I have already bought it, but am just curious.
HD had 4 different box connectors. Cheap ones for NM, BX, and BX/AC, and an expensive one for MC. The electrical clerk recommended the NM, but that didn't seem right. I was tempted by the cheap BX clamps, but took the MC since I only needed two of them anyhow. Would code require the ones labeled MC, or would the BX have been adequate? |
#2
![]()
Posted to alt.home.repair
|
|||
|
|||
![]() "Ted" wrote in message ... I have already bought it, but am just curious. HD had 4 different box connectors. Cheap ones for NM, BX, and BX/AC, and an expensive one for MC. The electrical clerk recommended the NM, but that didn't seem right. I was tempted by the cheap BX clamps, but took the MC since I only needed two of them anyhow. Would code require the ones labeled MC, or would the BX have been adequate? NEC requires MC connectors to be used with MC cable, BX connectors are not acceptable |
#3
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
In article , "Ted" wrote:
I have already bought it, but am just curious. HD had 4 different box connectors. Cheap ones for NM, BX, and BX/AC, and an expensive one for MC. The electrical clerk recommended the NM, but that didn't seem right. It wasn't. Generally speaking, advice from clerks in HD, Lowes, etc. is worth exactly what you pay for it. I was tempted by the cheap BX clamps, but took the MC since I only needed two of them anyhow. Would code require the ones labeled MC, Yes. or would the BX have been adequate? No. If the BX clamps were adequate for use with MC, they'd be identified for use with MC. They're not, so they aren't. |
#4
![]()
Posted to alt.home.repair
|
|||
|
|||
![]()
The clamps marked NM is solely for romex, not BX, because if you
compare it to a BX clamp, there is a stop preventing the cable from going through. This is necessary on BX so the anti-short bushing (little red plastic at the end) will not fall out. If you use BX on an NM clamp, the anti-short bushing can fall out |