  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3
Default Hot water but no central heating

Hi all im Tony and are new to this site
I hope some one can help me with this problem if I turn my programmer to
hot water boiler will fire up diverted will open and i get hot water
however if i ask for C/H and no hot water boiler no longer fires up this
been my problem
any advise would be welcome

--


  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 5,774
Default Hot water but no central heating

On 23/12/2014 00:44, TONY wrote:
Hi all im Tony and are new to this site
I hope some one can help me with this problem if I turn my programmer to
hot water boiler will fire up diverted will open and i get hot water
however if i ask for C/H and no hot water boiler no longer fires up this
been my problem
any advise would be welcome



Room thermostat set too low?
Wireless room thermostat battery failing?

--
mailto: news {at} admac {dot] myzen {dot} co {dot} uk
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 25,191
Default Hot water but no central heating

On 23/12/2014 00:44, TONY wrote:
Hi all im Tony and are new to this site
I hope some one can help me with this problem if I turn my programmer to
hot water boiler will fire up diverted will open and i get hot water
however if i ask for C/H and no hot water boiler no longer fires up this
been my problem
any advise would be welcome


What kind of boiler is it? conventional heating boiler with separate hot
water cylinder, or a combination boiler that uses no tank and heats
water on demand?

Based on what you have said so far, it could be the room stat not
working, or perhaps a valve not moving correctly.

You can read about the various ways in which these things can be
configured he

http://wiki.diyfaq.org.uk/index.php?...s_and_Zonin g



--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3
Default Hot water but no central heating

replying to alan_m , TONY wrote:
junk wrote:

Room thermostat set too low?
Wireless room thermostat battery failing?
--
mailto: news admac {dot] myzen co uk


Hi There
thanks for the response I have checked room stat and turned it up to full,
boiler still not firing up ???
I think the problem might be the programmer not communicating to the
boiler
or a fault in the micro switch in the boiler will check it out tomorrow
thanks Tony


--


  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3
Default Hot water but no central heating

replying to John Rumm , TONY wrote:
see.my.signature wrote:

What kind of boiler is it? conventional heating boiler with separate hot
water cylinder, or a combination boiler that uses no tank and heats
water on demand?
Based on what you have said so far, it could be the room stat not
working, or perhaps a valve not moving correctly.
You can read about the various ways in which these things can be
configured he

http://wiki.diyfaq.org.uk/index.php?...s_and_Zonin g
--
Cheers,
John.
/================================================== ===============
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
================================================== ===============/

Hi John
Thanks for the reply the boiler is a glow-worm flexicom system boiler
its on a S plan
i have checked the valves and they seem to be working ok and so dose the
pump
room stat seems to trip in and out ok
im thinking i have a problem with the programmer because when i have it on
hot water demand it works fine boiler fires up and pipes in the airing
cupboard get hot
when I put the demand onto central heating light on the programmer come on
but no response at the boiler
when i make a demand for hot water and central heating ,boiler fires up
both motorised valves move and all pipes in the airing cupboard get hot
what do you think
thanks Tony







--




  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1
Default Hot water but no central heating

On 23/12/2014 23:44, TONY wrote:
|
| John Rumm - john(at)internode(dot)co(dot)uk |
================================================== ===============/

Hi John
Thanks for the reply the boiler is a glow-worm flexicom system boiler
its on a S plan
i have checked the valves and they seem to be working ok and so dose the
pump
room stat seems to trip in and out ok
im thinking i have a problem with the programmer because when i have it on
hot water demand it works fine boiler fires up and pipes in the airing
cupboard get hot
when I put the demand onto central heating light on the programmer come on
but no response at the boiler
when i make a demand for hot water and central heating ,boiler fires up
both motorised valves move and all pipes in the airing cupboard get hot
what do you think thanks Tony

sounds more like the micro switch in the ch motorised valve at fault.
Find a wiring diagram for the valve and a multimeter,

  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4,120
Default Hot water but no central heating

On 24/12/2014 00:44, Bob wrote:
On 23/12/2014 23:44, TONY wrote:
|
| John Rumm - john(at)internode(dot)co(dot)uk |
================================================== ===============/

Hi John
Thanks for the reply the boiler is a glow-worm flexicom system boiler
its on a S plan
i have checked the valves and they seem to be working ok and so dose the
pump
room stat seems to trip in and out ok
im thinking i have a problem with the programmer because when i have
it on
hot water demand it works fine boiler fires up and pipes in the airing
cupboard get hot
when I put the demand onto central heating light on the programmer
come on
but no response at the boiler
when i make a demand for hot water and central heating ,boiler fires up
both motorised valves move and all pipes in the airing cupboard get hot
what do you think thanks Tony

sounds more like the micro switch in the ch motorised valve at fault.
Find a wiring diagram for the valve and a multimeter,


Agreed. Either the micro-switch has failed, or the valve is opening -
but not far enough to operate the micro-switch.
--
Cheers,
Roger
____________
Please reply to Newsgroup. Whilst email address is valid, it is seldom
checked.
  #8   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 395
Default Hot water but no central heating

TONY posted
replying to Bob , TONY wrote:
bob wrote:

|
sounds more like the micro switch in the ch motorised valve at fault.
Find a wiring diagram for the valve and a multimeter,


Hi Bob
yes your right i found that the micro switch on the ch valve was at fault
ive changed it over and all is working well now.


How do you mean, changed it over - swapped in a new one? How did you do
that? It looks easier said than done on a Honeywell 3-way motorised
valve.


--
Les
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Central heating - heating comes on even though only water on(according to controller) paulfoel UK diy 3 July 29th 13 08:28 PM
only hot water when central heating on andymac147 UK diy 2 June 20th 06 09:05 AM
Central heating OK but no hot water Kevsy1 UK diy 7 October 2nd 05 10:02 PM
Alternatives to gas for central heating and domestic water heating? Jimmy UK diy 55 January 16th 05 12:49 PM
hot water but no Central Heating Wngstr UK diy 2 October 27th 04 08:46 PM


All times are GMT +1. The time now is 10:19 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"