Default "rear cable entry" outside lights

What's the correct way to mount a " rear cable entry" outside wall light when the existing cable is surface mounted?
Cheers
Jim K
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,688
Default "rear cable entry" outside lights

On Tuesday, November 6, 2012 9:45:26 AM UTC, Jim K wrote:
What's the correct way to mount a " rear cable entry" outside wall light when the existing cable is surface mounted?

Cheers

Jim K


When I was considering something like this a while ago (I never got round to it) the ideas I mulled on we

1. Dig out some mortar and loop the cable behind, but whether that is possible depends on the location, size of fitting, bend radius of cable, etc.

2. Mount it on a thin box and make the connection in there (probably not pretty)

3. Cut a side entry hole and fit some type of rubber bush or grommet.

4. I've seen one mounted on two timber battens on the side of a barn which looked crap, but it was on a barn !

5. Move the cable (but that's not what you asked) !

I'm not sure what the "correct" or "standard" way is.

Simon.
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,944
Default "rear cable entry" outside lights

On Tue, 6 Nov 2012 02:39:53 -0800 (PST)
sm_jamieson wrote:

On Tuesday, November 6, 2012 9:45:26 AM UTC, Jim K wrote:
What's the correct way to mount a " rear cable entry" outside wall
light when the existing cable is surface mounted?

Cheers

Jim K


When I was considering something like this a while ago (I never got
round to it) the ideas I mulled on we

1. Dig out some mortar and loop the cable behind, but whether that is
possible depends on the location, size of fitting, bend radius of
cable, etc.

2. Mount it on a thin box and make the connection in there (probably
not pretty)

3. Cut a side entry hole and fit some type of rubber bush or grommet.

4. I've seen one mounted on two timber battens on the side of a barn
which looked crap, but it was on a barn !

5. Move the cable (but that's not what you asked) !

I'm not sure what the "correct" or "standard" way is.

Simon.


I am not a professional, but I did exactly 3 above, and it works, and
doesn't look bad.
--
Davey.
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,112
Default "rear cable entry" outside lights

On 06/11/2012 12:21, Davey wrote:
On Tue, 6 Nov 2012 02:39:53 -0800 (PST)
sm_jamieson wrote:

On Tuesday, November 6, 2012 9:45:26 AM UTC, Jim K wrote:
What's the correct way to mount a " rear cable entry" outside wall
light when the existing cable is surface mounted?

Cheers

Jim K


When I was considering something like this a while ago (I never got
round to it) the ideas I mulled on we

1. Dig out some mortar and loop the cable behind, but whether that is
possible depends on the location, size of fitting, bend radius of
cable, etc.

2. Mount it on a thin box and make the connection in there (probably
not pretty)

3. Cut a side entry hole and fit some type of rubber bush or grommet.

4. I've seen one mounted on two timber battens on the side of a barn
which looked crap, but it was on a barn !

5. Move the cable (but that's not what you asked) !

I'm not sure what the "correct" or "standard" way is.

Simon.


I am not a professional, but I did exactly 3 above, and it works, and
doesn't look bad.


Most light fittings have a slight "standoff" at the screw holes, just
about enough to clear 1 mm T&E. If coming up from below, I'd just add a
blob of silicone if plastic, or rubber grommet plus silicone if not.

If wire comes down from above, you don't want it to have any chance of
draining water into the light. You could increase the standoff slightly
using washers or grommets on the screws, then arrange the feed to have a
loop below the inlet hole, then seal as described.

Sometimes worth having a drain hole at the bottom of the light fitting
anyway.

  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 6,766
Default "rear cable entry" outside lights

newshound laid this down on his screen :
Sometimes worth having a drain hole at the bottom of the light fitting
anyway.


Always worth having a drain hole at the lowest point!

--
Regards,
Harry (M1BYT) (L)
http://www.ukradioamateur.co.uk




  #6   Report Post  
Posted to uk.d-i-y
ARW ARW is offline
external usenet poster
 
Posts: 10,161
Default "rear cable entry" outside lights

sm_jamieson wrote:
On Tuesday, November 6, 2012 9:45:26 AM UTC, Jim K wrote:
What's the correct way to mount a " rear cable entry" outside wall
light when the existing cable is surface mounted?

Cheers

Jim K


When I was considering something like this a while ago (I never got
round to it) the ideas I mulled on we

1. Dig out some mortar and loop the cable behind, but whether that is
possible depends on the location, size of fitting, bend radius of
cable, etc.

2. Mount it on a thin box and make the connection in there (probably
not pretty)

3. Cut a side entry hole and fit some type of rubber bush or grommet.

4. I've seen one mounted on two timber battens on the side of a barn
which looked crap, but it was on a barn !

5. Move the cable (but that's not what you asked) !

I'm not sure what the "correct" or "standard" way is.


I would not have a problem with any of those suggestions.

--
Adam


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Xpelair GXC6 rear cable entry Mike Clarke UK diy 6 June 24th 09 09:38 PM
Do you like "warm" lights or "cool" new ones? RPS Home Repair 7 April 23rd 08 01:44 AM
Do you like "warm" lights or "cool" new ones? RPS Home Ownership 9 April 23rd 08 01:44 AM
"Entry Level" what does that mean? HVAC question... Stevey Sandlin Home Repair 6 September 26th 06 11:55 AM
Yellow/bluw "ghost" in SONY 53'' XBR45 (rear projection unit) Cooldmitriy Electronics Repair 4 October 24th 05 08:16 PM


All times are GMT +1. The time now is 12:30 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"