  #1   Report Post  
Posted to rec.woodworking
external usenet poster
 
Posts: 425
Default Is it appropriate to mount this type of fan under existing roof vents?

I am going to install a whole house fan to exhaust hot air out of the rooms
on the top floor , and while I'm at it I'm thinking of installing fan(s),
most likely one (1). in the roof itself to exhaust the air right out from
over the ceiling of those rooms. Get it out of the rooms, into that upper
area; then why not right out of that area, a hot box.

I have looked into the packaging of one of these fans at HomeDepot. Its
just a 15"! (x6"?) circular shroud, and it is to be mounted anywhere- theres
no flush mounting or anything, just some metal clips. The pic in the manual
shows it mounted so it is blowing Horizontally - out of a louver vent
mounted on the front of an "attic" - above the ceiling & below the roof, at
the front of the pictured house.

I am thinking I would want to mount a fan under the existing vents on the
roof, pointing up and out these vents. I do not want to screw around with
the shingles outside. I've got 2 of the std. size approx 12"x12" vents,
with screen inside. These vents are only about 7' apart, on adjacent parts
of the roof, at the rear. The foof is about 10' x 20'. I am thinking of
wiring a switch inside, beside the whole house fan switch (maybe pull
cord?), and using metallic shielded cable.

Can I use this type of fan, mount it just below the vent(s) facing up?
Will I need to worry about a seal to the vent to create a push vacuum?
Do I need to worry about the size(s)/cfm carefully of the fan(s) wrt the
whole house fan?
Theres soffit venting 360, and 2 vents, need I cover (and seal) both (2)
vents with fans?

http://www.homedepot.com/webapp/wcs/...ctId=100055092
the "interior roof" fan

http://www.homedepot.com/webapp/wcs/...y=THDSiteMa p
the whole house fan



----== Posted via Newsfeeds.Com - Unlimited-Unrestricted-Secure Usenet News==----
http://www.newsfeeds.com The #1 Newsgroup Service in the World! 120,000+ Newsgroups
----= East and West-Coast Server Farms - Total Privacy via Encryption =----
  #2   Report Post  
Posted to rec.woodworking
external usenet poster
 
Posts: 425
Default Is it appropriate to mount this type of fan under existing roof vents?

whoops, sorry, this goes in a.b.c & a.h.r



----== Posted via Newsfeeds.Com - Unlimited-Unrestricted-Secure Usenet News==----
http://www.newsfeeds.com The #1 Newsgroup Service in the World! 120,000+ Newsgroups
----= East and West-Coast Server Farms - Total Privacy via Encryption =----
  #3   Report Post  
Posted to rec.woodworking
external usenet poster
 
Posts: 510
Default Is it appropriate to mount this type of fan under existing roof vents?

On Jun 26, 2:03 pm, "bent" wrote:
I am going to install a whole house fan to exhaust hot air out of the rooms
on the top floor , and while I'm at it I'm thinking of installing fan(s),
most likely one (1). in the roof itself to exhaust the air right out from
over the ceiling of those rooms. Get it out of the rooms, into that upper
area; then why not right out of that area, a hot box.

I have looked into the packaging of one of these fans at HomeDepot. Its
just a 15"! (x6"?) circular shroud, and it is to be mounted anywhere- theres
no flush mounting or anything, just some metal clips. The pic in the manual
shows it mounted so it is blowing Horizontally - out of a louver vent
mounted on the front of an "attic" - above the ceiling & below the roof, at
the front of the pictured house.

I am thinking I would want to mount a fan under the existing vents on the
roof, pointing up and out these vents. I do not want to screw around with
the shingles outside. I've got 2 of the std. size approx 12"x12" vents,
with screen inside. These vents are only about 7' apart, on adjacent parts
of the roof, at the rear. The foof is about 10' x 20'. I am thinking of
wiring a switch inside, beside the whole house fan switch (maybe pull
cord?), and using metallic shielded cable.

Can I use this type of fan, mount it just below the vent(s) facing up?
Will I need to worry about a seal to the vent to create a push vacuum?
Do I need to worry about the size(s)/cfm carefully of the fan(s) wrt the
whole house fan?


NO. Soffit vents are necesssary. The one fan you choose is a gable
mounted fan. These are used in conjunction with your soffit vents.
Basic venting depends upon convection to draw cooler air through the
soffit venting. A Ridge Vent is typically the most efficient approach
as it vents through the highest point(s) in the structure.

The House fan is designed to pull cool air through the windows, scree
door(s) etc. venting it into the attic where it should exit via
existing roof vents. However, if the square footage of the existing
vents is insufficient, the effectiveness of the House Fan will be
similarly diminished.

There may be a formula somewhere that will give you the minimum sf of
venting required in soffitts and in roof for basic convection venting.
I would suspect that forcing air into the space might well reuire an
incrase in the roof venting to handle the increase flows of air.

I have four 6" passive vents mounted (previous owner) and find he
house fan forces air out through the Soffitt vents - because, I
assume, I need larger (or more) roof venting. I willl install a ridge
vent when we re-roof and have two powered roof vents (thermostatically
controlled) to install in each gable end as well.

Good Luck
Theres soffit venting 360, and 2 vents, need I cover (and seal) both (2)
vents with fans?

http://www.homedepot.com/webapp/wcs/...uctDisplay?sto...
the "interior roof" fan

http://www.homedepot.com/webapp/wcs/...uctDisplay?id=...
the whole house fan

----== Posted via Newsfeeds.Com - Unlimited-Unrestricted-Secure Usenet News==----http://www.newsfeeds.comThe #1 Newsgroup Service in the World! 120,000+ Newsgroups
----= East and West-Coast Server Farms - Total Privacy via Encryption =----



  #4   Report Post  
Posted to rec.woodworking
tim tim is offline
external usenet poster
 
Posts: 2
Default Is it appropriate to mount this type of fan under existing roofvents?

I am building a 12' x 20' workshop, and as soon as I put the roof on
(gable), I could tell that it is going to get very hot in there when it
is closed up.
I don't want any windows, to increase wall space for storage, but have
double doors that I will keep open when I work, as well as my dust system.
I have installed an automatic venting gable fan on one end of the
building, and my question is, should I put a vent in the opposite side
of the ceiling, or somewhere on the base of the walls?

Thanks,
Tim



Hoosierpopi wrote:
On Jun 26, 2:03 pm, "bent" wrote:
I am going to install a whole house fan to exhaust hot air out of the rooms
on the top floor , and while I'm at it I'm thinking of installing fan(s),
most likely one (1). in the roof itself to exhaust the air right out from
over the ceiling of those rooms. Get it out of the rooms, into that upper
area; then why not right out of that area, a hot box.

I have looked into the packaging of one of these fans at HomeDepot. Its
just a 15"! (x6"?) circular shroud, and it is to be mounted anywhere- theres
no flush mounting or anything, just some metal clips. The pic in the manual
shows it mounted so it is blowing Horizontally - out of a louver vent
mounted on the front of an "attic" - above the ceiling & below the roof, at
the front of the pictured house.

I am thinking I would want to mount a fan under the existing vents on the
roof, pointing up and out these vents. I do not want to screw around with
the shingles outside. I've got 2 of the std. size approx 12"x12" vents,
with screen inside. These vents are only about 7' apart, on adjacent parts
of the roof, at the rear. The foof is about 10' x 20'. I am thinking of
wiring a switch inside, beside the whole house fan switch (maybe pull
cord?), and using metallic shielded cable.

Can I use this type of fan, mount it just below the vent(s) facing up?
Will I need to worry about a seal to the vent to create a push vacuum?
Do I need to worry about the size(s)/cfm carefully of the fan(s) wrt the
whole house fan?


NO. Soffit vents are necesssary. The one fan you choose is a gable
mounted fan. These are used in conjunction with your soffit vents.
Basic venting depends upon convection to draw cooler air through the
soffit venting. A Ridge Vent is typically the most efficient approach
as it vents through the highest point(s) in the structure.

The House fan is designed to pull cool air through the windows, scree
door(s) etc. venting it into the attic where it should exit via
existing roof vents. However, if the square footage of the existing
vents is insufficient, the effectiveness of the House Fan will be
similarly diminished.

There may be a formula somewhere that will give you the minimum sf of
venting required in soffitts and in roof for basic convection venting.
I would suspect that forcing air into the space might well reuire an
incrase in the roof venting to handle the increase flows of air.

I have four 6" passive vents mounted (previous owner) and find he
house fan forces air out through the Soffitt vents - because, I
assume, I need larger (or more) roof venting. I willl install a ridge
vent when we re-roof and have two powered roof vents (thermostatically
controlled) to install in each gable end as well.

Good Luck
Theres soffit venting 360, and 2 vents, need I cover (and seal) both (2)
vents with fans?

http://www.homedepot.com/webapp/wcs/...uctDisplay?sto...
the "interior roof" fan

http://www.homedepot.com/webapp/wcs/...uctDisplay?id=...
the whole house fan

----== Posted via Newsfeeds.Com - Unlimited-Unrestricted-Secure Usenet News==----http://www.newsfeeds.comThe #1 Newsgroup Service in the World! 120,000+ Newsgroups
----= East and West-Coast Server Farms - Total Privacy via Encryption =----



Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Should vinyl siding vents line up with the existing vents? Terry Home Repair 3 December 21st 06 03:57 AM
FS: UG-58A/U Type N Panel Mount Connector AAA RF Products Electronics Repair 0 May 25th 06 05:02 PM
New roof jacks in existing asphalt shingle roof [email protected] Home Repair 1 March 12th 06 05:38 PM
No soffit vents, no roof or ridge vents. How do I finish my attic?? Yank_fan_2965 Home Repair 9 December 31st 05 05:37 AM