  #1   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 174
Default Gas Pipes

My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to two
legs extending in opposite direction in my basement. They eventually meet in
one area, but connect to differing areas. One 3/4" leg extends to my boiler
and Ts off to my garage. The other leg extends to my water heater, my dryer
and a capped off pipe in case I want to install a gas stove. If you were to
see the cluster of pipes, especially as they meet in one area, it looks like
a bad roller coaster design. Therefore, I wanted to remove the two 3/4" legs
and run one 1" leg and teeing off to each area creating a more pleasing look
and eliminating misc. run on pipes.

Anyone see a problem with going to 1" black pipe?


  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 626
Default Gas Pipes

On 7/23/2012 4:11 PM, Meanie wrote:
My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to two
legs extending in opposite direction in my basement. They eventually meet in
one area, but connect to differing areas. One 3/4" leg extends to my boiler
and Ts off to my garage. The other leg extends to my water heater, my dryer
and a capped off pipe in case I want to install a gas stove. If you were to
see the cluster of pipes, especially as they meet in one area, it looks like
a bad roller coaster design. Therefore, I wanted to remove the two 3/4" legs
and run one 1" leg and teeing off to each area creating a more pleasing look
and eliminating misc. run on pipes.

Anyone see a problem with going to 1" black pipe?



if it ain't broken, why fix it? to make your basement look nicer? do you
spend a lot of time down there admiring the view?
  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 174
Default Gas Pipes


"chaniarts" wrote in message
...
On 7/23/2012 4:11 PM, Meanie wrote:
My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to
two
legs extending in opposite direction in my basement. They eventually meet
in
one area, but connect to differing areas. One 3/4" leg extends to my
boiler
and Ts off to my garage. The other leg extends to my water heater, my
dryer
and a capped off pipe in case I want to install a gas stove. If you were
to
see the cluster of pipes, especially as they meet in one area, it looks
like
a bad roller coaster design. Therefore, I wanted to remove the two 3/4"
legs
and run one 1" leg and teeing off to each area creating a more pleasing
look
and eliminating misc. run on pipes.

Anyone see a problem with going to 1" black pipe?



if it ain't broken, why fix it? to make your basement look nicer? do you
spend a lot of time down there admiring the view?


LOL...yea, I know. In preparation of having my furnace installed, I removed
my drop ceiling and realized what a mess it was above with unneeded wires
and pipes. Removing the pipes from my boiler/base boards and rearranging
wires really made it look nice and roomy, which made me want to do the
pipes. You're correct, it isn't broke but that neatness anal retentive
desire makes the hairs on my neck stand up.


  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 18,538
Default Gas Pipes

On Mon, 23 Jul 2012 19:42:22 -0400, "Meanie" wrote:


"chaniarts" wrote in message
...
On 7/23/2012 4:11 PM, Meanie wrote:
My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to
two
legs extending in opposite direction in my basement. They eventually meet
in
one area, but connect to differing areas. One 3/4" leg extends to my
boiler
and Ts off to my garage. The other leg extends to my water heater, my
dryer
and a capped off pipe in case I want to install a gas stove. If you were
to
see the cluster of pipes, especially as they meet in one area, it looks
like
a bad roller coaster design. Therefore, I wanted to remove the two 3/4"
legs
and run one 1" leg and teeing off to each area creating a more pleasing
look
and eliminating misc. run on pipes.

Anyone see a problem with going to 1" black pipe?



if it ain't broken, why fix it? to make your basement look nicer? do you
spend a lot of time down there admiring the view?


LOL...yea, I know. In preparation of having my furnace installed, I removed
my drop ceiling and realized what a mess it was above with unneeded wires
and pipes. Removing the pipes from my boiler/base boards and rearranging
wires really made it look nice and roomy, which made me want to do the
pipes. You're correct, it isn't broke but that neatness anal retentive
desire makes the hairs on my neck stand up.

I'd make it as simple as possible - and I'd use black pipe wherever
possible as it is neat and durable.
  #5   Report Post  
Posted to alt.home.repair
dpb dpb is offline
external usenet poster
 
Posts: 12,595
Default Gas Pipes

On 7/23/2012 6:11 PM, Meanie wrote:
My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to two
legs extending in opposite direction in my basement. They eventually meet in
one area, but connect to differing areas. One 3/4" leg extends to my boiler
and Ts off to my garage. ...

Anyone see a problem with going to 1" black pipe?


A single 1" is equivalent to the two 3/4" in capacity accounting for
pressure drop/friction loss over the same distance so it's adequate from
that standpoint.

Unless there's a point that's closer to the larger feed that is going to
have a larger demand I don't see much to gain, however, in reality.
Unless it's actually obstructing something or somehow preventing use of
an area or somesuch, that is.

If they're going to opposite locations, it would seem there would be no
actual reduction in run length and running a larger (therefore more
expensive) pipe in lieu of existing ones. If there's really some jungle
of fittings I might consider cleaning it up if I came up w/
significantly fewer connections in the end, but I don't think I'd
re-pipe just for the sake of saying I had unless there were a real problem.

--


--



  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 2,415
Default Gas Pipes

"Meanie" wrote:
My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to two
legs extending in opposite direction in my basement. They eventually meet in
one area, but connect to differing areas. One 3/4" leg extends to my boiler
and Ts off to my garage. The other leg extends to my water heater, my dryer
and a capped off pipe in case I want to install a gas stove. If you were to
see the cluster of pipes, especially as they meet in one area, it looks like
a bad roller coaster design. Therefore, I wanted to remove the two 3/4" legs
and run one 1" leg and teeing off to each area creating a more pleasing look
and eliminating misc. run on pipes.

Anyone see a problem with going to 1" black pipe?


I had a gas pipe installed. The guy put in 1 inch to 4 t's each with it's
own valve. I added another t and valve. Problem is, I have to move the
valve set because it's in my way. Work for me later.

Has the op split the 3/4 or the 1 inch ??

Greg
  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4,712
Default Gas Pipes

I'd suggest that you call your local building department, and ignore
anything you read on this list. Except me, you can trust me.

Christopher A. Young
Learn more about Jesus
www.lds.org
..

"Meanie" wrote in message ...
My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to two
legs extending in opposite direction in my basement. They eventually meet in
one area, but connect to differing areas. One 3/4" leg extends to my boiler
and Ts off to my garage. The other leg extends to my water heater, my dryer
and a capped off pipe in case I want to install a gas stove. If you were to
see the cluster of pipes, especially as they meet in one area, it looks like
a bad roller coaster design. Therefore, I wanted to remove the two 3/4" legs
and run one 1" leg and teeing off to each area creating a more pleasing look
and eliminating misc. run on pipes.

Anyone see a problem with going to 1" black pipe?




  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 575
Default Gas Pipes

Which would you trust more, you or Jesus? (Assuming he's not a plumber) ;O)

"Stormin Mormon" wrote in message ...
I'd suggest that you call your local building department, and ignore
anything you read on this list. Except me, you can trust me.

Christopher A. Young
Learn more about Jesus
www.lds.org
.

"Meanie" wrote in message ...
My main line from the gas meter enters the house with a 1" flex conduit
connected to a union, then a reducer to 3/4" black pipe which splits to two
legs extending in opposite direction in my basement. They eventually meet in
one area, but connect to differing areas. One 3/4" leg extends to my boiler
and Ts off to my garage. The other leg extends to my water heater, my dryer
and a capped off pipe in case I want to install a gas stove. If you were to
see the cluster of pipes, especially as they meet in one area, it looks like
a bad roller coaster design. Therefore, I wanted to remove the two 3/4" legs
and run one 1" leg and teeing off to each area creating a more pleasing look
and eliminating misc. run on pipes.

Anyone see a problem with going to 1" black pipe?




Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Can you get flexible gutter pipes/underground pipes? eden UK diy 8 June 25th 09 04:45 PM
Bob- Pipes [email protected] Home Repair 0 March 15th 08 11:43 PM
Pipes Mrs Bonk Home Repair 2 March 4th 06 02:23 AM
Plastic pipes v copper pipes! Vikki UK diy 11 November 26th 05 03:44 PM
Freezing Pipes or Pipes frozen could the Instant Hot Water Recirculator from RedyTemp work [email protected] Home Repair 1 January 11th 04 12:18 PM


All times are GMT +1. The time now is 09:59 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"