Default Ariston Combi problem

Anybody know what the pressure gauge on an Ariston Combi should read?
Son has just bought his first house and the boiler gauge is at 3 bar and
the water constantly drips from the overflow / expansion pipe when
running. Also the fill loop valve appears to be constantly open.
I am guessing the gauge should read between 0.5 and 1.5 bar, but it is
only a guess.
Many thanks


--
Posted via Mailgate.ORG Server - http://www.Mailgate.ORG
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4,046
Default Ariston Combi problem


"Grumpy owd man" wrote in message
news:52fcddbfd32ca97c42e2689eb3b1cbf3.115311@mygat e.mailgate.org...
Anybody know what the pressure gauge on an Ariston Combi should read?
Son has just bought his first house and the boiler gauge is at 3 bar and
the water constantly drips from the overflow / expansion pipe when
running. Also the fill loop valve appears to be constantly open.
I am guessing the gauge should read between 0.5 and 1.5 bar, but it is
only a guess.
Many thanks


0.5 and 1 bar when cold. If the valve drips even when cold replace it. If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.

  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 51
Default Ariston Combi problem


0.5 and 1 bar when cold. If the valve drips even when cold replace it. If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.



Ah!, I have not really explained it very well.
the water is coming from a pipe which runs to the outside of the
property if this make any difference. The drip is not internal



--
Posted via Mailgate.ORG Server - http://www.Mailgate.ORG
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4,046
Default Ariston Combi problem


"Grumpy owd man" wrote in message
news:3c270227b3833fa7756c53109fec9676.115311@mygat e.mailgate.org...

0.5 and 1 bar when cold. If the valve drips even when cold replace it.
If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.



Ah!, I have not really explained it very well.
the water is coming from a pipe which runs to the outside of the
property if this make any difference. The drip is not internal


Exactly. It is the pressure relief valve which is piped to outside. You will
know if the diaphragm is holed as water comes out of the shrader valve.

  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3
Default Ariston Combi problem

"Doctor Drivel" wrote in message
reenews.net


Many thanks, i will have a look tomorrow



--
Posted via Mailgate.ORG Server - http://www.Mailgate.ORG


  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,466
Default Ariston Combi problem

In message
ilgate.org, Grumpy
owd man writes

0.5 and 1 bar when cold. If the valve drips even when cold replace it. If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.



Ah!, I have not really explained it very well.
the water is coming from a pipe which runs to the outside of the
property if this make any difference. The drip is not internal

Pressure relief valve leaking ?

find it, open it so it gives a good squirt

there might be some crud which is preventing it from seating properly

else, it's a drain down and replace it


--
geoff
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
ferroli combi pressure problem senga UK diy 3 August 11th 06 10:13 PM
Water flow rate problem and Combi boiler Andrew Beck UK diy 15 September 3rd 04 11:00 PM
Ariston Microgenus 23 combi boiler Lawrence Raybould UK diy 3 January 7th 04 09:35 PM
Ariston STYX Combi boiler problems Sharma UK diy 5 July 15th 03 11:15 PM
Ariston euro combi problem BigWallop UK diy 0 July 3rd 03 11:21 PM


All times are GMT +1. The time now is 05:01 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"