220 V wiring question
I recently inherited my dad's Delta/Rockwell Unisaw with a 220V
motor. The saw is a dream to use compared to my old Craftsman. Luckily my shop is wired for 220 but I have a wiring question... The wall plug is a 4 blade and the saw has a 3 blade plug so I need a new plug for the saw. I was going to just buy a new 4 blade male plug and replace the existing 3 blade on the saw. So do I wire the ground/common from the saw to the ground or to the common on the plug? I can't seem to figure out which is appropriate. Or should I just buy a length of 12/3 and use all 4 lugs? Does it matter? I assume if I did that all I would need to do is screw the ground to the saw frame somewhere... right? |
#2
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
LA wrote:
wrote: You have a 120/240 receptacle. Your saw is 240 only. The best option is to add another receptacle with the right configuration. You will have 2 hots and a ground, no white. If I understand your comment...the receptacle is a 220v only. There is no way to plug in a 120v line and it has a 40 amp breaker. So you are saying wire the "common/grround" from the saw to the ground on the receptacle... right? Thanks! I believe you have him backwards, the saw needs no neutral, since it does not use 110v for anything. The outlet has a neutral, so it has 110 available. You should be able to change the plug to one that will fit the outlet, ignoring the neutral. |
#3
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
LA wrote:
wrote: You have a 120/240 receptacle. Your saw is 240 only. The best option is to add another receptacle with the right configuration. You will have 2 hots and a ground, no white. If I understand your comment...the receptacle is a 220v only. There is no way to plug in a 120v line and it has a 40 amp breaker. No he wrote and was right that the receptacle is both 120 and 240 supply. You saw only can use the 240 part of that. Some things like an electric range will have 240 heating elements and maybe a 120 clock so they need both. You could replace the plug on the saw and you would not connect any wire to one of the connectors on the plug (the one that feeds the white wire, you would only connect the red black and copper-green or as he suggested and so do I, leave the plug as it is on the saw and replace the receptacle on the wall with one that will fit the existing plug designed for 220 only, you would not connect the white wire to any part of that receptacle. So you are saying wire the "common/grround" from the saw to the ground on the receptacle... right? The common and the ground are NOT the same thing. The only place the connect is in the breaker box any where else the white is a current carrying wire and should be treated as such, the ground is the only ground wire. Thanks! -- Joseph Meehan Dia duit |
#4
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
Ahhhh.... I understand. Thanks Joeseph |
#5
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
Backwards. The four hole socket (not a four hole plug) has 220 and 110
available. The cord to your saw is 220 only. -- Christopher A. Young You can't shout down a troll. You have to starve them. .. "LA" wrote in message oups.com... wrote: You have a 120/240 receptacle. Your saw is 240 only. The best option is to add another receptacle with the right configuration. You will have 2 hots and a ground, no white. If I understand your comment...the receptacle is a 220v only. There is no way to plug in a 120v line and it has a 40 amp breaker. So you are saying wire the "common/grround" from the saw to the ground on the receptacle... right? Thanks! |
#6
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
I'd be very surprised if there was a plug coming out of the wall.
Totally unsafe. Should be a socket. You can replace the plug on the saw if you wish. Won't hurt anything. -- Christopher A. Young You can't shout down a troll. You have to starve them. .. "LA" wrote in message oups.com... I recently inherited my dad's Delta/Rockwell Unisaw with a 220V motor. The saw is a dream to use compared to my old Craftsman. Luckily my shop is wired for 220 but I have a wiring question... The wall plug is a 4 blade and the saw has a 3 blade plug so I need a new plug for the saw. I was going to just buy a new 4 blade male plug and replace the existing 3 blade on the saw. So do I wire the ground/common from the saw to the ground or to the common on the plug? I can't seem to figure out which is appropriate. Or should I just buy a length of 12/3 and use all 4 lugs? Does it matter? I assume if I did that all I would need to do is screw the ground to the saw frame somewhere... right? |
#7
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
On Mon, 10 Jul 2006 19:34:11 GMT, "Joseph Meehan"
wrote: LA wrote: wrote: You have a 120/240 receptacle. Your saw is 240 only. The best option is to add another receptacle with the right configuration. You will have 2 hots and a ground, no white. If I understand your comment...the receptacle is a 220v only. There is no way to plug in a 120v line and it has a 40 amp breaker. No he wrote and was right that the receptacle is both 120 and 240 supply. You saw only can use the 240 part of that. Some things like an electric range will have 240 heating elements and maybe a 120 clock so they need both. You could replace the plug on the saw and you would not connect any wire to one of the connectors on the plug (the one that feeds the white wire, you would only connect the red black and copper-green or as he suggested and so do I, leave the plug as it is on the saw and replace the receptacle on the wall with one that will fit the existing plug designed for 220 only, you would not connect the white wire to any part of that receptacle. So you are saying wire the "common/grround" from the saw to the ground on the receptacle... right? The common and the ground are NOT the same thing. The only place the connect is in the breaker box any where else the white is a current carrying wire and should be treated as such, the ground is the only ground wire. Sometimes they're connected together (often in 240V 3-wire cords). Thanks! -- Mark Lloyd http://notstupid.laughingsquid.com "Democracy is two wolves and a lamb voting on what to have for lunch. Liberty is a well armed lamb contesting the vote." - Benjamin Franklin |
#8
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
On Mon, 10 Jul 2006 21:17:11 GMT, "Stormin Mormon"
wrote: I'd be very surprised if there was a plug coming out of the wall. Totally unsafe. Should be a socket. A lot of people get their gender mixed up BTW, I know someone who wanted a "double male adapter" for 120V (after having put up some holiday lights wrong). That's a socket connected to 2 plugs. You can replace the plug on the saw if you wish. Won't hurt anything. -- Mark Lloyd http://notstupid.laughingsquid.com "Democracy is two wolves and a lamb voting on what to have for lunch. Liberty is a well armed lamb contesting the vote." - Benjamin Franklin |
#9
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
I'd be very surprised if there was a plug coming out of the wall. Totally unsafe. Should be a socket. A lot of people get their gender mixed up BTW, I know someone who wanted a "double male adapter" for 120V (after having put up some holiday lights wrong). That's a socket connected to 2 plugs. LOL... Yes... I have a "socket" in the wall. I had a new shop built on and it was wired for 220 by a professional. I'm just an amateur trying to figure out how to plug in my saw... Thanks all... I think you straightened me out and I know what to do next. I appreciate the help! |
#10
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
LA wrote: .... Yes... I have a "socket" in the wall. I had a new shop built on and it was wired for 220 by a professional. I'm just an amateur trying to figure out how to plug in my saw... Thanks all... I think you straightened me out and I know what to do next. Well, you left me _very_ cornpuzzled... A 4-hole wall outlet isn't what you want for a shop--that's for something like a range or a clothes dryer. What you really should do to do it correctly (but you don't say what you think it is you think you know ) is get the proper socket for the wall to match the saw and that matches the breaker amperage of the circuit you're going to use. That is, don't use a 220V/15A rated outlet in a 20A-protected circuit. The other way 'round is fine, (20A outlet on a 15A circuit). While it would function to put a plug on the saw to match the existing outlet, why butcher a tool to a non-standard configuration when it's just as simple to put the correct outlet in the wall? Plus, if you're making a shop, you should standardize on a particular outlet choice simply for future convenience. IMO, YMMV, $0.02, etc., ... |
#11
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
Use a four prong plug on your existing cord. Just use the two hots and the
ground, no need for a neutral. "LA" wrote in message oups.com... I recently inherited my dad's Delta/Rockwell Unisaw with a 220V motor. The saw is a dream to use compared to my old Craftsman. Luckily my shop is wired for 220 but I have a wiring question... The wall plug is a 4 blade and the saw has a 3 blade plug so I need a new plug for the saw. I was going to just buy a new 4 blade male plug and replace the existing 3 blade on the saw. So do I wire the ground/common from the saw to the ground or to the common on the plug? I can't seem to figure out which is appropriate. Or should I just buy a length of 12/3 and use all 4 lugs? Does it matter? I assume if I did that all I would need to do is screw the ground to the saw frame somewhere... right? |
#12
Posted to alt.home.repair
|
|||
|
|||
220 V wiring question
According to Jeff :
Use a four prong plug on your existing cord. Just use the two hots and the ground, no need for a neutral. It's probably a trifle cheaper and somewhat easier (aside from having to kill the breaker) to change around the receptacle on the wall than the plug on the cord. Retrofit 220V plugs are clunky things. I'd prefer to leave a molded cordset alone (if that's what the saw has), and do my changes with solid copper. Presuming of course that the thing isn't over-breakered for the receptacle that matches the saw plug. -- Chris Lewis, Una confibula non set est It's not just anyone who gets a Starship Cruiser class named after them. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Circuit Breaker Wiring Question ? | Home Repair | |||
Cooker element wiring question (and LPG deconversion as well) Diplomat APD5701 | UK diy | |||
Programmable Thermostat wiring question -rth7500 | Home Repair | |||
230V 15A wiring question. | Home Ownership | |||
circuit wiring question | Home Repair |