Default CM Zone kicks in even with the reads set to off

I posted to automated homes, but thought I would ask here too.

The HC60NG has decided to cycle 6 times an hour (it should not be firing
at all, and that's more than the 3 cph that I have configured it). You
can set your watch with it, it fires at xx:y8:55 and it lasts 90 seconds
(though minimum on time is set to 3 mins). That's with the CM67z set to
OFF and also with its usual, low set-points (14 and 13.5).

Things I tried:

- Checked rads; other than the bypass (no HR80UK) all cold.

- Pressed HC60NG button for 15 seconds, then again for 5 and synced with
the CM67z; the red light went off and the boiler kicked in.

- Checked the CM67z parameters, in particular:
. 7:PE 0 (disabled)
. 15:OP 0 (used to be enabled and I had no probs; disabling did not
fix it)
. 16:LC 0 (relay OFF)
. 17:SU (actually 13:SU in my case): 0 (HR80UK enabled) and 2 (both
HR80UK and HC60NG enabled) made no difference; 0 is my usual.
- 6:tS is 2 (enabled for display and control)

I will try to go around the house and remove the batteries from the
HR80UKs to see if I can eliminate it.

Any thought on how to address the dreaded problem will be most appreciated.

Thanks,

Kostas

--
Emails to this address are dropped.
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 55
Default CM Zone kicks in even with the reads set to off

On 17/09/2011 13:16, Kostas Kavoussanakis wrote:
I posted to automated homes, but thought I would ask here too.

The HC60NG has decided to cycle 6 times an hour (it should not be firing
at all, and that's more than the 3 cph that I have configured it). You
can set your watch with it, it fires at xx:y8:55 and it lasts 90 seconds
(though minimum on time is set to 3 mins). That's with the CM67z set to
OFF and also with its usual, low set-points (14 and 13.5).

Things I tried:

- Checked rads; other than the bypass (no HR80UK) all cold.

- Pressed HC60NG button for 15 seconds, then again for 5 and synced with
the CM67z; the red light went off and the boiler kicked in.

- Checked the CM67z parameters, in particular:
. 7:PE 0 (disabled)
. 15:OP 0 (used to be enabled and I had no probs; disabling did not fix it)
. 16:LC 0 (relay OFF)
. 17:SU (actually 13:SU in my case): 0 (HR80UK enabled) and 2 (both
HR80UK and HC60NG enabled) made no difference; 0 is my usual.
- 6:tS is 2 (enabled for display and control)

I will try to go around the house and remove the batteries from the
HR80UKs to see if I can eliminate it.

Any thought on how to address the dreaded problem will be most appreciated.


Caught it: HR80UK was not seated properly.

Kostas

--
Emails to this address are dropped.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Drive reads CD but not DVD [email protected] Electronics Repair 6 July 16th 07 05:25 PM
Nice Reads [email protected] Home Repair 0 February 11th 07 03:51 PM
OT Who reads this forum? Johnson Home Repair 52 August 18th 04 02:04 AM
thermostat compatibility for 2 zone hot water heating w/o zone valves Glacier Home Ownership 1 September 26th 03 02:01 AM


All times are GMT +1. The time now is 05:24 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"