Combi boiler - tepid water unless central heating running.
The hot water never gets piping hot but if the central heating is running
too, the radiators are almost too hot to touch and the hot water gets that way too. Is this the diverter valve at fault - do I need a man in? What else might it be? Geoff |
#2
Posted to uk.d-i-y
|
|||
|
|||
Combi boiler - tepid water unless central heating running.
On 10/10/2012 17:21, Geoff Pearson wrote:
The hot water never gets piping hot but if the central heating is running too, the radiators are almost too hot to touch and the hot water gets that way too. Is this the diverter valve at fault - do I need a man in? What else might it be? What make / model of boiler? What power output? Does the boiler fire up and keep running if you use just the hot water? Does the temperature increase if you reduce the flow rate? -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ |
#3
Posted to uk.d-i-y
|
|||
|
|||
Combi boiler - tepid water unless central heating running.
"John Rumm" wrote in message o.uk... On 10/10/2012 17:21, Geoff Pearson wrote: The hot water never gets piping hot but if the central heating is running too, the radiators are almost too hot to touch and the hot water gets that way too. Is this the diverter valve at fault - do I need a man in? What else might it be? What make / model of boiler? What power output? Does the boiler fire up and keep running if you use just the hot water? Does the temperature increase if you reduce the flow rate? -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ Does the boiler fire up and keep running if you use just the hot water? ------------------ Yes Does the temperature increase if you reduce the flow rate? ------------------------------No What make / model of boiler? What power output? ------------------------------------------I will check and report. Thanks for taking an interest. |
#4
Posted to uk.d-i-y
|
|||
|
|||
Combi boiler - tepid water unless central heating running.
On 11/10/2012 01:08, Geoff Pearson wrote:
Does the boiler fire up and keep running if you use just the hot water? ------------------ Yes Bonus question, if you keep the hot water running does the rad circuit heat up? (feeling the flow pipe out of the boiler should tell you). -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ |
#5
Posted to uk.d-i-y
|
|||
|
|||
Combi boiler - tepid water unless central heating running.
"John Rumm" wrote in message o.uk... On 11/10/2012 01:08, Geoff Pearson wrote: Does the boiler fire up and keep running if you use just the hot water? ------------------ Yes Bonus question, if you keep the hot water running does the rad circuit heat up? (feeling the flow pipe out of the boiler should tell you). -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ I will check and report - it is my nephew's boiler at the other side of the city. |
#6
Posted to uk.d-i-y
|
|||
|
|||
Combi boiler - tepid water unless central heating running.
"Geoff Pearson" wrote in message ... "John Rumm" wrote in message o.uk... On 10/10/2012 17:21, Geoff Pearson wrote: The hot water never gets piping hot but if the central heating is running too, the radiators are almost too hot to touch and the hot water gets that way too. Is this the diverter valve at fault - do I need a man in? What else might it be? What make / model of boiler? What power output? Does the boiler fire up and keep running if you use just the hot water? Does the temperature increase if you reduce the flow rate? -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ Does the boiler fire up and keep running if you use just the hot water? ------------------ Yes Does the temperature increase if you reduce the flow rate? ------------------------------No What make / model of boiler? What power output? ------------------------------------------I will check and report. Thanks for taking an interest. It is a Glowworm Compact Electronic - no rating marked. Need to do more testing of options.. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Central heating pump running and sometimes the boiler too when H/W &C/H turned off. | UK diy | |||
central heating combi boiler | Home Repair | |||
Running a combination boiler without central heating connected? | UK diy | |||
Complicated central Heating; Back-Boiler and Combi-Boiler | UK diy | |||
central heating combi boiler | UK diy |