Soil plumbing
The chalet bungalow upstairs bathroom.
Are there likely to be any issues with arranging a short 45 deg. fall in the toilet waste pipe? The current plan is a vertical outfall terminated at a manifold above the soffit. There is insufficient space to get this high enough to accept a full *horizontal* run. Probably 2m level, 45 deg. bend, 800mm and another 45 deg. to the manifold. I will arrange a vented (AAV) stack inboard to be higher than the basin overflow. -- Tim Lamb |
#2
Posted to uk.d-i-y
|
|||
|
|||
Soil plumbing
On 07/08/2018 08:47, Tim Lamb wrote:
The chalet bungalow upstairs bathroom. Are there likely to be any issues with arranging a short 45 deg. fall in the toilet waste pipe? Generally best of you can do it near the source end, but usually ok so long as most of the run is within the recommended falls (typically between 1 in 10 and 1 in 80 for 110mm soil pipe). Its quite common to need a little bit of pipe height adjustment near soil stacks for example. The current plan is a vertical outfall terminated at a manifold above the soffit. There is insufficient space to get this high enough to accept a full *horizontal* run. Probably 2m level, 45 deg. bend, 800mm and another 45 deg. to the manifold. I will arrange a vented (AAV) stack inboard to be higher than the basin overflow. -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ |
#3
Posted to uk.d-i-y
|
|||
|
|||
Soil plumbing
In message , John
Rumm writes On 07/08/2018 08:47, Tim Lamb wrote: The chalet bungalow upstairs bathroom. Are there likely to be any issues with arranging a short 45 deg. fall in the toilet waste pipe? Generally best of you can do it near the source end, but usually ok so long as most of the run is within the recommended falls (typically between 1 in 10 and 1 in 80 for 110mm soil pipe). Its quite common to need a little bit of pipe height adjustment near soil stacks for example. The current plan is a vertical outfall terminated at a manifold above the soffit. There is insufficient space to get this high enough to accept a full *horizontal* run. Probably 2m level, 45 deg. bend, 800mm and another 45 deg. to the manifold. I will arrange a vented (AAV) stack inboard to be higher than the basin overflow. OK. Sadly the basin waste can't conveniently be used as a flush. -- Tim Lamb |
#4
Posted to uk.d-i-y
|
|||
|
|||
Soil plumbing
"Tim Lamb" wrote in message ... The chalet bungalow upstairs bathroom. Are there likely to be any issues with arranging a short 45 deg. fall in the toilet waste pipe? The current plan is a vertical outfall terminated at a manifold above the soffit. There is insufficient space to get this high enough to accept a full *horizontal* run. Probably 2m level, 45 deg. bend, 800mm and another 45 deg. to the manifold. the water will leave the solids behind...... I will arrange a vented (AAV) stack inboard to be higher than the basin overflow. that is going to be noisey ....... |
#5
Posted to uk.d-i-y
|
|||
|
|||
Soil plumbing
On 07/08/2018 08:47, Tim Lamb wrote:
The chalet bungalow upstairs bathroom. Are there likely to be any issues with arranging a short 45 deg. fall in the toilet waste pipe? The current plan is a vertical outfall terminated at a manifold above the soffit. There is insufficient space to get this high enough to accept a full *horizontal* run. Probably 2m level, 45 deg. bend, 800mm and another 45 deg. to the manifold. Our second toilet exits through the wall, turns 90° and then immediately descends at 45° for about 800mm, before changing again to a normal "horizontal" run. There was no choice, as there was a window half-way down the stairs, between the toilet and the stack, preventing a straight run. It has worked fine for 9 years now, but from the outside, it is quite a bit noisier than the pipe from the other toilet. SteveW |
#6
Posted to uk.d-i-y
|
|||
|
|||
Soil plumbing
In message , Steve Walker
writes On 07/08/2018 08:47, Tim Lamb wrote: The chalet bungalow upstairs bathroom. Are there likely to be any issues with arranging a short 45 deg. fall in the toilet waste pipe? The current plan is a vertical outfall terminated at a manifold above the soffit. There is insufficient space to get this high enough to accept a full *horizontal* run. Probably 2m level, 45 deg. bend, 800mm and another 45 deg. to the manifold. Our second toilet exits through the wall, turns 90° and then immediately descends at 45° for about 800mm, before changing again to a normal "horizontal" run. There was no choice, as there was a window half-way down the stairs, between the toilet and the stack, preventing a straight run. It has worked fine for 9 years now, but from the outside, it is quite a bit noisier than the pipe from the other toilet. Hmm.. I'll let you know how I get on:-) -- Tim Lamb |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Fertilizing rocky soil where it's half soil half stones (and no dirt) | Home Repair | |||
Help: Soil Connection Options for Under Stairs Macerator (Soil Stack/ Manhole) | UK diy | |||
plumbing - soil waste | UK diy | |||
Plumbing wash m/c into main soil pipe? | UK diy | |||
Leak at plastic soil pipe to clay soil pipe join | UK diy |