Default Electrical Conduit Depth?

I need to run an electrical circuit out of my house to my pool's
filter. I plan on using a 1.5" Electrical PVC conduit for this run.
I've read many conflicting posts on the depth of this conduit. Many say
18" but other claim I can go shallower...12" if it's 120V single
circuit 15-20amps and GFCI at the house (which is what it is). The
reason I'm asking is that I want to run this conduit along side a wall
that has geogrid at about 14" below the surface. I cannot break this
material since it's required for this retaining wall. What are my
options?

Any comments will be greatly appreciated.

PS: I will be having a licensed electrician to do the job but want to
know my options before I get to that stage.

  #2   Report Post  
Posted to alt.home.repair
John Grabowski
 
Posts: n/a
Default Electrical Conduit Depth?


wrote in message
oups.com...
I need to run an electrical circuit out of my house to my pool's
filter. I plan on using a 1.5" Electrical PVC conduit for this run.
I've read many conflicting posts on the depth of this conduit. Many say
18" but other claim I can go shallower...12" if it's 120V single
circuit 15-20amps and GFCI at the house (which is what it is). The
reason I'm asking is that I want to run this conduit along side a wall
that has geogrid at about 14" below the surface. I cannot break this
material since it's required for this retaining wall. What are my
options?

Any comments will be greatly appreciated.

PS: I will be having a licensed electrician to do the job but want to
know my options before I get to that stage.


18" for PVC is correct with a dirt covering. You can go 12" if the 120 volt
20 amp circuit is GFCI protected, however I usually avoid that alternative.
The GFCI would be protecting the entire line and will be more prone to
nuisance tripping from moisture. As an alternative you can use galvanized
rigid conduit and only need to go down 6".

Incidentally, 1.5" is a very big conduit for a 20 amp circuit. Why do you
plan to use such a big pipe? Half inch or three quarter should suffice.

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Can't Get PC 690 Cut Depth Adjustment Ring to Work Morris Dovey Woodworking 0 December 7th 05 09:28 PM
Electrical Wiring FAQ (Part 1 of 2) Myron Samila Home Repair 1 March 15th 04 07:27 PM
Electrical inspector makes up new rules during inspection zxcvbob Home Repair 22 March 12th 04 04:54 PM
Forthcoming Building Regulations on electrical work (Part P) Andrew McKay UK diy 42 July 30th 03 08:05 AM
Routeing Electrical FTE cable pickerel UK diy 3 July 24th 03 12:43 AM


All times are GMT +1. The time now is 12:09 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"