Grumpy owd man November 19th 06 10:54 AM

Ariston Combi problem
 
Anybody know what the pressure gauge on an Ariston Combi should read?
Son has just bought his first house and the boiler gauge is at 3 bar and
the water constantly drips from the overflow / expansion pipe when
running. Also the fill loop valve appears to be constantly open.
I am guessing the gauge should read between 0.5 and 1.5 bar, but it is
only a guess.
Many thanks


--
Posted via Mailgate.ORG Server - http://www.Mailgate.ORG

Doctor Drivel November 19th 06 02:10 PM

Ariston Combi problem
 

"Grumpy owd man" wrote in message
news:52fcddbfd32ca97c42e2689eb3b1cbf3.115311@mygat e.mailgate.org...
Anybody know what the pressure gauge on an Ariston Combi should read?
Son has just bought his first house and the boiler gauge is at 3 bar and
the water constantly drips from the overflow / expansion pipe when
running. Also the fill loop valve appears to be constantly open.
I am guessing the gauge should read between 0.5 and 1.5 bar, but it is
only a guess.
Many thanks


0.5 and 1 bar when cold. If the valve drips even when cold replace it. If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.


Grumpy owd man November 19th 06 02:47 PM

Ariston Combi problem
 

0.5 and 1 bar when cold. If the valve drips even when cold replace it. If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.



Ah!, I have not really explained it very well.
the water is coming from a pipe which runs to the outside of the
property if this make any difference. The drip is not internal



--
Posted via Mailgate.ORG Server - http://www.Mailgate.ORG

Doctor Drivel November 19th 06 02:59 PM

Ariston Combi problem
 

"Grumpy owd man" wrote in message
news:3c270227b3833fa7756c53109fec9676.115311@mygat e.mailgate.org...

0.5 and 1 bar when cold. If the valve drips even when cold replace it.
If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.



Ah!, I have not really explained it very well.
the water is coming from a pipe which runs to the outside of the
property if this make any difference. The drip is not internal


Exactly. It is the pressure relief valve which is piped to outside. You will
know if the diaphragm is holed as water comes out of the shrader valve.


Clive Dive November 19th 06 03:18 PM

Ariston Combi problem
 
"Doctor Drivel" wrote in message
reenews.net


Many thanks, i will have a look tomorrow



--
Posted via Mailgate.ORG Server - http://www.Mailgate.ORG

raden November 19th 06 09:36 PM

Ariston Combi problem
 
In message
ilgate.org, Grumpy
owd man writes

0.5 and 1 bar when cold. If the valve drips even when cold replace it. If
it drips when hot then check the pressure vessel pressure or if the
diaphragm is holed replace it.



Ah!, I have not really explained it very well.
the water is coming from a pipe which runs to the outside of the
property if this make any difference. The drip is not internal

Pressure relief valve leaking ?

find it, open it so it gives a good squirt

there might be some crud which is preventing it from seating properly

else, it's a drain down and replace it


--
geoff