Three electrical code questions
Hi,
1. Is it permissible to install outlets in the same bay that also has heating system pipes? 2. Is it permissble to fasten two cables to a stud with a single staple? 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Many thanks in advance, Aaron Fude |
#2
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
"Aaron Fude" wrote in message ... Hi, 1. Is it permissible to install outlets in the same bay that also has heating system pipes? Yes 2. Is it permissble to fasten two cables to a stud with a single staple? Yes 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Many thanks in advance, Aaron Fude |
#3
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
On Dec 3, 7:14*am, "RBM" wrote:
"Aaron Fude" wrote in message ... Hi, 1. Is it permissible to install outlets in the same bay that also has heating system pipes? Yes 2. Is it permissble to fasten two cables to a stud with a single staple? Yes 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Just outside the electrical boxes or in several places along the way as well? Many thanks in advance, Aaron Fude- Hide quoted text - - Show quoted text - |
#4
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
On Dec 3, 7:07*am, Aaron Fude wrote:
On Dec 3, 7:14*am, "RBM" wrote: "Aaron Fude" wrote in message ... Hi, 1. Is it permissible to install outlets in the same bay that also has heating system pipes? Yes 2. Is it permissble to fasten two cables to a stud with a single staple? Yes 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Just outside the electrical boxes or in several places along the way as well? snip Less than 12" for a metal box, 3" for a plastic box IIRC. If in doubt ask your local building inspector. Quite a few accepted good practices are not incorporated into NEC code. Joe |
#5
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
On Dec 3, 9:55*am, Joe wrote:
On Dec 3, 7:07*am, Aaron Fude wrote: On Dec 3, 7:14*am, "RBM" wrote: "Aaron Fude" wrote in message .... Hi, 1. Is it permissible to install outlets in the same bay that also has heating system pipes? Yes 2. Is it permissble to fasten two cables to a stud with a single staple? Yes 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Just outside the electrical boxes or in several places along the way as well? snip Less than 12" for a metal box, 3" for a plastic box IIRC. If in doubt ask your local building inspector. Quite a few accepted good practices are not incorporated into NEC code. Joe- Hide quoted text - - Show quoted text - It is cinderblock, they were originallly made from old coal cinders. |
#6
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
Ah, that was going to be my question.
I cut out a section of drywall at the top - brought in the cable - and fished it down to the new outlets. For the outlets, I cut out a hole just the size of the box, and then screwed the box to the stud. I did stable the cable at the top since I had access. But next to the box, I did not have access, so I did not. wrote in message ... On Wed, 3 Dec 2008 05:07:19 -0800 (PST), Aaron Fude wrote: On Dec 3, 7:14 am, "RBM" wrote: "Aaron Fude" wrote in message ... Hi, 1. Is it permissible to install outlets in the same bay that also has heating system pipes? Yes 2. Is it permissble to fasten two cables to a stud with a single staple? Yes 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Just outside the electrical boxes or in several places along the way as well? If you are fishing in an existing wall you don't need to staple them |
#7
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
"Kevin" wrote in message l.net... Ah, that was going to be my question. I cut out a section of drywall at the top - brought in the cable - and fished it down to the new outlets. For the outlets, I cut out a hole just the size of the box, and then screwed the box to the stud. I did stable the cable at the top since I had access. But next to the box, I did not have access, so I did not. wrote in message ... On Wed, 3 Dec 2008 05:07:19 -0800 (PST), Aaron Fude wrote: On Dec 3, 7:14 am, "RBM" wrote: "Aaron Fude" wrote in message ... Hi, 1. Is it permissible to install outlets in the same bay that also has heating system pipes? Yes 2. Is it permissble to fasten two cables to a stud with a single staple? Yes 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Just outside the electrical boxes or in several places along the way as well? If you are fishing in an existing wall you don't need to staple them What you did is fine, you'd only have to staple the cable every 4.5 feet and at boxes, in open walls |
#8
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
In article , "RBM" wrote:
"Aaron Fude" wrote in message ... 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Why would they need to be stapled? Seems to me that falls under the clause permitting NM to be fished through voids in existing walls, doesn't it? |
#9
Posted to alt.home.repair
|
|||
|
|||
Three electrical code questions
"Doug Miller" wrote in message ... In article , "RBM" wrote: "Aaron Fude" wrote in message ... 3. I have a cinterblock wall that is framed with 2x4 sole and head plates and 2x3 studs so there is an inch of space between the cinterblocks and the studes. Is it OK for a wire to run behind the studs? Yes, but they still have to be stapled Why would they need to be stapled? Seems to me that falls under the clause permitting NM to be fished through voids in existing walls, doesn't it? Yup, I thought these were open walls until he clarified in a later post |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
electrical questions GFCIs, grounding, and code | Home Repair | |||
electrical code Q | Home Repair | |||
Pa electrical code | Home Repair | |||
Is This The Best Electrical Code Book To Have? | Home Repair | |||
Electrical service ok or out of code | Home Repair |