Default Electrical Wiring - Basic or ?

I've just come across about 3 or 4 wall outlets in my parent's home that are
of the style that will only receive a male plug of 2 prongs. What is
involved in replacing the box innards with the receptacle that will take the
male plug of 3 prongs (2 plus the third below and in the middle)? My
recollection from school days is that the major difference is the addition
of a ground wire to a screw in the middle of the receptacle. Or, am I
thinking of something altogether different. The rest of their house has the
3 prong receptacles so this really is a bit of a mystery.

Charlie.


  #2   Report Post  
 
Posts: n/a
Default

this is very common in homes built during the 50's and early 60's. the
actual wire is 3 conductor, however, the 'electricians' back then did not
fully understand the concept of alternate grounding. often, the ground wire
was cut, left coiled in the box and generally ignored as old stocks of 2
prong outlets got used up. dad told me that grounded outlets cost ten cents
and ungrounded were six.
Remember too that most builders back then were postmen, government clerks,
etc., that moonlighted as homebuilders when the need arose.
"Charlie" wrote in message
news:x6xhe.1354018$Xk.800039@pd7tw3no...
I've just come across about 3 or 4 wall outlets in my parent's home that

are
of the style that will only receive a male plug of 2 prongs. What is
involved in replacing the box innards with the receptacle that will take

the
male plug of 3 prongs (2 plus the third below and in the middle)? My
recollection from school days is that the major difference is the addition
of a ground wire to a screw in the middle of the receptacle. Or, am I
thinking of something altogether different. The rest of their house has

the
3 prong receptacles so this really is a bit of a mystery.

Charlie.




  #3   Report Post  
Doug Miller
 
Posts: n/a
Default

In article x6xhe.1354018$Xk.800039@pd7tw3no, "Charlie" wrote:
I've just come across about 3 or 4 wall outlets in my parent's home that are
of the style that will only receive a male plug of 2 prongs. What is
involved in replacing the box innards with the receptacle that will take the
male plug of 3 prongs (2 plus the third below and in the middle)? My
recollection from school days is that the major difference is the addition
of a ground wire to a screw in the middle of the receptacle. Or, am I
thinking of something altogether different. The rest of their house has the
3 prong receptacles so this really is a bit of a mystery.


If the cable supplying the receptacles has three conductors (two insulated and
one bare), you're home free: just install 3-prong (grounded) receptacles as
follows:
- black wire to gold-colored screw terminal
- white wire to silver-colored screw terminal
- bare wire to green screw terminal
and you're done.

If the cable has only two conductors (both insulated), you have two choices:

1) Leave them alone. They work. The only problem is, you can't plug a grounded
device into them.

2) Replace them with ground-fault circuit interrupter receptacles. You will
need one GFCI per circuit, installed in the location that is *electrically*
nearest the breaker box, and connected so as to protect the remainder of the
circuit (full instructions are included with the GFCI). Other 2-prong
receptacles on that circuit can be replaced with 3-prong receptacles wired as
I described above, except that you don't connect the ground wire (since there
isn't one). *** NOTE *** All of the receptacles, including the GFCI, must then
be marked "No Equipment Ground" using the sticky labels that come inside the
package with the GFCI.

--
Regards,
Doug Miller (alphageek at milmac dot com)

Nobody ever left footprints in the sands of time by sitting on his butt.
And who wants to leave buttprints in the sands of time?
  #4   Report Post  
Backlash
 
Posts: n/a
Default


"Doug Miller" wrote in message
...
If the cable supplying the receptacles has three conductors (two insulated
and
one bare), you're home free: just install 3-prong (grounded) receptacles
as
follows:
- black wire to gold-colored screw terminal
- white wire to silver-colored screw terminal
- bare wire to green screw terminal
and you're done.


He's not done, is he, until he checks to make sure that the other end of the
bare wire(s) is attached to the proper place in the panel, and is actually
acting as it should? You never know what someone has done ahead of you. An
$8 circuit tester to check all the receptacles in the house might be smart,
just to see if they are wired correctly. It's a cheap, self-empowering
investment. They are also handy just to see if a circuit is live.

RJ


  #5   Report Post  
Doug Miller
 
Posts: n/a
Default

In article , "Backlash" wrote:

"Doug Miller" wrote in message
m...
If the cable supplying the receptacles has three conductors (two insulated
and
one bare), you're home free: just install 3-prong (grounded) receptacles
as
follows:
- black wire to gold-colored screw terminal
- white wire to silver-colored screw terminal
- bare wire to green screw terminal
and you're done.


He's not done, is he, until he checks to make sure that the other end of the
bare wire(s) is attached to the proper place in the panel, and is actually
acting as it should? You never know what someone has done ahead of you. An
$8 circuit tester to check all the receptacles in the house might be smart,
just to see if they are wired correctly. It's a cheap, self-empowering
investment. They are also handy just to see if a circuit is live.


Point well taken.

--
Regards,
Doug Miller (alphageek at milmac dot com)

Nobody ever left footprints in the sands of time by sitting on his butt.
And who wants to leave buttprints in the sands of time?


  #6   Report Post  
Charlie
 
Posts: n/a
Default


"Doug Miller" wrote in message
...
In article x6xhe.1354018$Xk.800039@pd7tw3no, "Charlie"
wrote:
I've just come across about 3 or 4 wall outlets in my parent's home that
are
of the style that will only receive a male plug of 2 prongs. What is
involved in replacing the box innards with the receptacle that will take
the
male plug of 3 prongs (2 plus the third below and in the middle)? My
recollection from school days is that the major difference is the addition
of a ground wire to a screw in the middle of the receptacle. Or, am I
thinking of something altogether different. The rest of their house has
the
3 prong receptacles so this really is a bit of a mystery.


If the cable supplying the receptacles has three conductors (two insulated
and
one bare), you're home free: just install 3-prong (grounded) receptacles
as
follows:
- black wire to gold-colored screw terminal
- white wire to silver-colored screw terminal
- bare wire to green screw terminal
and you're done.


Many thanks. Each of the 4 boxes had the 3 conductors so it just took me
about an hour or so to replace the innards.

Charlie.


If the cable has only two conductors (both insulated), you have two
choices:

1) Leave them alone. They work. The only problem is, you can't plug a
grounded
device into them.

2) Replace them with ground-fault circuit interrupter receptacles. You
will
need one GFCI per circuit, installed in the location that is
*electrically*
nearest the breaker box, and connected so as to protect the remainder of
the
circuit (full instructions are included with the GFCI). Other 2-prong
receptacles on that circuit can be replaced with 3-prong receptacles wired
as
I described above, except that you don't connect the ground wire (since
there
isn't one). *** NOTE *** All of the receptacles, including the GFCI, must
then
be marked "No Equipment Ground" using the sticky labels that come inside
the
package with the GFCI.

--
Regards,
Doug Miller (alphageek at milmac dot com)

Nobody ever left footprints in the sands of time by sitting on his butt.
And who wants to leave buttprints in the sands of time?



Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Wiring an electrical shower NotMe UK diy 11 March 30th 05 04:31 PM
Wiring "new" electrical circuit Tim Wentworth Home Repair 33 December 18th 03 12:46 AM
Electrical wiring inspector? phil UK diy 14 November 25th 03 12:54 AM
Proposed Part P Building Regulations (Electrical Wiring) Andy Hall UK diy 5 September 10th 03 02:07 AM
Electrical Wiring Grouping Factors in IEE Regs pickerel UK diy 5 July 14th 03 01:26 AM


All times are GMT +1. The time now is 05:27 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"