at each switch with everything disconnected, that should tell us. I'll check for that, just in case that's what I have. If I do, I'll probably post back because I don't think I'll know what to do in that case. And, I have to admit that I was a little disappointed when I found out that a "California 3 way" didn't have anything to do with girls in bikinis. |
#27
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 11/25/2013 1:42 PM, Rick wrote:
"Rick" wrote in message ... "TomR" wrote in message ... I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Given the age of the house and wiring method, keep in mind there may be a possibility it's a "California 3 way" A variation, with both hots on same leg H--------o o--------H o--------light----------o N--------o o--------N A "Carter" circuit. Has long been not code compliant (the screw shell of the lamp has to connect to the neutral). I think it was once allowed back in the K&T days. And someone might mistakenly use it. If you wire it in any of the wrong ways it will blow a fuse. |
#28
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 11/24/2013 03:25 PM, TomR wrote:
I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Easy way to troubleshoot: get yourself a test light, voltmeter, or NCVD with adjustable sensitivity, and turn the sensitivity on the NCVD down so that you can "read" individual conductors. If using a test light or voltmeter plug an extension cord into an outlet that's not on the same circuit as the lights so you have a neutral available to test for voltage (I'm assuming that you don't have a ground to use for reference, since you said there were no obvious ground wires.) Then, turn off the circuit for the lights, pull both 3-ways out of their boxes, and disconnect all wires from the switches, and leave them hanging out of the boxes and not touching anything/each other. Turn the power back on. Check for voltage at all wires. There should only be one wire out of all six with power on it. That's your live feed, and should be connected to the common terminal at that switch. The other two are obviously the travelers. Turn the power back off and reinstall that one switch. Turn the power back on. Go to the second switch location. There should again be only one wire with power on it. That is one of your travelers. Flip the first switch. Now there should be a different wire with power on it. That's your other traveler. The wire that was never hot throughout the procedure should be the wire that is directly connected to the light. If you want to verify this, carefully touch it to the traveler that's hot. The light should come on. That wire that goes directly to the light connects to the common terminal of the second switch. Turn the power off, make connections to the 2nd switch, turn power back on, test, drink beer, pat self on back. I've been in your exact situation before, and I feel your pain ![]() shrink and colored electrical tape is your friend when dealing with old dirty cloth covered wiring. Hope this helps nate -- replace "roosters" with "cox" to reply. http://members.cox.net/njnagel |
#29
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
Nate Nagel wrote:
On 11/24/2013 03:25 PM, TomR wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Easy way to troubleshoot: get yourself a test light, voltmeter, or NCVD with adjustable sensitivity, and turn the sensitivity on the NCVD down so that you can "read" individual conductors. If using a test light or voltmeter plug an extension cord into an outlet that's not on the same circuit as the lights so you have a neutral available to test for voltage (I'm assuming that you don't have a ground to use for reference, since you said there were no obvious ground wires.) Then, turn off the circuit for the lights, pull both 3-ways out of their boxes, and disconnect all wires from the switches, and leave them hanging out of the boxes and not touching anything/each other. Turn the power back on. Check for voltage at all wires. There should only be one wire out of all six with power on it. That's your live feed, and should be connected to the common terminal at that switch. The other two are obviously the travelers. Turn the power back off and reinstall that one switch. Turn the power back on. Go to the second switch location. There should again be only one wire with power on it. That is one of your travelers. Flip the first switch. Now there should be a different wire with power on it. That's your other traveler. The wire that was never hot throughout the procedure should be the wire that is directly connected to the light. If you want to verify this, carefully touch it to the traveler that's hot. The light should come on. That wire that goes directly to the light connects to the common terminal of the second switch. Turn the power off, make connections to the 2nd switch, turn power back on, test, drink beer, pat self on back. I've been in your exact situation before, and I feel your pain ![]() shrink and colored electrical tape is your friend when dealing with old dirty cloth covered wiring. Hope this helps nate Thanks Nate. That's the same process that Metspitzer suggested, and that's what I am going to try first. Hopefully, that will work and I'll be all set. I thought I was going to be doing the work this week, but now it looks like I won't get back there to do it until next week. Either way, after I try what you and others suggested, I'll post back here how it worked out. |
#30
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 11/26/2013 03:35 PM, TomR wrote:
Nate Nagel wrote: On 11/24/2013 03:25 PM, TomR wrote: I am trying to solve a 3-way switch circuit issue in an old house. The wiring in the house is old, and it is either knob and tube wiring or whatever came after that and before "Romex" etc. There are no ground wires visible anywhere in either circuit, and everything is so dusty and dirty that I can't tell what is a white wire and what is a black wire etc. And, to be more precise, there are actually two different 3-way switch circuits that I am trying to get resolved at the same time. Downstairs, near the front door entrance, the are two 3-way switches -- one of the 3-way switches controls the downstairs living room ceiling light. The other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. At the top of the stairs, there are two 3-way switches -- one of those 3-way switches controls the downstairs living room ceiling light, and the other 3-way switch controls the hallway light that is outside of the upstairs bedrooms. I can tell which 3-way switch (upstairs and downstairs) is for the living room ceiling light, and which one (upstairs and downstairs) is for the hallway light. To make things a little more complicated, the whole setup was intentionally temporarily wired incorrectly a few years back because I couldn't figure out how to get things working correctly and I needed a way to at least be able to turn the living room light and the hallway light on and off -- even though the 3-way switch function was disabled in the process. In other words, I temporarily have it that only one switch controls each light. It's a long story why I did that, but that is not important now. Now, here's the story on the wiring: Coming into each of the 3-way switch boxes upstairs, and each of the 3-way switch boxes downstairs, are 3 exactly wires. There are no other wires in each switch box -- no neutrals wired together etc. -- just 3 wires in each box and no other wires leaving the boxes etc. I found the following link to various 3-way switch wiring options: http://www.easy-do-it-yourself-home-...g-diagram.html . Based on what I have (just 3 wires in each box) I am assuming that the two circuits are wired as shown in Option #8 on that link. The power source appears to go to each light, and from each light, the switch wires run to each of the switches. I concluded that because I don't see any other wiring options where there are ONLY 3 wires in each switch box. And, now for the problem: I need to put new 3-way switches in, both in the upstairs boxes and in the downstairs boxes. The downstairs boxes have push button 3-way switches that are broken, so they need to be replaced. I need to figure out how to rewire the system, using the existing wires, and connecting those wires to the four new 3-way switches that I bought. I am thinking that, with the power on, but the switches removed, I can figure out which wire is the hot "source" wire that goes to one of the switches for each circuit. I can connect that hot wire to the hot common for each of those two switches, and connect the other two wires in each of those boxes to the "traveler" screws on those switches. But, then, when I go to the other switch at the other end of each circuit, how can I tell which wire in each of those boxes goes to the hot "common" screw? Once I know that, I can connect that hot common wire to the black "common" screw and just connect the other two wires to the traveler screws. But, how do I know which of the 3 wires goes to the hot "common" screw? Easy way to troubleshoot: get yourself a test light, voltmeter, or NCVD with adjustable sensitivity, and turn the sensitivity on the NCVD down so that you can "read" individual conductors. If using a test light or voltmeter plug an extension cord into an outlet that's not on the same circuit as the lights so you have a neutral available to test for voltage (I'm assuming that you don't have a ground to use for reference, since you said there were no obvious ground wires.) Then, turn off the circuit for the lights, pull both 3-ways out of their boxes, and disconnect all wires from the switches, and leave them hanging out of the boxes and not touching anything/each other. Turn the power back on. Check for voltage at all wires. There should only be one wire out of all six with power on it. That's your live feed, and should be connected to the common terminal at that switch. The other two are obviously the travelers. Turn the power back off and reinstall that one switch. Turn the power back on. Go to the second switch location. There should again be only one wire with power on it. That is one of your travelers. Flip the first switch. Now there should be a different wire with power on it. That's your other traveler. The wire that was never hot throughout the procedure should be the wire that is directly connected to the light. If you want to verify this, carefully touch it to the traveler that's hot. The light should come on. That wire that goes directly to the light connects to the common terminal of the second switch. Turn the power off, make connections to the 2nd switch, turn power back on, test, drink beer, pat self on back. I've been in your exact situation before, and I feel your pain ![]() shrink and colored electrical tape is your friend when dealing with old dirty cloth covered wiring. Hope this helps nate Thanks Nate. That's the same process that Metspitzer suggested, and that's what I am going to try first. Hopefully, that will work and I'll be all set. I thought I was going to be doing the work this week, but now it looks like I won't get back there to do it until next week. Either way, after I try what you and others suggested, I'll post back here how it worked out. Yup, do that... there are other options to the "normal" setup but they are rare. What I'm expecting that you'll find is that since this is an older house, the electrician will have run the hot wire straight to the light fixture location, and from the same box run a 14/3 to each of the 3-ways. Back in the very old days electricity was thought of as primarily a lighting utility and installations reflected that; a floor was typically wired with the hot wires going to the ceiling boxes and switch legs dropped to the wall switches from there. Receps were also dropped from the ceiling light boxes. Wire fill would be unacceptably high today were this a new installation. I know what I said above sounds crazy, but that is exactly what I found in a house built in the late 40's that I had to do some troubleshooting on after a PO had a "handy friend" replace all the devices and none of the 3-ways worked. If you do find multiple hot wires with all the switches disconnected, stop there and ask for advice as you may be dealing with something like a California 3-way or if you're really unlucky a Carter circuit. If your house is newer than 1930ish and/or you can determine that your wiring is NOT K&T but actual cables (can you see the sheath of the cables inside the boxes? I've lived in several houses that had cloth covered wiring but they were a sort of ungrounded proto-Romex but with cloth over rubber insulation on the wires and a cloth sheath over the whole cable) you should not run into the Carter circuit which is good as it would be bad news if you did. I'd be tempted to treat the discovery of one as a sign that it is time to rewire, as it has been prohibited for ages as in half the switch positions it allows the shell of the socket to be energized, making removing a broken light bulb rather dangerous. nate -- replace "roosters" with "cox" to reply. http://members.cox.net/njnagel |
#31
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
My situation is a little trickier. When taking off all 6 wires, there's a hot wire at each switch. As I understand it, when the power source is between the switches, only one can be connected to the common. The way it's wired now, one switch must remain in the "on" then controlled from the second switch.
Without colored wires, the only ones I can identify are the hot wires. Any advice? |
#32
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() |
#33
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 10/22/2015 6:38 AM, Micky wrote:
On Thu, 22 Oct 2015 02:19:42 -0700 (PDT), wrote: My situation is a little trickier. When taking off all 6 wires, there's a hot wire at each switch. As I understand it, when the power source is between the switches, only one can be connected to the common. The way it's wired now, one switch must remain in the "on" then controlled from the second switch. Wired now? I thought you had disconnected the wires. Without colored wires, the only ones I can identify are the hot wires. First, make a drawing. Don't expect to remember what you've seen. Turn off the power and measure the voltage at the hot wires to make sure you turned off the right circuit. Then measure the resistance to ground or neutral of the other wires. The ones that go through the light bulb to neutral should have non-infinite resistance. Do this with real lightbulbs in the circuit. I'm not sure what the resistance of other bulbs is. Look online for various ways to wire a 3-way switch. With both switches removed, isn't the bulb connected to nothing on both ends? -- .. Christopher A. Young learn more about Jesus .. www.lds.org .. .. |
#34
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Thu, 22 Oct 2015 07:51:07 -0400, Stormin Mormon
wrote: On 10/22/2015 6:38 AM, Micky wrote: On Thu, 22 Oct 2015 02:19:42 -0700 (PDT), wrote: My situation is a little trickier. When taking off all 6 wires, there's a hot wire at each switch. As I understand it, when the power source is between the switches, only one can be connected to the common. The way it's wired now, one switch must remain in the "on" then controlled from the second switch. Wired now? I thought you had disconnected the wires. Without colored wires, the only ones I can identify are the hot wires. First, make a drawing. Don't expect to remember what you've seen. Turn off the power and measure the voltage at the hot wires to make sure you turned off the right circuit. Then measure the resistance to ground or neutral of the other wires. The ones that go through the light bulb to neutral should have non-infinite resistance. Do this with real lightbulbs in the circuit. I'm not sure what the resistance of other bulbs is. Look online for various ways to wire a 3-way switch. With both switches removed, isn't the bulb connected to nothing on both ends? Maybe with one or two of the ways it can be wired. I can't remember. But certainly with some ways it's still connected to neutral. |
#35
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
Micky wrote:
On Thu, 22 Oct 2015 02:19:42 -0700 (PDT), wrote: My situation is a little trickier. When taking off all 6 wires, there's a hot wire at each switch. As I understand it, when the power source is between the switches, only one can be connected to the common. The way it's wired now, one switch must remain in the "on" then controlled from the second switch. Wired now? I thought you had disconnected the wires. Without colored wires, the only ones I can identify are the hot wires. First, make a drawing. Don't expect to remember what you've seen. Turn off the power and measure the voltage at the hot wires to make sure you turned off the right circuit. Then measure the resistance to ground or neutral of the other wires. The ones that go through the light bulb to neutral should have non-infinite resistance. Do this with real lightbulbs in the circuit. I'm not sure what the resistance of other bulbs is. Mark down the resistance on your drawing. The ones with infinite resistance are probably just travelers, wires that went to the other switch, and which are disconnected now. Get the switches, and try to figure out from the way the wires are bent, which wires went to which screws, and try to figure out with a meter, which screw is common and which wires are supposed to be the travelers. With 6 wires, you should have made a drawing before you disconnected things . Look online for various ways to wire a 3-way switch. There are 4 or 5. Use your meter to help determine which method is yours. Any advice? http://users.wfu.edu/matthews/course.../switches.html In addition to what you said, the above link might be helpful to William. |
#36
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Thu, 22 Oct 2015 06:51:54 -0500, Ken wrote:
Micky wrote: On Thu, 22 Oct 2015 02:19:42 -0700 (PDT), wrote: My situation is a little trickier. When taking off all 6 wires, there's a hot wire at each switch. As I understand it, when the power source is between the switches, only one can be connected to the common. The way it's wired now, one switch must remain in the "on" then controlled from the second switch. Wired now? I thought you had disconnected the wires. Without colored wires, the only ones I can identify are the hot wires. First, make a drawing. Don't expect to remember what you've seen. Turn off the power and measure the voltage at the hot wires to make sure you turned off the right circuit. Then measure the resistance to ground or neutral of the other wires. The ones that go through the light bulb to neutral should have non-infinite resistance. Do this with real lightbulbs in the circuit. I'm not sure what the resistance of other bulbs is. Mark down the resistance on your drawing. The ones with infinite resistance are probably just travelers, wires that went to the other switch, and which are disconnected now. Get the switches, and try to figure out from the way the wires are bent, which wires went to which screws, and try to figure out with a meter, which screw is common and which wires are supposed to be the travelers. With 6 wires, you should have made a drawing before you disconnected things . Look online for various ways to wire a 3-way switch. There are 4 or 5. Use your meter to help determine which method is yours. Any advice? http://users.wfu.edu/matthews/course.../switches.html In addition to what you said, the above link might be helpful to William. It's very helpful to me, that's for sure. This subpage http://users.wfu.edu/matthews/course...ariations.html is just the sort of page I had in mind. And it enables me to answer the question Chris asked. Take a look and you'll see that one of the six wires always has continuity with the neutral, if a real lighbulb, not burned out, is in its socket. Assuming the neutral has continuity with the ground and that there's a ground wire in the box, that's one place to test with. And it also reminds me of added instructions for the OP. Because I need a drawing to think with. Is this normal, below normal or above normal? Is it a clever way to save brain power by letting the drawing do some of the thinking? Or would a smart person have all this in his head without any help? I really don't know the answer to these questions. I only have myself to compare with, and I always match. Keep the power off. (Always check with a voltmeter to make sure the power is off. Sometimes there are two circuits in the same box, even though I think this is not allowed, so one coudl be off and the other on.) Once you find the wire that has low resistance, under a couple 100 ohms, or a couple thousand if you can't find lower) to neutral, call it N, temporarily connect each of the other two wires in the same box to N. Then go to the other switch box, and check those three wires for neutral (Well, those two probably, because you already found that when the fuse or breaker is on, one of the wires is hot**. But if not, then 3.) The wire that connects to neutral is one of the travelers. Do the same thing with the other wire at the box1 where N is. Now at box2, you've identified both travelers, at both boxes. Reconnect the switches accordingly. **You claimed each box had hot wire. That's not possible if you had really disconnected all 6 wires. But if you didn't disconnect all of of them that's fine with me. Post back if you want instructions for when only one switch is disconnected, or only one or two wires of one switch. Let us know exactly what is connected, what isn't, and what the voltages and resistances are. It's unlikely both switches are broken but quite likely that one is. |
#37
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 10/22/2015 5:19 AM, wrote:
My situation is a little trickier. When taking off all 6 wires, there's a hot wire at each switch. As I understand it, when the power source is between the switches, only one can be connected to the common. The way it's wired now, one switch must remain in the "on" then controlled from the second switch. Without colored wires, the only ones I can identify are the hot wires. Any advice? Yellow vinyl tape and magic marker allows you to label the wires before removing. So you know where they go. Wrap the tape around the wire and back to itself, making a "tape flag". Eat light meals when driving on long trips, as over eating makes you sleepy. Treat everyone with kindness, and manners. Even the burglar who is in your house in the wee hours needs to be treated kindly before you shoot his ass off with a twelve gage and give his carcass to the dog. Fill the fuel tank of your car before the gage gets to half tank, and you'll be less likely to run out of gas in a bad spot. Wash your hands every time, after using the toilet. Helps cut down on spread of disease. Use a paper towel to open the public restroom door, so you don't get the disease the last guy had. (Last guy didn't wash his hands.) Use salt lightly on baked foods such as chicken to bring out the flavor. Girls like flowers, which are cheaper than divorces. -- .. Christopher A. Young learn more about Jesus .. www.lds.org .. .. |
#38
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 10/22/2015 4:49 AM, Stormin Mormon wrote:
On 10/22/2015 5:19 AM, wrote: My situation is a little trickier. When taking off all 6 wires, there's a hot wire at each switch. As I understand it, when the power source is between the switches, only one can be connected to the common. The way it's wired now, one switch must remain in the "on" then controlled from the second switch. Without colored wires, the only ones I can identify are the hot wires. Any advice? Yellow vinyl tape and magic marker allows you to label the wires before removing. So you know where they go. Wrap the tape around the wire and back to itself, making a "tape flag". Eat light meals when driving on long trips, as over eating makes you sleepy. Treat everyone with kindness, and manners. Even the burglar who is in your house in the wee hours needs to be treated kindly before you shoot his ass off with a twelve gage and give his carcass to the dog. Fill the fuel tank of your car before the gage gets to half tank, and you'll be less likely to run out of gas in a bad spot. Wash your hands every time, after using the toilet. Helps cut down on spread of disease. Use a paper towel to open the public restroom door, so you don't get the disease the last guy had. (Last guy didn't wash his hands.) Use salt lightly on baked foods such as chicken to bring out the flavor. Girls like flowers, which are cheaper than divorces. If you have a choice between buying a new car and getting married, buy a red one. |
#39
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On 10/22/2015 1:37 PM, Don Y wrote:
On 10/22/2015 4:49 AM, Stormin Mormon wrote: Girls like flowers, which are cheaper than divorces. If you have a choice between buying a new car and getting married, buy a red one. I once owned a red pickup. Sure felt manly. -- .. Christopher A. Young learn more about Jesus .. www.lds.org .. .. |
#40
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
On Thu, 22 Oct 2015 19:05:43 -0400, Stormin Mormon
wrote: On 10/22/2015 1:37 PM, Don Y wrote: On 10/22/2015 4:49 AM, Stormin Mormon wrote: Girls like flowers, which are cheaper than divorces. If you have a choice between buying a new car and getting married, buy a red one. I once owned a red pickup. Sure felt manly. I had a girlfriend with a red mustang convertible. Unfortunately, she didn't have it when I knew her in NYC. We went out once and she told me she wouldnt' go out with anymore because I was too young. I added a year to my age and told her I was 26, thinking that would settle it. She still said I was too young. In one of my few macho moments, I said, "Well, I'll ask you out again and you can decide then whether you want to go out with me. " And I did and she did. Found out later she was 14 years older than I was, 25 and 39. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
Wiring various machine health switches | Metalworking | |||
Wiring 2 switches to an outlet. | Home Repair | |||
Wiring for switches | UK diy | |||
wiring 3 switches in parallel | Home Repair | |||
lighted switches & aluminum wiring | Home Repair |