Short grounding wires
An open basement ceiling has an octagonal box that serves (and has)
the basement ceiling lights with three conductors coming in/out of it, and the copper grounding wires were wrapped around the metal cable holder (one on each side) and cut, so the grounding wires on each are not much longer than one inch or so. I'd like to add a single conductor to a wall switch to the box, and I'm wondering how to hook up the new grounding wire. Normally, I'd have the new wire go through one of those special grounding wire wire nuts to a box screw, with the other grounding wires wrapped around it in the wire nut, but the others here are too short. Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. Is there a different way of extending grounding wires such as a brass crimp connector? |
#2
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
On 4/15/2011 6:58 PM, terphenyl wrote:
.... ...Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. Is there a different way of extending grounding wires such as a brass crimp connector? Sure, any approved connector can be used. But, there's no reqm'nt that you _must_ use a wire nut; you can just twist and tape; wire nuts are just the quick 'n easy way. -- |
#3
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
terphenyl wrote:
An open basement ceiling has an octagonal box that serves (and has) the basement ceiling lights with three conductors coming in/out of it, and the copper grounding wires were wrapped around the metal cable holder (one on each side) and cut, so the grounding wires on each are not much longer than one inch or so. I'd like to add a single conductor to a wall switch to the box, and I'm wondering how to hook up the new grounding wire. Normally, I'd have the new wire go through one of those special grounding wire wire nuts to a box screw, with the other grounding wires wrapped around it in the wire nut, but the others here are too short. Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. Is there a different way of extending grounding wires such as a brass crimp connector? How about a set screw wire nut? Picture he http://tinyurl.com/45yoryk Run the wires in from opposite ends and leave the cap off. |
#4
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
"dpb" wrote in message ... On 4/15/2011 6:58 PM, terphenyl wrote: ... ...Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. Is there a different way of extending grounding wires such as a brass crimp connector? Sure, any approved connector can be used. But, there's no reqm'nt that you _must_ use a wire nut; you can just twist and tape; wire nuts are just the quick 'n easy way. **They are required to be held together by an approved splicing device, or screwed to a metal box. -- |
#5
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
"terphenyl" wrote in message ... An open basement ceiling has an octagonal box that serves (and has) the basement ceiling lights with three conductors coming in/out of it, and the copper grounding wires were wrapped around the metal cable holder (one on each side) and cut, so the grounding wires on each are not much longer than one inch or so. I'd like to add a single conductor to a wall switch to the box, and I'm wondering how to hook up the new grounding wire. Normally, I'd have the new wire go through one of those special grounding wire wire nuts to a box screw, with the other grounding wires wrapped around it in the wire nut, but the others here are too short. Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. Is there a different way of extending grounding wires such as a brass crimp connector? Buchanan makes a small brass crimp connector. They call them "splice cap crimp connectors" . We call them beer barrels |
#6
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
On 4/15/2011 7:58 PM, terphenyl wrote:
An open basement ceiling has an octagonal box that serves (and has) the basement ceiling lights with three conductors coming in/out of it, and the copper grounding wires were wrapped around the metal cable holder (one on each side) and cut, so the grounding wires on each are not much longer than one inch or so. I'd like to add a single conductor to a wall switch to the box, and I'm wondering how to hook up the new grounding wire. Normally, I'd have the new wire go through one of those special grounding wire wire nuts to a box screw, with the other grounding wires wrapped around it in the wire nut, but the others here are too short. Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. Is there a different way of extending grounding wires such as a brass crimp connector? One of you code wizards please jump in here- this place, like most of the places I saw built growing up, has the boxes grounded that exact same way, and the devices are grounded via their mounting tabs to the metal box. It USED to be code-legal, at least here in midwest. When did it become not legal? Is old work grandfathered, or are you supposed to screw around redoing the old wires whenever you open a box? Other than in damp locations where the touch points could get corroded, or if they were installed improperly and don't make good contact, why would the old way provide any less protection? -- aem sends... |
#7
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
On Apr 15, 8:11*pm, dpb wrote:
On 4/15/2011 6:58 PM, terphenyl wrote: ... ...Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. *Is there a different way of extending grounding wires such as a brass crimp connector? Sure, any approved connector can be used. *But, there's no reqm'nt that you _must_ use a wire nut; you can just twist and tape; wire nuts are just the quick 'n easy way. -- Sounds like a small split bolt might work. I have a few of these with a tapped hole on the backside so that you can screw them to the box. Jimmie |
#8
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
"aemeijers" wrote in message ... On 4/15/2011 7:58 PM, terphenyl wrote: An open basement ceiling has an octagonal box that serves (and has) the basement ceiling lights with three conductors coming in/out of it, and the copper grounding wires were wrapped around the metal cable holder (one on each side) and cut, so the grounding wires on each are not much longer than one inch or so. I'd like to add a single conductor to a wall switch to the box, and I'm wondering how to hook up the new grounding wire. Normally, I'd have the new wire go through one of those special grounding wire wire nuts to a box screw, with the other grounding wires wrapped around it in the wire nut, but the others here are too short. Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. Is there a different way of extending grounding wires such as a brass crimp connector? One of you code wizards please jump in here- this place, like most of the places I saw built growing up, has the boxes grounded that exact same way, and the devices are grounded via their mounting tabs to the metal box. It USED to be code-legal, at least here in midwest. When did it become not legal? Is old work grandfathered, or are you supposed to screw around redoing the old wires whenever you open a box? Other than in damp locations where the touch points could get corroded, or if they were installed improperly and don't make good contact, why would the old way provide any less protection? -- aem sends... ** One would have to know when this was installed, to know what the requirements were at the time. Typically electrical wiring is grandfathered, if it was done properly to begin with, however it's advisable to correct any issues at locations where you're upgrading or extending |
#9
Posted to alt.home.repair
|
|||
|
|||
Short grounding wires
On Apr 15, 7:20*pm, Dean Hoffman wrote:
terphenyl wrote: An open basement ceiling has an octagonal box that serves (and has) the basement ceiling lights with three conductors coming in/out of it, and the copper grounding wires were wrapped around the metal cable holder (one on each side) and cut, so the grounding wires on each are not much longer than one inch or so. *I'd like to add a single conductor to a wall switch to the box, and I'm wondering how to hook up the new grounding wire. *Normally, I'd have the new wire go through one of those special grounding wire wire nuts to a box screw, with the other grounding wires wrapped around it in the wire nut, but the others here are too short. *Adding a wire nut/new pigtail to the older ones, and then another wire nut to link them all together will fill the box. *Is there a different way of extending grounding wires such as a brass crimp connector? * * *How about a set screw wire nut? *Picture he * *http://tinyurl.com/45yoryk* *Run the wires in from opposite ends and leave the cap off. I puzzled as to why you would add a single conductor to a wall switch. Then what happens past the wall switch, how does the wire continue on, or whatever. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
NM wires too short. Now what? | Home Repair | |||
Wires Too Short in Outlet Box, How to Extend Length ? | Home Repair | |||
Adiabatic short-circuit compliance on very short short-circuits | UK diy | |||
Grounding Of Ground Wires In An Electrical Gang Box (how to handle the green ground wires) | Home Repair | |||
Doulble Receptacle Grounding Question/ Switch Grounding | Home Repair |