Default Short grounding wires

An open basement ceiling has an octagonal box that serves (and has)
the basement ceiling lights with three conductors coming in/out of it,
and the copper grounding wires were wrapped around the metal cable
holder (one on each side) and cut, so the grounding wires on each are
not much longer than one inch or so. I'd like to add a single
conductor to a wall switch to the box, and I'm wondering how to hook
up the new grounding wire. Normally, I'd have the new wire go through
one of those special grounding wire wire nuts to a box screw, with the
other grounding wires wrapped around it in the wire nut, but the
others here are too short. Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. Is there a different way of extending grounding wires such
as a brass crimp connector?
  #2   Report Post  
Posted to alt.home.repair
dpb dpb is offline
external usenet poster
 
Posts: 12,595
Default Short grounding wires

On 4/15/2011 6:58 PM, terphenyl wrote:
....

...Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. Is there a different way of extending grounding wires such
as a brass crimp connector?


Sure, any approved connector can be used. But, there's no reqm'nt that
you _must_ use a wire nut; you can just twist and tape; wire nuts are
just the quick 'n easy way.

--

  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 254
Default Short grounding wires

terphenyl wrote:
An open basement ceiling has an octagonal box that serves (and has)
the basement ceiling lights with three conductors coming in/out of it,
and the copper grounding wires were wrapped around the metal cable
holder (one on each side) and cut, so the grounding wires on each are
not much longer than one inch or so. I'd like to add a single
conductor to a wall switch to the box, and I'm wondering how to hook
up the new grounding wire. Normally, I'd have the new wire go through
one of those special grounding wire wire nuts to a box screw, with the
other grounding wires wrapped around it in the wire nut, but the
others here are too short. Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. Is there a different way of extending grounding wires such
as a brass crimp connector?


How about a set screw wire nut? Picture he
http://tinyurl.com/45yoryk Run the wires in from opposite ends and
leave the cap off.
  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,473
Default Short grounding wires


"dpb" wrote in message ...
On 4/15/2011 6:58 PM, terphenyl wrote:
...

...Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. Is there a different way of extending grounding wires such
as a brass crimp connector?


Sure, any approved connector can be used. But, there's no reqm'nt that
you _must_ use a wire nut; you can just twist and tape; wire nuts are just
the quick 'n easy way.


**They are required to be held together by an approved splicing device, or
screwed to a metal box.



--



  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,473
Default Short grounding wires


"terphenyl" wrote in message
...
An open basement ceiling has an octagonal box that serves (and has)
the basement ceiling lights with three conductors coming in/out of it,
and the copper grounding wires were wrapped around the metal cable
holder (one on each side) and cut, so the grounding wires on each are
not much longer than one inch or so. I'd like to add a single
conductor to a wall switch to the box, and I'm wondering how to hook
up the new grounding wire. Normally, I'd have the new wire go through
one of those special grounding wire wire nuts to a box screw, with the
other grounding wires wrapped around it in the wire nut, but the
others here are too short. Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. Is there a different way of extending grounding wires such
as a brass crimp connector?


Buchanan makes a small brass crimp connector. They call them "splice cap
crimp connectors" . We call them beer barrels




  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 5,149
Default Short grounding wires

On 4/15/2011 7:58 PM, terphenyl wrote:
An open basement ceiling has an octagonal box that serves (and has)
the basement ceiling lights with three conductors coming in/out of it,
and the copper grounding wires were wrapped around the metal cable
holder (one on each side) and cut, so the grounding wires on each are
not much longer than one inch or so. I'd like to add a single
conductor to a wall switch to the box, and I'm wondering how to hook
up the new grounding wire. Normally, I'd have the new wire go through
one of those special grounding wire wire nuts to a box screw, with the
other grounding wires wrapped around it in the wire nut, but the
others here are too short. Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. Is there a different way of extending grounding wires such
as a brass crimp connector?


One of you code wizards please jump in here- this place, like most of
the places I saw built growing up, has the boxes grounded that exact
same way, and the devices are grounded via their mounting tabs to the
metal box. It USED to be code-legal, at least here in midwest. When did
it become not legal? Is old work grandfathered, or are you supposed to
screw around redoing the old wires whenever you open a box? Other than
in damp locations where the touch points could get corroded, or if they
were installed improperly and don't make good contact, why would the old
way provide any less protection?

--
aem sends...

  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,417
Default Short grounding wires

On Apr 15, 8:11*pm, dpb wrote:
On 4/15/2011 6:58 PM, terphenyl wrote:
...

...Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. *Is there a different way of extending grounding wires such
as a brass crimp connector?


Sure, any approved connector can be used. *But, there's no reqm'nt that
you _must_ use a wire nut; you can just twist and tape; wire nuts are
just the quick 'n easy way.

--


Sounds like a small split bolt might work. I have a few of these with
a tapped hole on the backside so that you can screw them to the box.

Jimmie
  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,473
Default Short grounding wires


"aemeijers" wrote in message
...
On 4/15/2011 7:58 PM, terphenyl wrote:
An open basement ceiling has an octagonal box that serves (and has)
the basement ceiling lights with three conductors coming in/out of it,
and the copper grounding wires were wrapped around the metal cable
holder (one on each side) and cut, so the grounding wires on each are
not much longer than one inch or so. I'd like to add a single
conductor to a wall switch to the box, and I'm wondering how to hook
up the new grounding wire. Normally, I'd have the new wire go through
one of those special grounding wire wire nuts to a box screw, with the
other grounding wires wrapped around it in the wire nut, but the
others here are too short. Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. Is there a different way of extending grounding wires such
as a brass crimp connector?


One of you code wizards please jump in here- this place, like most of the
places I saw built growing up, has the boxes grounded that exact same way,
and the devices are grounded via their mounting tabs to the metal box. It
USED to be code-legal, at least here in midwest. When did it become not
legal? Is old work grandfathered, or are you supposed to screw around
redoing the old wires whenever you open a box? Other than in damp
locations where the touch points could get corroded, or if they were
installed improperly and don't make good contact, why would the old way
provide any less protection?

--
aem sends...



** One would have to know when this was installed, to know what the
requirements were at the time. Typically electrical wiring is grandfathered,
if it was done properly to begin with, however it's advisable to correct any
issues at locations where you're upgrading or extending


  #9   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 3,236
Default Short grounding wires

On Apr 15, 7:20*pm, Dean Hoffman wrote:
terphenyl wrote:
An open basement ceiling has an octagonal box that serves (and has)
the basement ceiling lights with three conductors coming in/out of it,
and the copper grounding wires were wrapped around the metal cable
holder (one on each side) and cut, so the grounding wires on each are
not much longer than one inch or so. *I'd like to add a single
conductor to a wall switch to the box, and I'm wondering how to hook
up the new grounding wire. *Normally, I'd have the new wire go through
one of those special grounding wire wire nuts to a box screw, with the
other grounding wires wrapped around it in the wire nut, but the
others here are too short. *Adding a wire nut/new pigtail to the older
ones, and then another wire nut to link them all together will fill
the box. *Is there a different way of extending grounding wires such
as a brass crimp connector?


* * *How about a set screw wire nut? *Picture he
* *http://tinyurl.com/45yoryk* *Run the wires in from opposite ends and
leave the cap off.


I puzzled as to why you would add a single conductor to a wall
switch. Then what happens past the wall switch, how does the wire
continue on, or whatever.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
NM wires too short. Now what? Limp Arbor Home Repair 12 February 20th 10 08:40 AM
Wires Too Short in Outlet Box, How to Extend Length ? BOB Home Repair 19 March 20th 06 02:41 PM
Adiabatic short-circuit compliance on very short short-circuits Will Dean UK diy 17 August 23rd 05 12:03 PM
Grounding Of Ground Wires In An Electrical Gang Box (how to handle the green ground wires) Robert11 Home Repair 7 March 8th 05 03:45 PM
Doulble Receptacle Grounding Question/ Switch Grounding Michael Roback Home Repair 1 September 7th 03 07:37 AM