Barry Ashcroft
 
Posts: n/a
Default Central Heating Problem

Hi All,

I have an interesting problem that has just started with my CH system. I'll
explain what I know about the system.

In the airing cupboard I have a copper tank which I assume feeds the system.
Beneaf this there is a big insulated tank. The only pipe linking these two
is an overflow from the insulated tank which enters at the top. The copper
tank has a cold water feed operated with a ball cock, again at the top. At
abou the same height there is an overflow pipe. There is also another pipe
which exits the tank at the bottow and leads to somewhere else.

I have a boiler in the kitchen (ideal elan 2) which has two pipe
enterting/exiting the top of the boiler. I assume that the pipe leading off
from the copper tank goes to the boiler but I may be wrong with this.

The problem I am experienceing is that the copper tank is filling and
overflowing. My initial thought was that the ball cock was faulty. I
replaced this but the problem has persisted, the ball cock is not at fault.
The water seems to enter the copper tank through the bottom pipe, and the
water is a dirty sandy color.

Has anyone any idea what could be causing this to happen. Has anyone got a
electronic copy of a manual or schematic for the boiler or CH diagrams that
I can use to try trouble shoot the problem.

Many thanks

Barry.


  #2   Report Post  
Roger Mills
 
Posts: n/a
Default Central Heating Problem


"Barry Ashcroft" wrote in message
news
Hi All,

I have an interesting problem that has just started with my CH system.

I'll
explain what I know about the system.

In the airing cupboard I have a copper tank which I assume feeds the

system.
Beneaf this there is a big insulated tank. The only pipe linking these two
is an overflow from the insulated tank which enters at the top. The copper
tank has a cold water feed operated with a ball cock, again at the top. At
abou the same height there is an overflow pipe. There is also another pipe
which exits the tank at the bottow and leads to somewhere else.

I have a boiler in the kitchen (ideal elan 2) which has two pipe
enterting/exiting the top of the boiler. I assume that the pipe leading

off
from the copper tank goes to the boiler but I may be wrong with this.

The problem I am experienceing is that the copper tank is filling and
overflowing. My initial thought was that the ball cock was faulty. I
replaced this but the problem has persisted, the ball cock is not at

fault.
The water seems to enter the copper tank through the bottom pipe, and the
water is a dirty sandy color.

Has anyone any idea what could be causing this to happen. Has anyone got a
electronic copy of a manual or schematic for the boiler or CH diagrams

that
I can use to try trouble shoot the problem.

Many thanks

Barry.



I presume that you have also got a smaller header tank in the attic - which
acts as a fill and expansion tank for the primary circuit?

Your insulated tank holds your domestic hot water - which is heated by water
from the boiler which passes through a heat exchanger coil inside the tank.
The water in the primary circuit (i.e. the loop which goes to the boiler) is
not supposed to mix with your domestic hot water - with heat transfer taking
place through this sealed coil.

Your problem is that this sealed coil is leaking inside your tank. The
greater static pressure generated by your header tank in the attic is
forcing primary water (which is horrible grotty stuff which has picked up
all sorts of corrosion from your radiators) to mix with your domestic hot
water - which in turn is overflowing into what you describe as your copper
tank.

If my diagnosis is correct - and I'm 99% confident that it is - you'll need
to replace your insulated hot water cylinder. You can d-i-y this, if you
know what you are doing - the tank itself costs about £85 from ScrewFix.

HTH,
Roger


  #3   Report Post  
Jonathan Curtis
 
Posts: n/a
Default Central Heating Problem

To check, turn off mains, put hot water taps on, level of tank in the
attic should go down.

Jon


--
Posted via Mailgate.ORG Server - http://www.Mailgate.ORG
  #4   Report Post  
Christian McArdle
 
Posts: n/a
Default Central Heating Problem

The water seems to enter the copper tank through the bottom pipe, and the
water is a dirty sandy color.


Probably a heat exchanger coil leak in the cylinder. This can only be fixed
by replacement.

Christian.



Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Central Heating valve problem. TerenceBooth UK diy 2 October 21st 03 12:34 PM
Central Heating - Serious Air Ingress Problem hodihouk UK diy 2 October 10th 03 01:05 PM
Central Heating - Problem with 3 way valve wiring. John UK diy 1 October 3rd 03 06:28 PM
Central Heating problem - 2A fuse blowing in honeywell wiring box Andy Hall UK diy 9 September 30th 03 09:29 PM
Pool water in central heating system Andy Hall UK diy 1 September 2nd 03 05:01 PM


All times are GMT +1. The time now is 10:42 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"