Default proper installation of double GFI receptacles in one box

I am doing a complete bathroom renovation. I wish to install two GFI
receptacles in a double box. The incomming wire is always hot and
goes no further than the box in question. As there is already one
existing GFI recptacle in place i can see how its wired. can i just
pigtale its white and the new ones white to the incomming white and
pigtale the current black and the new black to the incomming black
and common the grounds
  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 168
Default proper installation of double GFI receptacles in one box

wrote in message
...
I am doing a complete bathroom renovation. I wish to install two GFI
receptacles in a double box. The incomming wire is always hot and
goes no further than the box in question. As there is already one
existing GFI recptacle in place i can see how its wired. can i just
pigtale its white and the new ones white to the incomming white and
pigtale the current black and the new black to the incomming black
and common the grounds


Why not install a regular (non GFI) duplex receptacle downstream of the
existing GFI?


  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,934
Default proper installation of double GFI receptacles in one box


wrote in message
...
I am doing a complete bathroom renovation. I wish to install two GFI
receptacles in a double box. The incomming wire is always hot and
goes no further than the box in question. As there is already one
existing GFI recptacle in place i can see how its wired. can i just
pigtale its white and the new ones white to the incomming white and
pigtale the current black and the new black to the incomming black
and common the grounds




Yes or you can do as Peter suggested to save a little on the cost of an
additional GFI. Put your pigtail wires from the second receptacle into the
LOAD terminals on the first GFI. That will make the second receptacle GFI
protected. The current code calls for a separate 20 amp circuit for the
bathroom.

  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,353
Default proper installation of double GFI receptacles in one box


"John Grabowski" wrote in message
...

wrote in message
...
I am doing a complete bathroom renovation. I wish to install two GFI
receptacles in a double box. The incomming wire is always hot and
goes no further than the box in question. As there is already one
existing GFI recptacle in place i can see how its wired. can i just
pigtale its white and the new ones white to the incomming white and
pigtale the current black and the new black to the incomming black
and common the grounds




Yes or you can do as Peter suggested to save a little on the cost of an
additional GFI. Put your pigtail wires from the second receptacle into
the LOAD terminals on the first GFI. That will make the second receptacle
GFI protected. The current code calls for a separate 20 amp circuit for
the bathroom.


This is excellent advice but you will need to use the decora style duplex so
that you can find a 2 gang cover to fit.


--
Colbyt
Please come visit www.househomerepair.com


  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,563
Default proper installation of double GFI receptacles in one box


"Colbyt" wrote in message
news

"John Grabowski" wrote in message
...

wrote in message
...
I am doing a complete bathroom renovation. I wish to install two GFI
receptacles in a double box. The incomming wire is always hot and
goes no further than the box in question. As there is already one
existing GFI recptacle in place i can see how its wired. can i just
pigtale its white and the new ones white to the incomming white and
pigtale the current black and the new black to the incomming black
and common the grounds




Yes or you can do as Peter suggested to save a little on the cost of an
additional GFI. Put your pigtail wires from the second receptacle into
the LOAD terminals on the first GFI. That will make the second
receptacle GFI protected. The current code calls for a separate 20 amp
circuit for the bathroom.


This is excellent advice but you will need to use the decora style duplex
so that you can find a 2 gang cover to fit.


--
Colbyt
Please come visit www.househomerepair.com


They actually make two gang Decora/Duplex plates, although a two gang
Decora/Decora plate would look more attractive


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Proper GFCI installation dclutch Home Repair 7 January 11th 07 12:36 AM
Proper Installation of Corrugated Pipe for Drainage Purposes [email protected] Home Repair 6 August 21st 06 02:15 PM
proper window installation [email protected] Home Repair 9 September 22nd 05 05:16 PM
Proper Receptacles for 20 Amp Circuit Todd Home Repair 6 June 28th 05 06:07 PM
Gutters--Proper installation question Dave Combs Home Repair 11 June 18th 05 02:26 AM


All times are GMT +1. The time now is 06:31 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"